Levelflex FMP55 PROFIBUS PA
Commissioning
Hauser
25
8.3
Device configuration
8.3.1
Configuring interface measurement
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK (DC )
2
2
DK
DC
1
1
(
)
A0011177
10
Configuration parameters for interface measurement
R = Reference point of measurement
D
I
= Interface distance (distance from flange to DK
2
)
E = Empty calibration (= zero point)
L
I
= Interface
F = Full calibration (= span)
D
L
= Distance
LN = probe length
L
L
= Level
UP = Measured thickness upper layer
1.
Setup → Tag description
Enter device tag.
2.
Setup→ Device address
Enter the device bus address (only if the address is set via the software).
3.
Setup → Operating mode
Select
Interface with capacitance
option.
4.
Setup → Distance unit
Select the length unit.
5.
Setup → Tank type
Select tank type.