Liquicap M FTI51, FTI52
Commissioning
Hauser
65
6.2.10
Activating the self-test (function test)
"
Caution!
Make sure that you do not accidentally activate any processes with the self-test!
This could result, for example, in overflowing of the tank.
!
Note!
The self-test simulates switching states (probe not covered, probe covered).
This allows you to check if the connected devices are activated correctly.
To carry out a self-test, proceed as follows:
1.
Turn the function switch to position 6.
2.
Press the "+" and "–" keys simultaneously for at least two seconds.
The self-test is active when the green LED 5 flashes.
The green operational LED 1 is off.
3.
After approx. 20 seconds, the test is completed. This is indicated by the lighting up of the
operational LED 1.
You have now carried out the self-test and can turn the function switch back to position 1
(operation).
Function switch
position
Function
– key
+ key
Light emitting diodes (LED signals)
A
B
C
1 (green)
2 (green)
3 (red)
4 (green)
5 (green)
6 (yellow)
6
Self-test (function test)
Press both keys
Off *
(inactive)
Flashes
(active)
**
*
These settings are factory settings.
** Switch status signaling (on/off/flashing) depends on the mounting location selected and the failsafe mode (MIN/MAX) set.
The LED flashes if a calibration has not yet been carried out.
1
7
3
5
_
+
16 mA 0,8 mA
±
16 mA 0,8 mA
±
8 mA 0,5 mA
±
8 mA 0,5 mA
±
Start condition: covered
Proof Test
START
Proof Test
END
Start condition: uncovered
Fail-safe mode MIN
Fail-safe mode MAX