Commissioning
Levelflex FMP55 PROFIBUS PA
26
Hauser
6.
Setup → Tube diameter
(only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
7.
Setup → DC value
Specify the dielectric constant of the upper medium
8.
Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
9.
Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
10.
Setup → Level
Displays the measured level L
L
.
11.
Setup → Interface
Displays the interface height L
I
.
12.
Setup → Distance
Displays the distance D
L
between the reference point R and the level L
L
.
13.
Setup → Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
14.
Setup → Signal quality
Displays the signal quality of the analyzed level echo.
15.
Setup → Mapping → Confirm distance
Make sure the vessel is completely empty. Then select
Tank empty
option.
NOTICE
Wrong measurement due to incorrect dielectric constant of the lower medium
‣
If, for Operating mode =
Interface with capacitance
, the lower medium is not water, the
dielectric constant (DC value) of the medium must be specified: Setup → Advanced setup →
Interface → DC value lower medium
NOTICE
Wrong measurement due to incorrect empty capacitance
‣
In the case of rod and rope probes in the bypass and if
Operating mode
=
Interface with
capacitance
, a correct measurement is only possible once the empty capacitance has been
determined. For this purpose, select
Confirm distance
=
Tank empty
after installing the
probe when the tank is completely empty (Step 13 in the table above).
The empty capacitance is always calibrated ex works in the case of coax probes.