D
R
A
F
T
Micropilot FMR53, FMR54
26
V. 1, Rev. 7, 26-10-2012
Hauser
"Power Supply, Output"
1)
"Approval"
2)
Terminal voltage U at the
device
Maximum load R, depending on the supply voltage U
0
at the
supply unit
C:
2-wire; 4-20mA HART, 4-20mA any
12 to 30 V
3)
R [
]
?
U0 [V]
10
12
23
20
30
0
500
A0017055
1)
Feature 020 of the product structure
2)
Feature 010 of the product structure
3)
For ambient temperatures T
a
£
-30 °C (-22 °F) a minimum voltage of 16 V is required for the satrtup of the device at the MIN error current (3.6 mA).
Polarity reversal protection
Yes
Admissible residual ripple
at f = 0 to 100 Hz
U
SS
< 1 V
Admissible residual ripple
at f = 100 to 10000 Hz
U
SS
< 10 mV