background image

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

Operating menu

Hauser

153

"Safety settings" submenu

Navigation

 Setup → Advanced setup → Safety sett.

Output echo lost

Navigation

 Setup → Advanced setup → Safety sett. → Output echo lost

Description

Define the behavior of the output signal in case of a lost echo.

Selection

• Last valid value

• Ramp at echo lost

• Value echo lost

• Alarm

Factory setting

Last valid value

Additional information

Meaning of the options

Last valid value

The last valid value is kept in the case of a lost echo.

Ramp at echo lost

In the case of a lost echo the output value is continously shifted towards 0% or 100%.

The slope of the ramp is defined in the 

Ramp at echo lost

 parameter (→   154).

Value echo lost

In the case of a lost echo the output assumes the value defined in the 

Value echo lost

parameter (→   153).

Alarm

In the case of a lost echo the device generates an alarm; see the 

Failure mode

 parameter

Value echo lost

Navigation

 Setup → Advanced setup → Safety sett. → Value echo lost

Prerequisite

Output echo lost (→   153)

 = 

Value echo lost

Description

Define output value in case of a lost echo.

User entry

0 to 200

 

000.0 %

Factory setting

0.0 %

Additional information

Use the unit which has been defined for the measured value output:

• without linearization: 

Level unit (→   140)

• with linearization: 

Unit after linearization (→   147)

Summary of Contents for Micropilot FMR51

Page 1: ...Products Solutions Services Operating Instructions Micropilot FMR51 FMR52 FOUNDATION Fieldbus Free space radar BA01121F 00 EN 03 16 71344019 01 01 zz Device firmware ...

Page 2: ...2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 ...

Page 3: ... 1 Horn antenna FMR51 26 6 4 2 Mesurement from the outside through plastic walls FMR50 FMR51 28 6 4 3 Horn antenna flush mount FMR52 29 6 5 Installation in stilling well 30 6 5 1 Recommendations for the stilling well 30 6 5 2 Examples for the construction of stilling wells 31 6 6 Installation in bypass 32 6 6 1 Recommendations for the bypass pipe 32 6 6 2 Example for the construction of a bypass 3...

Page 4: ...guration 81 12 2 1 Preparatory steps 81 12 2 2 Configuring the Resource Block 81 12 2 3 Configuring the Transducer Blocks 81 12 2 4 Configuring the Analog Input Blocks 82 12 2 5 Additional configuration 82 12 3 Scaling of the measured value in an AI Block 82 12 4 Language selection 83 12 5 Configuration of a level measurement 84 12 6 Configuration of the on site display 85 12 6 1 Factory settings ...

Page 5: ...es 113 16 4 System components 113 17 Operating menu 114 17 1 Overview of the operating menu display module 114 17 2 Overview of the operating menu operating tool 120 17 3 Setup menu 126 17 3 1 Mapping wizard 133 17 3 2 Analog input 1 to 5 submenu 134 17 3 3 Advanced setup submenu 136 17 4 Diagnostics menu 174 17 4 1 Diagnostic list submenu 176 17 4 2 Event logbook submenu 177 17 4 3 Device informa...

Page 6: ...n Failure to avoid this situation can result in serious or fatal injury CAUTION CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE NOTE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Symbol Meaning Direct current Alternating current Direct...

Page 7: ...tted Procedures processes or actions that are permitted Preferred Procedures processes or actions that are preferred Forbidden Procedures processes or actions that are forbidden Tip Indicates additional information Reference to documentation A Reference to page Reference to graphic Notice or individual step to be observed 1 2 3 Series of steps Result of a step Help in the event of a problem Visual...

Page 8: ...l the essential information from incoming acceptance to initial commissioning Description of Device Parameters GP01017F FMR5x FOUNDATION Fieldbus Reference for your parameters The document provides a detailed explanation of each individual parameter in the operating menu The description is aimed at those who work with the device over the entire life cycle and perform specific configurations Specia...

Page 9: ...A00692F XA00684F B4 ATEX II 1 2 G Ex ia IIC T6 T1 Ga Gb ATEX II 1 2 G Ex d ia IIC T6 T1 Ga Gb FMR51 FMR52 XA00681F XA00681F XA00681F XA00689F CD CSA C US DIP Cl II III Div 1 Gr E G FMR51 XA01113F XA01113F XA01113F XA01115F XA01113F C2 CSA C US IS Cl I II III Div 1 Gr A G NI Cl 1 Div 2 Ex ia FMR51 FMR52 XA01112F XA01112F XA01112F XA01114F C3 CSA C US XP Cl I II III Div 1 Gr A G NI Cl 1 Div 2 Ex d F...

Page 10: ... Ga FMR51 FMR52 XA01199F XA01199F XA01199F XA01208F NB NEPSI Ex ia IIC T6 Ga Gb FMR51 FMR52 XA01199F XA01199F XA01199F XA01208F NC NEPSI Ex d ia IIC T6 Ga Gb FMR51 FMR52 XA01202F XA01202F XA01202F XA01211F XA01202F NG NEPSI Ex nA II T6 Gc FMR51 FMR52 XA01201F XA01201F XA01201F XA01210F XA01201F NH NEPSI Ex ic IIC T6 Gc FMR51 FMR52 XA01201F XA01201F XA01201F XA01210F XA01201F N2 NEPSI Ex ia IIC T6 ...

Page 11: ... Ga IIC T6 T1 Gc BH L or M ATEX II 3G Ex ic ia Ga IIC T6 T1 Gc B3 L or M ATEX II 1 2G Ex d ia IIC T6 T1 Ga Gb ATEX II 1 2D Ex ta ia Db IIIC Txx C Da Db IG L or M IECEx Ex nA ia Ga IIC T6 T1 Gc IH L or M IECEx Ex ic ia Ga IIC T6 T1 Gc I3 L or M IECEx Ex d ia IIC T6 T1 Ga Gb IECEx Ex ta ia Db IIIC Txx C Da Db MH L or M Ex ic ia Ga IIC T6 Gc NG L or M NEPSI Ex nA ia Ga IIC T6 T1 Gc NH L or M NEPSI Ex...

Page 12: ...for the version with advanced dynamics maximum pulse power 23 3 mW average power 0 076 mW Operation is completely harmless to humans and animals Observing the limit values specified in the Technical data and listed in the Operating Instructions and supplementary documentation the measuring device may be used for the following measurements only Measured process variables level distance signal stren...

Page 13: ... To eliminate a danger for persons or for the facility when the device is used in the hazardous area e g explosion protection pressure vessel safety Based on the nameplate check whether the ordered device is permitted for the intended use in the hazardous area Observe the specifications in the separate supplementary documentation that is an integral part of these Instructions 2 5 Product safety Th...

Page 14: ... 1 1 2 3 3 3 5 4 1 A0016818 1 Design of the Micropilot FMR51 26 GHz 1 Electronics housing 2 Process connection Thread 3 Horn antenna 4 Flange 5 Antenna extension 3 1 2 Micropilot FMR52 1 1 1 2 3 5 4 4 4 A0016788 2 Design of the Micropilot FMR52 26 GHz 1 Electronics housing 2 Tri Clamp process connection 3 Dairy coupling 4 PTFE cladding 5 Flange ...

Page 15: ...2 3 4 5 6 9 7 8 A0012422 3 Design of the electronics housing 1 Electronics compartment cover 2 Display module 3 Main electronics module 4 Cable glands 1 or 2 depending on instrument version 5 Nameplate 6 I O electronics module 7 Terminals pluggable spring terminals 8 Connection compartment cover 9 Grounding terminal ...

Page 16: ...ks FOUNDATIONTM Fieldbus Registered trademark of the FieldComm Group Austin Texas USA KALREZ VITON Registered trademark of DuPont Performance Elastomers L L C Wilmington USA TEFLON Registered trademark of E I DuPont de Nemours Co Wilmington USA TRI CLAMP Registered trademark of Alfa Laval Inc Kenosha USA ...

Page 17: ...esent If required see nameplate Are the Safety Instructions XA present If one of these conditions is not satisfied contact your Endress Hauser Sales Center 4 2 Product identification The following options are available for identification of the measuring device Nameplate specifications Extended order code with breakdown of the device features on the delivery note Enter serial numbers from nameplat...

Page 18: ...a length only for FMR51 with antenna extension 8 Certificate symbol 9 Certificate and approval relevant data 10 Degree of protection e g IP NEMA 11 Document number of the Safety Instructions e g XA ZD ZE 12 Data Matrix Code 13 Modification mark 14 Manufacturing date year month 15 Temperature resistance of the cable 16 Geräterevision Dev Rev 17 Additional information about the device version certif...

Page 19: ...horn may be damaged or break away Risk of injury Transport the measuring device to the measuring point in its original packaging or at the process connection Do not fasten lifting devices hoisting slings lifting eyes etc at the housing or the antenna horn but at the process connection Take into account the mass center of the device in order to avoid unintended tilting Comply with the safety instru...

Page 20: ...ecommended distance A from wall to outer edge of nozzle 1 6 of tank diameter Nevertheless the device should not be installed closer than 15 cm 5 91 in to the tank wall Not in the center 2 as interference can cause signal loss Not above the fill stream 3 It is recommended to us a weather protection cover 1 in order to protect the device from direct sun or rain ...

Page 21: ... any installations point level switches temperature sensors braces vacuum rings heating coils baffles etc inside the signal beam Take into account the beam angle 23 6 1 3 Reduction of interference echoes A0016890 Metallic screens mounted at a slope spread the radar signal and can therefore reduce interference echoes ...

Page 22: ... Endress Hauser for further information 2 3 1 A0017123 6 1 5 Optimization options Antenna size The bigger the antenna the smaller the beam angle α and the fewer interference echoes 23 Mapping The measurement can be optimized by means of electronic suppression of interference echoes See the Confirm distance parameter 130 for details Antenna alignment Take into account the marker on the flange or th...

Page 23: ... 4 in Beam angle α 23 18 10 8 Measuring distance D Beamwidth diameter W 3 m 9 8 ft 1 22 m 4 ft 0 95 m 3 1 ft 0 53 m 1 7 ft 0 42 m 1 4 ft 6 m 20 ft 2 44 m 8 ft 1 9 m 6 2 ft 1 05 m 3 4 ft 0 84 m 2 8 ft 9 m 30 ft 3 66 m 12 ft 2 85 m 9 4 ft 1 58 m 5 2 ft 1 26 m 4 1 ft 12 m 39 ft 4 88 m 16 ft 3 80 m 12 ft 2 1 m 6 9 ft 1 68 m 5 5 ft 15 m 49 ft 6 1 m 20 ft 4 75 m 16 ft 2 63 m 8 6 ft 2 10 m 6 9 ft 20 m 66...

Page 24: ...ts the tank bottom Particularly with dish bottoms or conical outlets the level cannot be detected below this point In stilling well applications the electromagnetic waves do not propagate completely outside the tube It must be taken into account that the accuracy may be reduced in the area C In order to guarantee the required accuracy in these cases it is recommended to position the zero point at ...

Page 25: ... required torque see table Retighten the screws after 24 hours or after the first temperature cycle Depending on process pressure and process temperature check and retighten the screws at regular intervals Usually the PTFE flange cladding also serves as a seal between the nozzle and the device flange Flange size Number of screws Recommended torque Nm minimum maximum EN DN50 PN16 4 45 65 DN80 PN16 ...

Page 26: ...ge may be reduced if the horn antenna is not vertically aligned A marking at the flange somewhere between the flange holes or the boss enables alignment of the antenna This marking must be aligned towards the tank wall as well as possible 9 0 9 0 90 90 90 90 90 90 9 0 9 0 A B A0018974 Depending on the device version the marking may be a circle or two short parallel lines Nozzle mounting For optimu...

Page 27: ...orn 100mm 4 282 mm 11 1 in 1 Feature 070 of the product structure Conditions for longer nozzles If the medium has good reflective properties higher nozzles can be accepted In this case the maximum nozzle height Hmax is dependent on the nozzle diameter D Hmax øD A0023611 Nozzle diameter D Maximum nozzle height Hmax Recommended antenna 1 40 mm 1 5 in 100 mm 3 9 in BA Horn 40mm 1 1 2 50 mm 2 in 150 m...

Page 28: ...may be necessary depending on the antenna size to unmount the horn before fastening the device and to mount it again afterwards Tighten with the hexagonal nut only Tool 55 mm hexagonal wrench Maximum permissible torque 60 Nm 44 lbf ft 6 4 2 Mesurement from the outside through plastic walls FMR50 FMR51 Dielectric constant of the medium εr 10 If possible use an antenna 100 mm 4 in The distance from ...

Page 29: ...l as possible 9 0 9 0 90 90 90 90 90 90 9 0 9 0 A B A0018974 Depending on the device version the marking may be a circle or two short parallel lines Nozzle mounting Hmax A0016819 7 Nozzle height for horn antenna flush mount FMR52 Antenna 1 Maximum nozzle height Hmax BO Horn 50mm 2 500 mm 19 7 in BP Horn 80mm 3 500 mm 19 7 in 1 Feature 070 of the product structure Please contact Endress Hauser for ...

Page 30: ...pipe diameter de burred Length and number do not have any influence on the measurement Select horn antenna as big as possible For intermedaite sizes e g 180 mm 7 in select next larger antenna and adapt it mechanically for horn antennas At any transition i e when using a ball valve or mending pipe segments no gap may be left exceeding 1 mm 0 04 in The stilling well must be smooth on the inside aver...

Page 31: ...icropilot FMR50 FMR51 Horn 40mm 1 B Micropilot FMR50 FMR51 FMR52 FMR54 Horn 80mm 3 C Stilling well with slots D Full bore ball valve 1 Marking for axial alignment 2 Threaded connection 3 e g welding neck flange DIN2633 4 hole max 1 10 stilling well 5 hole max 1 10 stilling well single sided or drilled through 6 Inside of holes deburred 7 Diameter of opening of ball valve must always be equivalent ...

Page 32: ...ccess to the display and the terminal compartment 34 6 6 1 Recommendations for the bypass pipe Metal no plastic or enamel coating Constant diameter Select horn antenna as big as possible For intermediate sizes e g 95 mm 3 5 in select next larger antenna and adapt it mechanically for horn antennas Diameter difference between horn antenna and inner diameter of the bypass as small as possible At any ...

Page 33: ... FMR50 FMR51 FMR52 FMR54 Horn 80mm 3 B Full bore ball valve C Minimum distance to upper connection pipe 400 mm 15 7 in 1 Marking for axial alignment 2 e g welding neck flange DIN2633 3 Diameter of the connection pipes as small as possible 4 Do not weld through the pipe wall the inside of the bypass must remain smooth 5 Diameter of opening of ball valve must always be equivalent to pipe diameter Av...

Page 34: ... radiation or convection The insulation may not exceed beyond the neck of the housing 6 8 Turning the transmitter housing To provide easier access to the connection compartment or display module the transmitter housing can be turned max 350 8 mm 8 mm A0013713 1 Unscrew the securing screw using an open ended wrench 2 Rotate the housing in the desired direction 3 Tighten the securing screw 1 5 Nm fo...

Page 35: ...s module and plug the display module into the electronics compartment until it engages 6 Screw the cover of the electronics compartment firmly back onto the transmitter housing 7 Tighten the securing clamp again using the Allen key Torque 2 5 Nm 6 10 Post installation check Is the device undamaged visual inspection Does the device conform to the measuring point specifications For example Process t...

Page 36: ...06 07 FIELDBUS 1 3 2 4 P A F F 1 0 m m Spare part 71108xxx 2 wire level 4 20 mA PFS FIELDBUS 26 27 open A 4 1 1 2 3 6 5 3 3 4 4 A0011341 10 Terminal assignment PROFIBUS PA FOUNDATION Fieldbus A Without integrated overvoltage protection B With integrated overvoltage protection 1 Cable screen Observe cable specifications 2 Switch output open collector Terminals 3 and 4 3 PROFIBUS PA FOUNDATION Field...

Page 37: ...an external resistor internal resistance of the relay or Pull up resistor of 1000 Ω 7 1 2 Cable specification Devices without integrated overvoltage protection Pluggable spring force terminals for wire cross sections 0 5 to 2 5 mm2 20 to 14 AWG Devices with integrated overvoltage protection Screw terminals for wire cross sections 0 2 to 2 5 mm2 24 to 14 AWG For ambient temperature TU 60 C 140 F us...

Page 38: ...s with fieldbus plug connector M12 or 7 8 the signal line can be connected without opening the housing Pin assignment of the M12 plug connector 2 1 3 4 A0011175 Pin Meaning 1 Signal 2 not connected 3 Signal 4 Ground Pin assignment of the 7 8 plug connector 4 2 3 1 A0011176 Pin Meaning 1 Signal 2 Signal 3 Not connected 4 Screen ...

Page 39: ...liquids which requires the use of overvoltage protection according to DIN EN 60079 14 standard for test procedures 60060 1 10 kA pulse 8 20 μs overvoltage protection has to be ensured by an integrated or external overvoltage protection module Integrated overvoltage protection An integrated overvoltage protection module is available for 2 wire HART as well as PROFIBUS PA and FOUNDATION Fieldbus dev...

Page 40: ...tential bonding line to the exterior ground terminal Required tools and accessories For instruments with safety pin for the lid AF 3 Allen key Wire stripping pliers When using stranded wires Wire end sleeves 1 2 3 10 0 4 10 0 4 mm in 4 5 5 A0012619 1 Loosen the screw of the securing clamp of the connection compartment cover and turn the clamp 90 counterclockwise 2 Unscrew the connection compartmen...

Page 41: ...age protection have pluggable spring force terminals Rigid conductors or flexible conductors with cable sleeve can directly be inserted and are contacted automatically To remove cables from the terminal Press on the groove between the terminals using a flat tip screwdriver 3 mm 0 12 inch while pulling the cables out of the terminals mm in 3 0 12 A0013661 7 3 Post connection check m Are cables or t...

Page 42: ...ss Hauser m If required Is the protective earth connected correctly m If supply voltage is present Is the device ready for operation and do values appear on the display module m Are all housing covers installed and firmly tightened m Is the securing clamp tightened correctly ...

Page 43: ...ambient temperature for the display 20 to 70 C 4 to 158 F The readability of the display may be impaired at temperatures outside the temperature range Operating elements local operation with 3 push buttons external operation via touch control 3 optical keys Operating elements also accessible in various hazardous areas Additional functionality Data backup function The device configuration can be sa...

Page 44: ...play and operating module SD02 push buttons cover must be removed 3 Display and operating module SD03 optical keys can be operated through the glass of the cover 8 1 3 Remote operation Via FOUNDATION Fieldbus FF H1 FF H1 BT BT PS 3 4 PS BT SB BT FF HSE IN LD ENDRESS HAUSER E 1 1 2 2 A0017188 14 FOUNDATION Fieldbus system architecture with associated components 1 FFblue Bluetooth modem 2 Field Xper...

Page 45: ...peed Ethernet FF H1 FOUNDATION Fieldbus H1 LD Linking Device FF HSE FF H1 PS Bus Power Supply SB Safety Barrier BT Bus Terminator Via service interface CDI E 1 2 3 A0014019 1 Service interface CDI of the measuring device Endress Hauser Common Data Interface 2 Commubox FXA291 3 Computer with FieldCare operating tool ...

Page 46: ...all parameters needed to check the measurement capability of the device Heartbeat 3 Contains all wizards for the Heartbeat Verification and Heartbeat Monitoring application packages Expert 4 Contains all parameters of the device including those which are already contained in one of the above submenus This menu is organized according to the function blocks of the device The parameter of the Expert ...

Page 47: ...ocal display from unauthorized access 48 Access authorization to parameters User role Read access Write access Without access code from the factory With access code Without access code from the factory With access code Operator Maintenance If an incorrect access code is entered the user obtains the access rights of the Operator role The user role with which the user is currently logged on is indic...

Page 48: ...ced setup Administration Define access code 2 Define a max 4 digit numeric code as an access code Write protection is active Parameters that can always be changed The write protection does not include certain parameters that do not affect the measurement Despite the defined access code they can always be modified even if the other parameters are locked If no key is pressed for 10 minutes in the na...

Page 49: ... the access code appears 2 Enter the access code The symbol in front of the parameters disappears all previously write protected parameters are now re enabled 8 2 5 Deactivation of the write protection via access code Via local display 1 Navigate to Setup Advanced setup Administration Define access code Define access code 2 Enter 0000 3 Repeat 0000 in Confirm access code parameter The write protec...

Page 50: ...r values are now read only and cannot be edited any more exception Contrast display parameter Via local display Via FOUNDATION Fieldbus E 2 5 Nm 1 84 lbf ft 3 mm XXXXXXXXXXXXX WP CDI SIM ON WP SIM OFF A0021474 1 Loosen the securing clamp 2 Unscrew the housing cover 3 Pull out the display module with a gentle rotation movement To make it easier to access the lock switch attach the display module to...

Page 51: ...addition to this the symbol appears in the header of the measured value display and in the navigation view in front of the parameters XXXX XXX X X 20 50 XX XX A0015870 If the hardware write protection is disabled No option is displayed in the Locking status parameter The symbol disappears in the header of the measured value display and in the navigation view in front of the parameters 5 Feed the s...

Page 52: ...t menu Enabling the keylock For the SD03 display The keylock is automatically activated If the device has not been operated via the display for 1 minute After a restart of the device To activate the keylock manually 1 The device is in the measured value display Press for at least 2 seconds A context menu appears 2 Select Keylock on from the context menu The keylock is enabled When attempting to ac...

Page 53: ... error symbol if an error is active 1 2 Measured value symbols 1 3 Measured value 1 4 Unit 2 Measured value display 1 bargraph 1 value 2 1 Bargraph for measured value 1 2 2 Measured value 1 including unit 2 3 Measured value symbols for measured value 1 2 4 Measured value 2 2 5 Unit for measured value 2 2 6 Measured value symbols for measured value 2 3 Representation of a parameter here a parameter...

Page 54: ...ou are in the Diagnostics menu Status signals A0013956 Failure A device error is present The measured value is no longer valid A0013959 Function check The device is in service mode e g during a simulation A0013958 Out of specification The device is operated Outside of its technical specifications e g during startup or a cleaning Outside of the configuration carried out by the user e g level outsid...

Page 55: ...urrent A0012106 Terminal voltage A0012104 Temperature of the electronics or the sensor Measuring channels A0012000 Measuring channel 1 A0012107 Measuring channel 2 Status of the measured value A0012102 Status Alarm The measurment is interrupted The output assumes the defined alarm value A diagnostic message is generated A0012103 Status Warning The device continues measuring A diagnostic message is...

Page 56: ...unction of the parameter For text and numeric editor Pressing the key briefly Opens the selected group Carries out the selected action Pressing the key for 2 s confirms the edited parameter value A0013971 Escape key combination press keys simultaneously For menu submenu Pressing the key briefly Exits the current menu level and takes you to the next higher level If help text is open closes the help...

Page 57: ...the numeric and text editor Numeric editor symbols Symbol Meaning 0 9 A0013998 Selection of numbers from 0 to 9 A0016619 Inserts decimal separator at the input position A0016620 Inserts minus sign at the input position A0013985 Confirms selection A0016621 Moves the input position one position to the left A0013986 Exits the input without applying the changes A0014040 Clears all entered characters T...

Page 58: ...n tools A0013986 Exits the input without applying the changes A0014040 Clears all entered characters Correction symbols under A0013989 Clears all entered characters A0013991 Moves the input position one position to the right A0013990 Moves the input position one position to the left A0013988 Deletes one character immediately to the left of the input position ...

Page 59: ...p Simulation Calling up and closing the context menu The user is in the operational display 1 Press for 2 s The context menu opens XXXXXXXXXX kg h 20 50 Setup Conf backup disp Simulation A0014003 EN 2 Press simultaneously The context menu is closed and the operational display appears Calling up the menu via the context menu 1 Open the context menu 2 Press to navigate to the desired menu 3 Press to...

Page 60: ...UNDATION Fieldbus 60 Endress Hauser 8 3 5 Envelope curve on the display and operating module In order to assess the measuring signal the envelope curve and if a mapping has been recorded the mapping curve can be displayed E 2s E 2 x E E A0014277 ...

Page 61: ...tion software used When integrating the field devices into the FF system make sure you are using the right files You can read out the required version by means of the Device Revision DEV_REV and DD Revision DD_REV parameters in the Resource Block The device is integrated into the FF network as follows 1 Start the FF configuration program 2 Download the Cff and device description files ffo sym for ...

Page 62: ...ATA_TRANSFER_ TRDHROM xxxxxxxxxxx ANALOG_INPUT_1_ AI xxxxxxxxxxx ANALOG_INPUT_2_ UNK xxxxxxxxxxx DISCRETE_INPUT_ DI xxxxxxxxxxx MULTIPLE_AO_ MAO xxxxxxxxxxx ARITHMETIC_ AR xxxxxxxxxxx INPUT_SELECTOR_ ISEL xxxxxxxxxxx ANALOG_ALARM_ AAL xxxxxxxxxxx PID_ PID xxxxxxxxxxx MULTIPLE_DO_ MDO xxxxxxxxxxx SIGNAL_CHAR_ SC xxxxxxxxxxx INTEGRATOR_ IT xxxxxxxxxxx SERVICE_SENSOR_ TRDSRVSB xxxxxxxxxxx ADV_SETUP_ ...

Page 63: ...tliple Discrete Output Block MDO 1 PID Block PID 1 Arithmetic Block AR 1 Signal Characterizer Block SC 1 Input Selector Block ISEL 1 Integrator Block IT 1 Analog Alarm Block AAL In addition to the pre instantiated blocks already mentioned the following blocks can also be instantiated 3 AI Blocks AI 2 Discrete Input Blocks DI 1 PID Block PID 1 Arithemetic Block AR 1 Signal Characterizer Block SC 1 ...

Page 64: ...Secondary value Distance 9 5 Assignment of the measured values CHANNEL in an AI Block The input value of an Analog Input Block is defined by the CHANNEL parameter Channel Measured value 0 Uninitialized 211 Terminal voltage 773 Analog output advance diagnostics 1 774 Analog output advance diagnostics 2 32786 Absolute echo amplitude 32856 Distance 32885 Elektronic temperature 32949 Level linearized ...

Page 65: ...tance Confirm distance 30 ENUM16 2 Static Maintenance OOS mapping_start_point Mapping start point 31 FLOAT 4 Static Maintenance OOS mapping_end_point Mapping end point 32 FLOAT 4 Static Maintenance OOS end_map_ampl End map amplitude 33 FLOAT 4 Static Maintenance OOS map_end_x Present mapping 34 FLOAT 4 Dynamic map_end_y Map end Y 35 FLOAT 4 Dynamic record_map Record map 36 ENUM16 2 Static Maintena...

Page 66: ...nce OOS table_mode Table mode 33 ENUM16 2 Static Maintenance OOS activate_table Tabelle aktivieren 34 ENUM16 2 Static Maintenance OOS custom_table_sel_level Level 67 FLOAT 4 Static Maintenance OOS custom_table_sel_value Customer value 68 FLOAT 4 Static Maintenance OOS level_semiautomatic Level 69 FLOAT 4 Dynamic output_echo_lost Output echo lost 70 ENUM16 2 Static Maintenance OOS value_echo_lost V...

Page 67: ...2 STRING 12 Static Maintenance AUTO display_separator Separator 33 ENUM16 2 Static Maintenance AUTO number_format Zahlenformat 34 ENUM16 2 Static Maintenance AUTO decimal_places_menu Decimal places menu 35 ENUM16 2 Static Maintenance AUTO contrast_display Contrast display 36 FLOAT 4 Static Operator AUTO backlight Backlight 37 ENUM16 2 Static Operator AUTO operating_time Operating time 38 STRING 14...

Page 68: ...e Last check time 43 STRING 14 Dynamic level_signal Level signal 44 ENUM16 2 Static Development AUTO device_check_timestamp Timestamp 45 UINT32 14 Static Development AUTO assign_channel_1 Assign channel 1 54 ENUM16 2 Static Maintenance AUTO assign_channel_2 Assign channel 2 55 ENUM16 2 Static Maintenance AUTO assign_channel_3 Assign channel 3 56 ENUM16 2 Static Maintenance AUTO assign_channel_4 As...

Page 69: ...tance Sicherheitsdistanz 42 FLOAT 4 Static Maintenance OOS in_safety_distance In safety distance 43 ENUM16 2 Static Maintenance OOS acknowledge_alarm Acknowledge alarm 44 ENUM16 2 Static Maintenance AUTO evaluation_mode Evaluation mode 45 ENUM16 2 Static Maintenance OOS history_reset History reset 46 ENUM16 2 Static Maintenance OOS history_learning_control History learning control 47 ENUM16 2 Stat...

Page 70: ...27 STRING 14 Dynamic reset_min_max_temp Reset min max Temp 28 ENUM16 2 Static Service AUTO used_calculation Used calculation 29 ENUM16 2 Dynamic tank_trace_state Status Tanktrace 30 ENUM16 2 Dynamic max_draining_speed Max draining speed 31 FLOAT 4 Static Development AUTO max_filling_speed Max filling speed 32 FLOAT 4 Static Entwicklung AUTO time_max_level Time max level 33 STRING 14 Dynamic max_le...

Page 71: ...LOAT 4 Dynamic min_value_ad1 Minimum value 1 26 FLOAT 4 Dynamic reset_min_max_ad1 Reset min max 1 27 ENUM16 2 Static Maintenance AUTO assign_status_sig_ad1 Assign status signal to AD event 1 28 ENUM16 2 Static Maintenance OOS assign_event_behaviour_ad1 Assign event behaviourn 1 29 ENUM16 2 Static Maintenance OOS alarm_delay_ad1 Alarm delay 30 FLOAT 4 Static Maintenance OOS assign_diag_ signal_ad2 ...

Page 72: ...s resets the device configuration to a defined state ENP Restart This method is located in the Resource Block and directly prompts the setting of the parameters of the Electronic Name Plate ENP Setup This method is located in the SETUP Transducer Block and allows to set the most important parameters in this block for device configuration measuring units type of tank or vessel type of medium empty ...

Page 73: ...page of the device appears 1 A0027720 1 Commissioning button calls up the wizard 3 Click on Commissioning to call up the wizard 4 Enter or select the appropriate value for each parameter These values are immediately written to the device 5 Click Next to switch to the next page 6 After finishing the last page click End of sequence to close the wizard If the wizard is cancelled before all necessary ...

Page 74: ...easuring point Checklist Post installation check 35 Checklist Post connection check 41 11 2 Setting the operating language Factory setting English or ordered local language XXXX XXX X X 20 50 Operation Setup Main menu 0104 1 Language English Español Français Language English Deutsch à 0104 1 à Español Français Language English Deutsch 0104 1 Betrieb Setup Hauptmenü Sprache Deutsch 0104 1 XX XX A00...

Page 75: ...er of the stilling well or bypass 5 Navigate to Setup Medium group Specify medium group Water based DC 4 or Others 6 Navigate to Setup Empty calibration Enter empty distance E Distance from reference point R to the 0 level 5 7 Navigate to Setup Full calibration Enter full distance F Distance from the 0 to the 100 level 8 Navigate to Setup Level Indicates the measrued level L 9 Navigate to Setup Di...

Page 76: ...ding of an interference echo map 12 When operating via operating tool Navigate to Setup Confirm distance Compare distance indicated on the display to real distance in order to start the recording of an interference echo map 13 Navigate to Setup Advanced setup Level Level unit Select level unit m mm ft in Factory setting The response time of the device is preset by the Tank type parameter 126 More ...

Page 77: ...reference curve parameter Navigation in the menu Expert Diagnostics Envelope diagnostics Save reference curve Meaning of the options No No action Yes The current envelope curve is saved as reference curve In devices which have been delivered with software version 01 00 zz this submenu is only visible for the Service user role The reference curve can only be displayed in the envelope curve diagram ...

Page 78: ...ay 11 5 1 Factory settings of the on site display Parameter Factory setting Format display 1 value max size Value 1 display Level linearized Value 2 display None Value 3 display None Value 4 display None 11 5 2 Adjustment of the on site display The on site display can be adjusted in the following submenu Setup Advanced setup Display ...

Page 79: ...opy comprises the transmitter and sensor data of the device Duplicate The transmitter configuration is duplicated to another device using the transmitter display module The following parameters which characterize the individual measuring point are not included in the transmitted configuration Medium type Compare The device configuration saved in the display module is compared to the current device...

Page 80: ...52 FOUNDATION Fieldbus 80 Endress Hauser 11 7 Protection of the settings against unauthorized changes There are two ways to protect the settings against unauthorized changes Via parameter settings software locking 48 Via locking switch hardware locking 50 ...

Page 81: ...evice by means of the Pd tag FF_PD_TAG parameter 12 2 2 Configuring the Resource Block 1 Open the Resource Block 2 If necessary disable the lock for device operation 3 If necessary change the block name Factory setting RS xxxxxxxxxxx RB2 4 If necessary assign a description to the block by means of the Tag Description TAG_DESC parameter 5 If necessary change other parameters as per the requirements...

Page 82: ...T_SCALE parameters are the same for the Direct linearization type If the values and units do not match the Block Error BLOCK_ERR parameter reports Block Configuration Error and the block mode cannot be set to Auto 6 Enter the alarm and critical alarm messages by means of the High High Limit HI_HI_LIM High Limit HI_LIM Low Low Limit LO_LO_LIM and Low Limit LO_LIM parameters The limit values entered...

Page 83: ...parameters can only be changed in the OOS block mode 12 4 Language selection Step Block Parameter Action 1 DISPLAY TRDDISP Language language Select language 1 Selection 1268 Swedish 32805 Arabian 32824 Chinese simplified 32842 Czech 32881 Dutch 32888 English 32917 French 32920 German 32945 Italian 32946 Japanese 32948 Korean 33026 Polish 33027 Portuguese 33062 Russian 33083 Spanish 33103 Thai 3312...

Page 84: ...TUP TRDSUP Tank type tank_type Select tank type Selection 1271 Process vessel with agitator 1272 Process vessel standard 1273 Storage vessel 1274 Wave guide antenna 1279 Sphere 32816 Bypass pipe 33013 Open channel 33094 Stilling well 3 SETUP TRDSUP Tube diameter tube_diameter 1 Enter the diameter of the bypass or stilling well 4 SETUP TRDSUP Medium group medium_group Select medium group Selection ...

Page 85: ...Value 1 display Level linearized Value 2 display None Value 3 display None Value 4 display None The on site display can be adjusted in the DISPLAY TRDDISP transducer block 12 7 Configuration management After commissioning you can save the current device configuration copy it to another measuring point or restore the previous device configuration You can do so using the Configuration management par...

Page 86: ...vice configuration saved in the display module is compared to the current device configuration of the HistoROM 32848 Clear backup data The backup copy of the device configuration is deleted from the display module of the device HistoROM A HistoROM is a non volatile device memory in the form of an EEPROM While this action is in progress the configuration cannot be edited via the local display and a...

Page 87: ... specification M Maintenance required The diagnostic category of pre defined groups of events can be adjusted by the user according to the requirements of the specific application Certain events can be separated from their group and can be handled individually 941 Echo lost 942 In safety distance 950 Advanced Diagnostic occurred Additional information and remedial measures are transmitted together...

Page 88: ...F282 Data storage F283 Memory content F311 Electronic Failure Configuration 29 F410 Data transfer F435 Linearization F437 Configuration incompatible F482 Block in OOS Process 28 F803 Current loop 1 F825 Current loop 1 F936 EMC interference F941 Echo lost 1 F970 Linearization 1 This event can be removed from the group in order to define its behavior individually see section Configurable area Severi...

Page 89: ...ference S942 In safety distance 1 S943 In blocking distance S944 Level range S968 Level limited 1 This event can be removed from the group in order to define its behavior individually see section Configurable area Severity of the event Default diagnostic category Source of the event Bit Events within the group Lowest severity Maintenance required M Sensor 19 not used in Micropilot Elektronics 18 M...

Page 90: ...the respective event category is assigned to the group The following table represents the default setting of the allocation parameters In the default setting there is a unique relationship between the severity of the event and its category i e its allocation parameter Default setting of the allocation parameters Standard area Configurable area Severity of the event Highest severity High severity L...

Page 91: ...r to be classified as Failure F but as Funcktion check C 1 Use the FieldCare navigation window to navigate to the the following screen Expert Communication Field diagnostics Alarm detection enable 2 22 Default state of the Fail Map and Check Map columns Look for the Configuration Highest Severity group in the Fail Map column and deactivate the associated checkbox A Activate the respective checkbox...

Page 92: ... is transmitted with the event message As a consequence the message will not be recognized by the control system The Alarm detection enable screen is used to configure the detection of diagnostic events but not the transmission of event messages to the bus The latter is configured on the Alarm broadcast enable screen which is operated exactly in the same way as the Alarm detection enable screen St...

Page 93: ...igArea_1 to FF912ConfigArea_15 in the DIAGNOSTIC TRDDIAG block Thereafter the selected bit can be switched from 0 to 1 in the desired allocation parameter Example To change the category of error 942 In safety distance from Out of specification S default to Function check C proceed as follows 1 Use the FieldCare navigation window to navigate to the the following screen Expert Communication Field di...

Page 94: ... 0 for all events The priority can be adjusted individually for each allocation parameter This is done by the following four priority parameters Suppression of individual events For individual events the transmission to the bus can suppressed by the use of a mask The corresponding events will be displayed but not transmitted to the bus In FieldCare this mask can be found at Expert Communication Fi...

Page 95: ...OM port on the computer Check the setting of the COM port on the computer and change it if necessary Device measures incorrectly Parametrization error Check and adjust parameterization 13 1 2 Parametrization errors Error Possible cause Remdy Measured value incorrect If measured distance Setup Distance matches the real distance Calibration error Check and adjust Empty calibration parameter 127 if n...

Page 96: ...ring filling emptying the measxured value jumps downwards Multiple echoes Check Tank type parameter 126 If possible do not select central installation position If appropriate use a stilling well Error message F941 or S941 Echo lost Level echo is too weak Check Medium group parameter 127 If necessary select a more detailed setting in Medium property parameter 138 Optimize alignment of antenna If ne...

Page 97: ...ent text Operating elements Status signals A0013956 Failure A device error is present The measured value is no longer valid A0013959 Function check The device is in service mode e g during a simulation A0013958 Out of specification The device is operated Outside of its technical specifications e g during startup or a cleaning Outside of the configuration carried out by the user e g level outside c...

Page 98: ...ext Example A0013962 A0013958 441 Curr output 1 3 digit number If two or more diagnostic messages are pending simultaneously only the message with the highest priority is shown Additional pending diagnostic messages can be shown in Diagnostic list submenu 176 Past diagnostic messages that are no longer pending are shown as follows On the local display in Event logbook submenu 177 In FieldCare via ...

Page 99: ...nostic behavior with diagnostic code 5 Operation time of occurrence 6 Remedial measures The user is in the diagnostic message 1 Press symbol Diagnostic list submenu opens 2 Select the desired diagnostic event with or and press The message for the remedial measures for the selected diagnostic event opens 3 Press simultaneously The message for the remedial measures closes The user is in the Diagnost...

Page 100: ...Block TRDDIAG The Actual diagnostics parameter displays the message with the highest priority Every message is also output as per the FOUNDATION Fieldbus Specification by means of the XD_ERROR and BLOCK_ERROR parameters A list of diagnostic messages is displayed in the Diagnostics 1 to Diagnostics 5 parameters If more than 5 messages are currently active only those with the highest priority are di...

Page 101: ...73 Main electronic failure 1 Emergency operation via display 2 Change main electronics F Alarm 275 I O module failure Change I O module F Alarm 276 I O module failure 1 Restart device 2 Change I O module F Alarm 282 Data storage 1 Restart device 2 Contact service F Alarm 283 Memory content 1 Transfer data or reset device 2 Contact service F Alarm 311 Electronic failure 1 Transfer data or reset dev...

Page 102: ...Change of reference 1 Check reference configuration 2 Check pressure 3 Check sensor S Warning 941 Echo lost Check parameter DC value F Alarm 1 942 In safety distance 1 Check level 2 Check safety distance 3 Reset self holding S Alarm 1 943 In blocking distance Reduced accuracy Check level S Warning 950 Advanced diagnostic 1 to 2 occured Maintain your diagnostic event M Warning 1 1 Diagnostic behavi...

Page 103: ...eter you can define which category of event messages is displayed in the Event list submenu angezeigt werden Navigation path Diagnostics Event logbook Filter options Filter categories All Failure F Function check C Out of specification S Maintenance required M Information 13 7 3 Overview of information events Info number Info name I1000 Device ok I1089 Power on I1090 Configuration reset I1091 Conf...

Page 104: ...nstructions Description of Parameters Technical Information 06 2012 01 00 zz Original software BA01121F 00 EN 01 13 GP01017F 00 EN 01 13 TI01040F 00 EN 03 13 05 2015 01 01 zz additional languages HistoROM functionality enhanced Improvements and bugfixes BA01121F 00 EN 02 15 BA01121F 00 EN 03 16 1 GP01017F 00 EN 02 15 TI01040F 00 EN 05 15 TI01040F 00 EN 07 16 1 1 contains information on the Heartbe...

Page 105: ...ways use cleaning agents that do not attack the surface of the hosuing and the seals 14 2 Replacing seals The process seals of the sensors at the process connection must be replaced periodically particularly if molded seals aseptic construction are used The period between changes depends on the frequency of cleaning cycles and on the temperature of the measured substance and the cleaning temperatu...

Page 106: ...th identical parts Carry out repairs according to the instructions On completion of repairs carry out the specified routine test on the device Only Endress Hauser Service may convert a certified device into a different certified variant Document all repair work and conversions 15 1 3 Replacement of an electronics module If an electronics module has been replaced it is not necessary to perform a ne...

Page 107: ...ctr Additional information www endress com deviceviewer 71023451 XPF0001 XPF0002 XPF0003 71023451 71023451 71023451 71023451 3 4 1 5 2 6 A0014979 25 Example for spare part nameplate in connection compartment cover Measuring device serial number Is located on the device and spare part nameplate Can be read out via the Serial number parameter in the Device information submenu 15 3 Return The measuri...

Page 108: ...222 8 74 A0015466 298 5 11 8 273 7 10 8 255 1 10 1 5 6 6 1 4 a 164 6 46 b 3 5 6 5 5 5 A0015472 26 Weather protection cover Dimensions mm in a 37 8 mm 1 5 in b 54 mm 2 1 in The weather protection cover can be ordered together with the device product structure feature 620 Accessory Enclosed option PB Weather Protection Cover Alternatively it can be separately ordered as an accessory order code 71162...

Page 109: ... and a FHX50 display is to be retrofitted you must select version B Not prepared for display FHX50 under feature 050 Measuring device version when ordering the FHX50 In this case a retrofit kit for the device is supplied with the FHX50 The kit can be used to prepare the device so that the FHX50 can be used Use of the FHX50 may be restricted for transmitters with an approval A device can only be re...

Page 110: ...orn protection see table below For details refer to mounting instructions SD01084F Process conditions Maximum vessel pressure 0 5 bar 7 252 psi Maximum process temperature 130 C 266 F Danger of explosion Avoid electrostatic charging of the horn protection Horn protection for FMR51 Antenna 1 Order code horn protection Dimensions antenna horn protection L 2 Ød ØD BC Horn 80mm 3 71105890 238 mm 9 4 i...

Page 111: ... A øD ød A0027190 A Antenna extension not supplied with the horn protection B Horn antenna of the Micropilot not supplied with the horn protection C Horn protection d Diameter of horn protection see table below D Minimum nozzle diameter see table below L Length of antenna with horn protection see table below Horn protection for FMR51 with variable antenna extension Antenna 1 Order code horn protec...

Page 112: ...0 71128617 For 2 channel devices feature 020 option B C E or G OVP20 71128619 Hosuing lid for retrofitting In order to keep the necessary safety distances the housing lid needs to be replaced if the device is retrofitted with the overvoltage protection Depending on the housing type the order code of the suitable lid is as follows GT18 housing Lid 71185516 GT19 housing Lid 71185518 GT20 housing Lid...

Page 113: ...les efficient device configuration and diagnostics for HART and FOUNDATION fieldbus devices in the non Ex area and the Ex area For details see Operating Instructions BA01202S 16 3 Service specific accessories Accessory Description FieldCare DeviceCare Endress Hauser s FDT based Plant Asset Management tool Helps to configure and maintain all field devices of your plant By supplying status informati...

Page 114: ...ion Operating menu Language 162 Setup 126 Distance unit 126 Tank type 126 Tube diameter 127 Medium group 127 Empty calibration 127 Full calibration 128 Level 129 Distance 129 Signal quality 130 Mapping 133 Confirm distance 133 Mapping end point 133 Record map 133 Distance 133 Prepare recording map 133 Analog inputs Analog input 1 to 5 134 Block tag 134 ...

Page 115: ...er access code 137 Level 138 Medium type 138 Medium property 138 Max filling speed liquid 139 Max draining speed liquid 139 Advanced process conditions 139 Level unit 140 Blocking distance 141 Level correction 141 Tank silo height 142 Linearization 144 Linearization type 146 Unit after linearization 147 Free text 148 Maximum value 149 Diameter 149 Intermediate height 149 Table mode 150 ...

Page 116: ...ue echo lost 153 Ramp at echo lost 154 Blocking distance 141 Switch output 156 Switch output function 156 Assign status 156 Assign limit 157 Assign diagnostic behavior 157 Switch on value 158 Switch on delay 159 Switch off value 159 Switch off delay 160 Failure mode 160 Switch status 160 Invert output signal 160 Display 162 Language 162 Format display 162 Value 1 to 4 display 164 ...

Page 117: ...66 Decimal places menu 166 Backlight 167 Contrast display 167 Configuration backup display 168 Operating time 168 Last backup 168 Configuration management 168 Comparison result 169 Administration 171 Define access code 173 Define access code 173 Confirm access code 173 Device reset 171 Diagnostics 174 Actual diagnostics 174 Previous diagnostics 174 Operating time from restart 175 Operating time 16...

Page 118: ...Event list 177 Device information 178 Device tag 178 Serial number 178 Firmware version 178 Device name 178 Order code 179 Extended order code 1 to 3 179 Measured values 180 Distance 129 Level linearized 148 Terminal voltage 1 180 Electronic temperature 181 Analog inputs Analog input 1 to 5 181 Block tag 134 Channel 134 Status 182 Value 182 Units index 182 ...

Page 119: ... logging data 184 Display channel 1 to 4 185 Simulation 188 Assign measurement variable 189 Value process variable 189 Switch output simulation 189 Switch status 190 Simulation device alarm 190 Diagnostic event category Simulation diagnostic event Device check 191 Start device check 191 Result device check 191 Last check time 191 Level signal 192 ...

Page 120: ... type 126 Tube diameter 127 Medium group 127 Empty calibration 127 Full calibration 128 Level 129 Distance 129 Signal quality 130 Confirm distance 130 Present mapping 131 Mapping end point 131 Record map 132 Analog inputs Analog input 1 to 5 134 Block tag 134 Channel 134 Process Value Filter Time 135 Advanced setup 136 Locking status 136 Access status tooling 136 Enter access code 137 ...

Page 121: ... liquid 139 Advanced process conditions 139 Level unit 140 Blocking distance 141 Level correction 141 Tank silo height 142 Linearization 144 Linearization type 146 Unit after linearization 147 Free text 148 Level linearized 148 Maximum value 149 Diameter 149 Intermediate height 149 Table mode 150 Table number 151 Level 151 Level 152 Customer value 152 Activate table 152 ...

Page 122: ...utput 156 Switch output function 156 Assign status 156 Assign limit 157 Assign diagnostic behavior 157 Switch on value 158 Switch on delay 159 Switch off value 159 Switch off delay 160 Failure mode 160 Switch status 160 Invert output signal 160 Display 162 Language 162 Format display 162 Value 1 to 4 display 164 Decimal places 1 to 4 164 Display interval 164 Display damping 165 Header 165 ...

Page 123: ...ation backup display 168 Operating time 168 Last backup 168 Configuration management 168 Backup state 169 Comparison result 169 Administration 171 Define access code 173 Device reset 171 Diagnostics 174 Actual diagnostics 174 Timestamp 174 Previous diagnostics 174 Timestamp 175 Operating time from restart 175 Operating time 168 Diagnostic list 176 Diagnostics 1 to 5 176 Timestamp 1 to 5 176 ...

Page 124: ...code 179 Extended order code 1 to 3 179 Measured values 180 Distance 129 Level linearized 148 Terminal voltage 1 180 Electronic temperature 181 Analog inputs Analog input 1 to 5 181 Block tag 134 Channel 134 Status 182 Value 182 Units index 182 Data logging 183 Assign channel 1 to 4 183 Logging interval 183 Clear logging data 184 Simulation 188 Assign measurement variable 189 ...

Page 125: ...dress Hauser 125 Value process variable 189 Switch output simulation 189 Switch status 190 Simulation device alarm 190 Simulation diagnostic event Device check 191 Start device check 191 Result device check 191 Last check time 191 Level signal 192 Heartbeat 193 ...

Page 126: ...tion Setup Distance unit Description Select distance unit Selection SI units mm m US units ft in Factory setting m Tank type Navigation Setup Tank type Prerequisite Medium type 138 Liquid Description Select tank type Selection Bypass pipe Stilling well Workbench test Open channel Sphere Storage vessel Process vessel standard Process vessel with agitator Wave guide antenna Factory setting Depending...

Page 127: ...inition of the DC use the Medium property parameter 138 The Medium group parameter presets the Medium property parameter 138 as follows Medium group Medium property 138 Others Unknown Water based DC 4 DC 4 7 The Medium property parameter can be changed at a later point of time However when doing so the Medium group parameter retains its value Only the Medium property parameter is relevant for the ...

Page 128: ...ts at the point at which the radar beam hits the tank or silo bottom In the case of dished boiler ends or conical outlets levels below this point can not be measured Full calibration Navigation Setup Full calibr Description Specify the distance F between the minimum level 0 and the maximum level 100 User entry Depending on the antenna Factory setting Depending on the antenna Additional information...

Page 129: ...0019482 29 Level in case of liquid measurements The unit is defined in the Level unit parameter 140 Distance Navigation Setup Distance Description Displays the measured distance D between the reference point lower edge of the flange or threaded connection and the level Additional information D A0019483 30 Distance for liquid measurements The unit is defined in the Distance unit parameter 126 ...

Page 130: ...vice generates the following error message F941 for Output echo lost 153 Alarm S941 if another option has been selected in Output echo lost 153 Confirm distance Navigation Setup Confirm distance Description Specify whether the measured distance matches the real distance Depending on the selection the device automatically sets the range of mapping Selection Manual map Distance ok Distance unknown D...

Page 131: ...e into account that in case of conical outlets for example a measurement is only possible up to the point at which the radar hits the bottom of the tank or silo If the Tank empty option is used Empty calibration 127 and Tank silo height may not reach below this point as otherwise the empty signal is suppressed Factory map To be selected if the present mapping curve if one exists is to be deleted T...

Page 132: ...site Confirm distance 130 Manual map or Distance too small Description Start recording of the map Selection No Record map Overlay map Factory map Delete partial map Factory setting No Additional information Meaning of the options No The map is not recorded Record map The map is recorded After the recording is completed the new measured distance and the new mapping range appear on the display When ...

Page 133: ...n the display module at any one time The upper parameter can be edited whereas the lower parameter is displayed for reference purposes only Navigation Setup Mapping Confirm distance Navigation Setup Mapping Confirm distance Description 130 Mapping end point Navigation Setup Mapping Map end point Description 131 Record map Navigation Setup Mapping Record map Description 132 Distance Navigation Setu...

Page 134: ... Setup Analog inputs Analog input 1 to 5 Block tag Navigation Setup Analog inputs Analog input 1 to 5 Block tag Description Defined to be unique throughout the control system at one plant site The tag may be changed using the FB_Tag service Factory setting Channel Navigation Setup Analog inputs Analog input 1 to 5 Channel Description Use this function to select the input value that should be proce...

Page 135: ...og inputs Analog input 1 to 5 PV Filter Time Description Use this function to enter the filter time specification for the filtering of the unconverted input value PV User entry Positive floating point number Factory setting 0 s Additional information Factory setting If the value 0 s is entered filtering will not be performed ...

Page 136: ...ctivated Writing access to the relevant parameters is denied Temporarily locked priority 4 Write access to the parameters is temporarily locked on account of internal processes in progress in the device e g data upload download reset etc The parameters can be modified as soon as the processes are complete On the display module the symbol appears in front of parameters that cannot be modified since...

Page 137: ...king status parameter 136 Enter access code Navigation Setup Advanced setup Ent access code Description Enter access code to disable write protection of parameters User entry 0 to 9999 Additional information For local operation the customer specific access code which has been defined in the Define access code parameter 171 has to be entered If an incorrect access code is entered the user retains h...

Page 138: ... not to change the factory setting Medium property Navigation Setup Advanced setup Level Medium property Description Specify relative dielectric constant εr of the medium Selection Unknown DC 1 4 1 6 DC 1 6 1 9 DC 1 9 2 5 DC 2 5 4 DC 4 7 DC 7 15 DC 15 Factory setting Dependent on Medium type 138 and Medium group 127 Additional information Dependency on Medium type and Medium group Medium type 138 ...

Page 139: ...point of time it may be necessary to repeat the fine adjustment Max draining speed liquid Navigation Setup Advanced setup Level Max drain liquid Prerequisite Medium type 138 Liquid Description Select expected maximum draining speed Selection Slow 1cm 0 4in min Medium 10cm 4in min Standard 1m 40in min Fast 2m 80in min Very fast 2m 80in min No filter test Factory setting Depending on the Tank type p...

Page 140: ...ues in the case of a changing dielectric constant The Changing DC values option is only available for liquid applications FMR50 FMR51 FMR52 FMR53 FMR54 Small tanks 1m 3ft option This option provides a simple possibility to reduce the echo width of the sensor module This enables an improved detection of superimposed echos especially in the near field Internally all paramters related to the echo wid...

Page 141: ...lready in the blocking distance when the device is switched on are ignored This behavior is only valid if the following two conditions are met Expert Sensor Echo tracking Evaluation mode Short time history or Long time history Expert Sensor Gas phase comp GPC mode On Without correction or External correction If one of these conditions is not met signals in the blocking distance will always be igno...

Page 142: ...999 m Factory setting Empty calibration 127 Additional information If the parametrized measuring range Empty calibration 127 differs significantly from the tank or silo height it is recommended to enter the tank or silo height Example Continuous level monitoring in the upper third of a tank or silo 0 E 1 A0019867 32 Tank silo height parameter 142 for measurements in liquids E Empty calibration 127...

Page 143: ...dent on the shape of the vessel 1 Selection of linearization type and unit 2 Configuration of the linearization A Linearization type 146 None B Linearization type 146 Linear C Linearization type 146 Table D Linearization type 146 Pyramid bottom E Linearization type 146 Conical bottom F Linearization type 146 Angled bottom G Linearization type 146 Horizontal cylinder H Linearization type 146 Sphere...

Page 144: ...f the submenu on the display module Navigation Setup Advanced setup Linearization Linearization Linearization type 146 Unit after linearization 147 Free text 148 Maximum value 149 Diameter 149 Intermediate height 149 Table mode 150 Edit table Level 151 Customer value 152 Activate table 152 ...

Page 145: ...ting tool e g FieldCare Navigation Setup Advanced setup Linearization Linearization Linearization type 146 Unit after linearization 147 Free text 148 Level linearized 148 Maximum value 149 Diameter 149 Intermediate height 149 Table mode 150 Table number 151 Level 151 Level 152 Customer value 152 Activate table 152 ...

Page 146: ...nced setup Linearization Lineariz type Description Select linearization type Selection None Linear Table Pyramid bottom Conical bottom Angled bottom Horizontal cylinder Sphere Factory setting None Additional information 0 100 0 100 100 0 100 0 0 100 A B C D E F G A0021476 34 Linearization types A None B Table C Pyramid bottom D Conical bottom E Angled bottom F Sphere G Horizontal cylinder ...

Page 147: ...mediate height 149 The height of the pyramid Conical bottom The output value corresponds to the volume or weight in a tank with conical bottom The following additional parameters have to be specified Unit after linearization 147 Maximum value 149 Maximum volume or weight Intermediate height 149 The height of the conical part of the tank Angled bottom The output value corresponds to the volume or w...

Page 148: ... distance unit To do so select the Linear linearization mode In order to define the new level unit select the Free text option in the Unit after linearization parameter and enter the required unit into the Free text parameter 148 Free text Navigation Setup Advanced setup Linearization Free text Prerequisite Unit after linearization 147 Free text Description Enter unit symbol User entry Up to 32 al...

Page 149: ...000 0 Factory setting 100 0 Diameter Navigation Setup Advanced setup Linearization Diameter Prerequisite Linearization type 146 has one of the following values Horizontal cylinder Sphere Description Specify tank diameter User entry 0 to 9999 999 m Factory setting 2 m Additional information The unit is defined in the Distance unit parameter 126 Intermediate height Navigation Setup Advanced setup Li...

Page 150: ...zation table Selection Manual Semiautomatic Clear table Sort table Factory setting Manual Additional information Meaning of the options Manual The level and the associated linearized value are entered manually for each linearization point Semiautomatic The level is measured by the device for each linearization point The associated linearized value is entered manually Clear table Deletes the existi...

Page 151: ...ldCare The table points can be entered via the Table number 151 Level 151 and Customer value 152 parameters As an alternative the graphic table editor may be used Device Operation Device Functions Additional Functions Linearization Online Offline Via local display Select the Edit table submenu to call up the graphic table editor The table is displayed and can be edited line by line The factory set...

Page 152: ...he table point User entry Signed floating point number Factory setting 0 Activate table Navigation Setup Advanced setup Linearization Activate table Prerequisite Linearization type 146 Table Description Activate enable or deactivate disable the linearization table Selection Disable Enable Factory setting Disable Additional information Meaning of the options Disable The measured level is not linear...

Page 153: ... a lost echo the output value is continously shifted towards 0 or 100 The slope of the ramp is defined in the Ramp at echo lost parameter 154 Value echo lost In the case of a lost echo the output assumes the value defined in the Value echo lost parameter 153 Alarm In the case of a lost echo the device generates an alarm see the Failure mode parameter Value echo lost Navigation Setup Advanced setup...

Page 154: ...or the slope of the ramp is percentage of the measuring range per minute min For a negative slope of the ramp The measured value is continuously decreased until it reaches 0 For a positive slope of the ramp The measured value is continuosly increased until it reaches 100 Blocking distance Navigation Setup Advanced setup Safety sett Blocking dist Description Specify blocking distance BD User entry ...

Page 155: ...onditions are met Expert Sensor Echo tracking Evaluation mode Short time history or Long time history Expert Sensor Gas phase comp GPC mode On Without correction or External correction If one of these conditions is not met signals in the blocking distance will always be ignored If required a different behavior for signals in the blocking distance can be defined by the Endress Hauser service BD A00...

Page 156: ...n diagnostic behavior parameter 157 determines for which type of event the output is opened Limit The output is normally closed and is only opened if a measured variable exceeds or falls below a defined limit The limit values are defined by the following parameters Assign limit 157 Switch on value 158 Switch off value 159 Digital Output The switching state of the output tracks the output value of ...

Page 157: ...he switch output Assign limit Navigation Setup Advanced setup Switch output Assign limit Prerequisite Switch output function 156 Limit Description Select process variable for limit monitoring Selection Off Level linearized Distance Terminal voltage Electronic temperature Relative echo amplitude Area of incoupling Factory setting Off Assign diagnostic behavior Navigation Setup Advanced setup Switch...

Page 158: ...ends on the relative position of the Switch on value and Switch off value parameters Switch on value Switch off value The output is closed if the measured value is larger than Switch on value The output is opened if the measured value is smaller than Switch off value t t A B C D A0015585 A Switch on value B Switch off value C Output closed conductive D Output opened non conductive Switch on value ...

Page 159: ...n limit 157 Off Description Define switch on delay User entry 0 0 to 100 0 s Factory setting 0 0 s Switch off value Navigation Setup Advanced setup Switch output Switch off value Prerequisite Switch output function 156 Limit Description Enter measured value for the switch off point User entry Signed floating point number Factory setting 0 Additional information The switching behavior depends on th...

Page 160: ... 0 s Failure mode Navigation Setup Advanced setup Switch output Failure mode Description Define output behavior in alarm condition Selection Actual status Open Closed Factory setting Open Switch status Navigation Setup Advanced setup Switch output Switch status Description Displays the current state of the switch output Invert output signal Navigation Setup Advanced setup Switch output Invert outp...

Page 161: ...ION Fieldbus Operating menu Endress Hauser 161 Additional information Meaning of the options No The behavior of the switch output is as described above Yes The states Open and Closed are inverted as compared to the description above ...

Page 162: ... Portuguesa Polski русский язык Russian Svenska Türkçe 中文 Chinese 日本語 Japanese 한국어 Korean Bahasa Indonesia tiếng Việt Vietnamese čeština Czech Factory setting The language selected in feature 500 of the product structure If no language has been selected English Format display Navigation Setup Advanced setup Display Format display Description Select how measured values are shown on the display Sele...

Page 163: ...3 5 159 0 mm 23 5 V 1 Â 1 1 V Â Â A0019966 39 Format display 1 value large 2 values 93 5 159 0 mm 93 5 V 26 3 C 1 Â 1 1 1 V Â Â Â A0019968 40 Format display 4 values The Value 1 to 4 display 164 parameters specify which measured values are shown on the display and in which order If more measured values are specified than the current display mode permits the values alternate on the device display T...

Page 164: ...tory setting Value 1 display Level linearized Value 2 display None Value 3 display None Value 4 display None Decimal places 1 to 4 Navigation Setup Advanced setup Display Decimal places 1 Description Select the number of decimal places for the display value Selection x x x x xx x xxx x xxxx Factory setting x xx Additional information The setting does not affect the measuring or computational accur...

Page 165: ...ced setup Display Display damping Description Define display reaction time to fluctuations in the measured value User entry 0 0 to 999 9 s Factory setting 0 0 s Header Navigation Setup Advanced setup Display Header Description Select header contents on local display Selection Device tag Free text Factory setting Device tag Additional information 1 XXXXXXXXX A0013375 1 Position of the header text o...

Page 166: ...p Advanced setup Display Separator Description Select decimal separator for displaying numerical values Selection Factory setting Number format Navigation Setup Advanced setup Display Number format Description Choose number format for the display Selection Decimal ft in 1 16 Factory setting Decimal Additional information The ft in 1 16 option is only valid for distance units Decimal places menu Na...

Page 167: ...al display with optical keys Description Switch the local display backlight on and off Selection Disable Enable Factory setting Disable Additional information Meaning of the options Disable Switches the backlight off Enable Switches the backlight on Regardless of the setting in this parameter the backlight may be automatically switched off by the device if the supply voltage is too low Contrast di...

Page 168: ...up Conf backup disp Operating time Navigation Setup Advanced setup Conf backup disp Operating time Description Indicates how long the device has been in operation User interface Days d hours h minutes m seconds s Additional information Maximum time 9999 d 27 years Last backup Navigation Setup Advanced setup Conf backup disp Last backup Description Indicates when the last data backup was saved to t...

Page 169: ...configuration of the HistoROM The result of this comparison is displayed in the Comparison result parameter 169 Clear backup data The backup copy of the device configuration is deleted from the display module of the device While this action is in progress the configuration cannot be edited via the local display and a message on the processing status appears on the display If an existing backup is ...

Page 170: ...onfiguration of the HistoROM is corrupt or not compatible with the backup copy in the display module Check not done The device configuration of the HistoROM has not yet been compared to the backup copy in the display module Dataset incompatible The data sets are incompatible and can not be compared To start the comparison set Configuration management 168 Compare If the transmitter configuration ha...

Page 171: ... all parameters marked with the symbol in this document On the local display the symbol in front of a parameter indicates that the parameter is write protected Once the access code has been defined write protected parameters can only be modified if the access code is entered in the Enter access code parameter 137 Please contact your Endress Hauser Sales Center if you lose your access code For disp...

Page 172: ...ettings have been ordered This option is only visible if customer specific settings have been ordered Of customer settings All customer parameters are reset to their factory setting Service parameters however remain unchanged To transducer defaults Every measurment related parameter is reset to its factory setting Service parameters and communication related parameters however remain unchanged Res...

Page 173: ...ctly in the Administration submenu The Confirm access code parameter is not available for operation via operating tool Navigation Setup Advanced setup Administration Def access code Define access code Navigation Setup Advanced setup Administration Def access code Def access code Description 171 Confirm access code Navigation Setup Advanced setup Administration Def access code Confirm code Descript...

Page 174: ...ausing the message and remedy measures can be viewed via the symbol on the display Timestamp Navigation Diagnostics Timestamp Description Displays timestamp for the Actual diagnostics parameter 174 User interface Days d hours h minutes m seconds s Previous diagnostics Navigation Diagnostics Prev diagnostics Description Displays the last diagnostic message which has been active before the current m...

Page 175: ...econds s Operating time from restart Navigation Diagnostics Time fr restart Description Displays the time the device has been in operation since the last device restart User interface Days d hours h minutes m seconds s Operating time Navigation Diagnostics Operating time Description Indicates how long the device has been in operation User interface Days d hours h minutes m seconds s Additional inf...

Page 176: ...Description Display the current diagnostics messages with the highest to fifth highest priority Additional information The display consists of Symbol for event behavior Code for diagnostic behavior Operating time of occurrence Event text Timestamp 1 to 5 Navigation Diagnostics Diagnostic list Timestamp Description Displays timestamp for the Diagnostics 1 to 5 parameter 176 User interface Days d ho...

Page 177: ... This parameter is only used for operation via the local display The status signals are categorized according to NAMUR NE 107 Event list submenu The Event list submenu displays the history of past events of the category selected in the Filter options parameter 177 A maximum of 100 events are displayed in chronological order The following symbols indicate whether an event has occurred or has ended ...

Page 178: ...serial number To identify the device quickly e g when contacting Endress Hauser To obtain specific information on the device using the Device Viewer www endress com deviceviewer The serial number is also indicated on the nameplate Firmware version Navigation Diagnostics Device info Firmware version Description Indicates the installed Firmware version User interface xx yy zz Additional information ...

Page 179: ...d roder code which defines all device features of the product structure In contrast the device features can not be read directly from the order code Extended order code 1 to 3 Navigation Diagnostics Device info Ext order cd 1 to 3 Description Displays the three parts of the extended order code Additional information The extended order code indicates the version of all the features of the product s...

Page 180: ...nge or threaded connection and the level Additional information D A0019483 41 Distance for liquid measurements The unit is defined in the Distance unit parameter 126 Level linearized Navigation Diagnostics Measured val Level linearized Description Displays linearized level Additional information The unit is defined by the Unit after linearization parameter 147 Terminal voltage 1 Navigation Diagnos...

Page 181: ...be configured in this submenu For a detailed configuration of the AI blocks refer to the Expert menu Navigation Diagnostics Analog inputs Analog input 1 to 5 Block tag Navigation Diagnostics Analog inputs Analog input 1 to 5 Block tag Description Defined to be unique throughout the control system at one plant site The tag may be changed using the FB_Tag service Factory setting Channel Navigation D...

Page 182: ...n Indicates the status of the output of the AI block according to the FOUNDATION Fieldbus specification Value Navigation Diagnostics Analog inputs Analog input 1 to 5 Value Description Indicates the output value of the AI block Units index Navigation Diagnostics Analog inputs Analog input 1 to 5 Units index Description Indicates the unit of the output value ...

Page 183: ...ta points if 3 logging channels are used 250 data points if 4 logging channels are used If the maximum number of data points is reached the oldest data points in the data log are cyclically overwritten in such a way that the last 1000 500 333 or 250 measured values are always in the log ring memory principle The logged data are deleted if a new option is selected in this parameter Logging interval...

Page 184: ...ry ring memory principle The logged data are deleted if this parameter is changed Example When using 1 logging channel Tlog 1000 1 s 1000 s 16 5 min Tlog 1000 10 s 1000 s 2 75 h Tlog 1000 80 s 80000 s 22 h Tlog 1000 3600 s 3600000 s 41 d Clear logging data Navigation Diagnostics Data logging Clear logging Description Initiate a deletion of the complete logging memory Selection Cancel Clear data Fa...

Page 185: ...he FieldCare function Event List HistoROM The Display channel 1 to 4 submenus invoke a diagram of the logging history of the respective channel x axis depending on the number of selected channels 250 to 1000 measured values of a process variable are displayed y axis covers the approximate measured value span and constantly adapts this to the measurement To return to the operating menu press and si...

Page 186: ...gn measurement variable 189 Value process variable 189 Specific state of the switch output Switch output simulation 189 Switch status 190 Existence of an alarm Simulation device alarm 190 Enable disable simulation The simulation of measured values can be enabled or disabled via a hardware switch SIM switch at the electronics Simulating a measured value is only possible if the SIM switch is in the ...

Page 187: ...ed to the edge of the electronics compartment A0013909 4 SIM switch in the ON position measured values can be simulated SIM switch in the OFF position factory setting Simulation of measured values is disabled 5 Feed the spiral cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment in the desired direction until it engages 6 S...

Page 188: ...ATION Fieldbus 188 Endress Hauser Structure of the submenu Navigation Expert Diagnostics Simulation Simulation Assign measurement variable 189 Value process variable 189 Switch output simulation 189 Switch status 190 Simulation device alarm 190 ...

Page 189: ...is active This is indicated by a diagnotic message of the Function check C category Value process variable Navigation Expert Diagnostics Simulation Value proc var Prerequisite Assign measurement variable 189 Off Description Specify value of the process value being simulated User entry Signed floating point number Factory setting 0 Additional information Downstream measured value processing and the...

Page 190: ...us assumes the value defined in this parameter This helps to check correct operation of connected control units Simulation device alarm Navigation Expert Diagnostics Simulation Sim alarm Description Switch alarm simulation on or off Selection Off On Factory setting Off Additional information When selecting the On option the device generates an alarm This helps to check the correct output behavior ...

Page 191: ...the result of the device check Additional information Meaning of the display options Installation ok Measurement possible without restrictions Accuracy reduced A measurement is possible However the measuring accuracy may be reduced due to the signal amplitudes Measurement capability reduced A measurement is currently possible Howerver there is the risk of an echo loss Check the mounting position o...

Page 192: ...check Level signal Prerequisite Device check has been performed Description Displays result of the device check for the level signal User interface Check not done Check not OK Check OK Additional information For Level signal Check not OK Check the mounting position of the device and the dielectric constant of the medium ...

Page 193: ...193 17 4 9 Heartbeat submenu The Heartbeat submenu is only available via FieldCare or DeviceCare It contains the wizards which are part of the Heartbeat Verification and Heartbeat Monitoring application packages Detailed description SD01871F Navigation Diagnostics Heartbeat ...

Page 194: ... Parameter 164 Decimal places menu Parameter 166 Declaration of Conformity 13 Define access code 48 Define access code Parameter 171 173 Define access code Wizard 173 Designated use 12 Device check Submenu 191 Device information Submenu 178 Device name Parameter 178 Device replacement 106 Device reset Parameter 171 Device tag Parameter 178 Diagnostic event In the operating tool 100 Diagnostic even...

Page 195: ...ration 79 85 Mapping Wizard 133 Mapping end point Parameter 131 133 Max draining speed liquid Parameter 139 Max filling speed liquid Parameter 139 Maximum value Parameter 149 Measured materials 12 Measured value symbols 55 Measured values Submenu 180 Medium group Parameter 127 Medium property Parameter 138 Medium type Parameter 138 Menu Diagnostics 174 Setup 126 N Number format Parameter 166 O Ope...

Page 196: ...ch status Parameter 160 190 Switch off delay Parameter 160 Switch off value Parameter 159 Switch on delay Parameter 159 Switch on value Parameter 158 Symbols For correction 57 In the text and numeric editor 57 System components 113 T Table mode Parameter 150 Table number Parameter 151 Tank type Parameter 126 Tank silo height Parameter 142 Terminal voltage 1 Parameter 180 Timestamp Parameter 174 17...

Page 197: ......

Page 198: ...www addresses endress com 71344019 71344019 ...

Reviews: