Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
150
Hauser
For "Operating mode" = "Level" and "Medium type" = "Solid"
Process property
Step response time / s
Very fast > 100 m (333 ft) /h
37
Fast > 10 m (33 ft) /h
37
Standard < 10 m (33 ft) /h
74
Medium < 1 m (3ft) /h
146
Slow < 0.1 m (0.3ft) /h
290
No filter / test
< 1
For "Operating mode" = "Interface" or "Interface with capacitance"
Process property
Step response time / s
Very fast > 10 m (400 in)/min
5
Fast > 1 m (40 in)/min
5
Standard < 1 m (40in) /min
23
Medium < 10 cm (4in) /min
47
Slow < 1 cm (0.4in) /min
81
No filter / test
2.2
Advanced process conditions
Navigation
Setup → Advanced setup → Level → Adv. conditions
Description
Specify additional process conditions (if required).
Selection
• None
• Oil/Water condensate
• Probe near tank bottom
• Build up
• Foam (>5cm/0,16ft)
Factory setting
None
Additional information
Meaning of the options
•
Oil/Water condensate
(only
Medium type
=
Liquid
)
Makes sure that in the case of two-phase media only the total level is detected (example:
oil/condensate application).
•
Probe near tank bottom
(only for
Medium type
=
Liquid
)
Improves the empty detection, especially if the probe is mounted close to the tank
bottom.
•
Build up
Enables a safe empty-detection even if the end-of-probe signal has shifted due to build-
up.
•
Foam (>5cm/0,16ft)
(only for
Medium type
=
Liquid
)
Optimizes the signal evaluation in applications with foam formation.