Mounting
Liquiphant FTL62 HART
12
Hauser
A0042281
2
Handling the device during transportation
5
Mounting
Mounting instructions
• Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
• Vertical orientation from above for device with long pipe
• Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
1
A0042153
3
Installation examples in a vessel, pipe or tank
1
Temperature spacer/pressure-tight feedthrough (optional) for tank with insulation and/or high process
temperatures
5.1
Mounting requirements
NOTICE
Scratches or impacts damage the coated surface of the device.
‣
Ensure the device is handled properly and professionally during all mounting work.
5.1.1
Pay attention to the temperature for devices with a PFA
coating (conductive)
The difference in temperature between the outer and inner side of the flange may not
exceed 60 °C (140 °F).
If necessary, use external insulation.