Mounting
Liquiphant FTL62 HART
14
Hauser
Enamel-coated tuning fork
~17 (0.67)
D
A
~14 (0.55)
C
D
D
~5 (0.2)
B
A0043327
6
Typical switch points, enamel-coated tuning fork. Unit of measurement mm (in)
A
Installation from above
B
Installation from below
C
Installation from the side
D
Switch point
5.1.3
Take viscosity into consideration
Low viscosity
Low viscosity, e.g. water: < 2
000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
> 25 (0.98)
>
!
50 (1.97)
A0042204
7
Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
‣
Make sure that the liquid can run off the tuning fork easily.
‣
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10
000 mPa⋅s
The tuning fork must be located outside the installation socket!