Mounting
Liquicap M FMI52 HART
8
Hauser
≥
500 (19.7)
100%
0 %
L1
L3
A0040579
Unit of measurement mm (in)
L1 Measuring range
L3 Inactive length
When installing in a nozzle, use inactive length L3.
The 0 % and 100 % calibration can be inverted.
4.1.3
Installation examples
Rope probes
The probe can be installed from above in conductive tanks made from metal.
If the process connection of the probe is insulated from the metal tank using a seal material,
then the ground connection on the probe housing must be connected to the tank using a short
line.
• The probe may not come into contact with the container wall! Do not install probes in
the area of the filling curtain.
• If multiple probes are mounted next to each other, a minimum distance of
500 mm (19.7 in) between the probes must be observed.
• When mounting, ensure there is a good electrically conductive connection between the
process connection and the tank. Use an electrically conductive sealing band for
example.
A fully insulated rope probe may be neither shortened nor extended.
Damaged insulation of the probe rope causes improper measurements.