Calibration

Calibration of thermometers

Calibration involves comparing the measured values of a device under test (DUT) with those of a

more precise calibration standard using a defined and reproducible measurement method. The aim is

to determine the deviation of the DUT's measured values from the true value of the measured

variable. Two different methods are used for thermometers:

• Calibration at fixed-point temperatures, e.g. at the freezing point of water at 0 °C,

• Calibration compared against a precise reference thermometer.
The thermometer to be calibrated must display the fixed point temperature or the temperature of

the reference thermometer as accurately as possible. Temperature-controlled calibration baths with

very homogeneous thermal values, or special calibration furnaces into which the DUT and the

reference thermometer, where necessary, can project to a sufficient degree, are typically used for

thermometer calibrations.
The measurement uncertainty can increase due to heat dissipation errors and short immersion

lengths. The existing measurement uncertainty is listed on the individual calibration certificate.
For accredited calibrations according to ISO17025, the measurement uncertainty shouldn’t be twice

as high as the accredited measurement uncertainty. If this is exceeded, only a factory calibration can

be performed.

Evaluation of thermometers

If a calibration with an acceptable uncertainty of measurement and transferable measurement

results is not possible, Hauser offers customers a thermometer evaluation measurement

service, if technically feasible. This is the case when:

• The process connections/flanges are too big or the immersion length (IL) is too short to allow the

DUT to be immersed sufficiently in the calibration bath or furnace (see the following table), or

• Due to heat conduction along the thermometer tube, the resulting sensor temperature generally

deviates significantly from the actual bath/furnace temperature.

The measured value of the DUT is determined using the maximum possible immersion depth and the

specific measuring conditions and measurement results are documented on an evaluation certificate.

Sensor transmitter matching

The resistance/temperature curve of platinum resistance thermometers is standardized but in

practice it is rarely possible to keep to the values precisely over the entire operating temperature

range. For this reason, platinum resistance sensors are divided into tolerance classes, such as Class

A, AA or B as per IEC 60751. These tolerance classes describe the maximum permissible deviation of

the specific sensor characteristic curve from the standard curve, i.e. the maximum temperature-

dependent characteristic error that is permitted. The conversion of measured sensor resistance

values to temperatures in temperature transmitters or other meter electronics is often susceptible to

considerable errors as the conversion is generally based on the standard characteristic curve.
When using temperature transmitters from Hauser, this conversion error can be reduced

significantly by sensor-transmitter matching:

• Calibration at three temperatures at least and determination of the actual temperature sensor

characteristic curve,

• Adjustment of the sensor-specific polynomial function using Calendar-van Dusen (CvD)

coefficients,

• Configuration of the temperature transmitter with the sensor-specific CvD coefficients for

resistance/temperature conversion, and

• another calibration of the reconfigured temperature transmitter with connected resistance

thermometer.

Hauser offers this kind of sensor-transmitter matching as a separate service. Furthermore,

the sensor-specific polynomial coefficients of platinum resistance thermometers are always provided

on every Hauser calibration certificate where possible, e.g. at least three calibration points,

so that users themselves can also appropriately configure suitable temperature transmitters.
For the device, Hauser offers standard calibrations at a reference temperature of

–20 to +500 °C (–4 to +932 °F) based on the ITS90 (International Temperature Scale). Calibrations in

other temperature ranges are available from your Hauser sales center on request.

Calibrations are traceable to national and international standards. The calibration certificate is

referenced to the serial number of the device. Only the insert is calibrated.

Minimum insertion length (IL) for inserts required to perform a correct calibration

The insert length IL is automatically calculated for every thermometer configuration in the

Hauser Configurator

+Temperature

 software application. The system also automatically

checks whether the selected insert length suffices to perform a factory calibration. For further

information, see the 'Accessories' section →   38

Summary of Contents for iTHERM TM401

Page 1: ...ce iTHERM inserts globally unique automated production Full traceability and consistently high product quality for reliable measured values iTHERM QuickSens fastest response times t90s 1 5 s for optim...

Page 2: ...18 Humidity 18 Climate class 18 Degree of protection 18 Shock and vibration resistance 18 Electromagnetic compatibility EMC 18 Process 18 Process temperature range 18 Thermal shock 18 Process pressur...

Page 3: ...resistant and fast response sensor technology iTHERM StrongSens and QuickSens and approval for use in hazardous areas TM411 mm A0018239 TM412 inch A0018691 TM40x characterizes the device that uses bas...

Page 4: ...e thin platinum layer from contamination and oxidation even at high temperatures The primary advantages of thin film temperature sensors over wire wound versions are their smaller sizes and better vib...

Page 5: ...316L high or low head optionally with display window Aluminum high or low head with or without display window Polypropylene low head Polyamide high head without display window Your benefits Optimum t...

Page 6: ...ibration resistant 60g 50 to 500 C 58 to 932 F Pt100 thin film iTHERM QuickSens fast response 50 to 200 C 58 to 392 F Pt100 wire wound extended measuring range 200 to 600 C 328 to 1112 F Output Output...

Page 7: ...Fieldbus head transmitters Universally programmable head transmitter with FOUNDATION Fieldbus communication Conversion of various input signals into digital output signals High accuracy over the compl...

Page 8: ...ed 3 wire single 2 x 3 wire single 4 wire single Outside screw Red1 Red3 White5 White3 Red1 Red2 Black5 Black6 Green4 Red1 Red3 White4 White6 A0034451 EN Head mounted field transmitter TMT162 dual inp...

Page 9: ...1 2 3 4 1 2 3 4 5 6 7 8 Electrical connection terminal head Flying leads Not connected not insulated 3 wire terminal block 1x Pt100 RD RD WH RD RD WH RD RD WH RD RD WH i 4 wire terminal block 1x Pt100...

Page 10: ...onnection combination insert transmitter Insert Transmitter connection 1 1x 1 channel 2x 1 channel 2 1x 2 channel 2x 2 channel 2 1x Pt100 flying leads Pt100 1 transmitter 1 Pt100 1 transmitter 1 Trans...

Page 11: ...nical Information of the iTEMP temperature transmitters Maximum measured error RTD resistance thermometer corresponding to IEC 60751 Class max Tolerances C Characteristics RTD maximum error type TF Cl...

Page 12: ...itter very small measurement current is connected Response time Tests in water at 0 4 m s 1 3 ft s according to IEC 60751 10 K temperature step change Response time without heat transfer paste 1 Prote...

Page 13: ...tice it is rarely possible to keep to the values precisely over the entire operating temperature range For this reason platinum resistance sensors are divided into tolerance classes such as Class A AA...

Page 14: ...length depending on the calibration unit if the insert cannot be fully immersed To check the actual accuracy rating of the thermometers installed a cyclic calibration of the installed sensor needs to...

Page 15: ...0 M at ambient temperature Insulation resistance between the terminals and the outer jacket is measured with a minimum voltage of 100 V DC Installation Orientation No restrictions However self drainin...

Page 16: ...so that it extends past the pipe axis Installation at an angle 4 could be another solution When determining the immersion length or installation depth all the parameters of the thermometer and of the...

Page 17: ...in the scope of supply for the thermometer Liquiphant M weld in adapters with associated seal kits are available as accessories 35 Procedure in case of seal failure indicated by leak detection port D...

Page 18: ...the measuring point depends on the sensor type and design see the following table Version Vibration resistance for the sensor tip Pt100 WW or TF 30 m s 3g 1 iTHERM StrongSens Pt100 TF iTHERM QuickSens...

Page 19: ...ture and on the process pressure The following figures exemplify the maximum permitted flow velocities in water and superheated steam at a process pressure of 40 bar 580 PSI L mm A 0 10 20 30 40 50 60...

Page 20: ...see also the individual table data T Length of protection tube shaft variable or predefined depends on protection tube version see also the individual table data U Immersion length variable depending...

Page 21: ...calculating the insert length ILa for immersion into a protection tube TT412 already available Version 1 2 4 and 5 ILa U T 38 1 mm 1 5 in 1 Version 3 ILa U T 19 05 mm 0 75 in 1 1 ILa Insert length wit...

Page 22: ...ion versions 1 Thermometer with extension hex nipple and Tri clamp process connection 2 Thermometer with extension nipple union nipple NUN and Tri clamp process connection 3 Thermometer with quick fas...

Page 23: ...xtension hex nipple and Tri clamp process connection E 25 4 mm 1 in Version 2 Thermometer with extension nipple union nipple NUN and Tri clamp process connection E 63 5 mm 2 5 in Version 3 Thermometer...

Page 24: ...for continuous use in air Properties AISI 316L 650 C 1202 F 1 Austenitic stainless steel High corrosion resistance in general Particularly high corrosion resistance in chlorine based and acidic non o...

Page 25: ...ed Seals silicone Threaded cable entry G NPT and M20x1 5 Protection armature connection NPT M24x1 5 Head color blue RAL 5012 Cap color gray RAL 7035 Weight 420 g 14 81 oz With TID10 display Ground ter...

Page 26: ...ary clamp TA30R optionally with display window in cover Specification 64 2 52 96 3 8 64 2 52 71 2 8 25 1 96 3 8 A0017145 Dimensions of version with display window in cover Degree of protection standar...

Page 27: ...on M24x1 5 or NPT Ground terminal internal in standard version external terminal optionally available Available in conjunction with 3 A marked sensors TA30S Specification 122 4 8 28 1 1 78 3 1 50 1 97...

Page 28: ...nt errors Weight 1 25 kg 2 76 lb Available in conjunction with 3 A marked sensors Cable glands and fieldbus connectors Type Suitable for cable entry Degree of protection Temperature range Cable gland...

Page 29: ...NPT connection 6 1 x 18 UNEF thread for mounting in existing protection tube IL Insert length ILa Insert length without nipple E Length of the extension neck available at point of installation provide...

Page 30: ...2 DN63 5 77 5 mm 3 05 in 68 9 to 75 8 mm 2 71 to 2 98 in Tri clamp 3 DN70 76 5 91 mm 3 58 in 75 8 mm 2 98 in 1 Pipes in accordance with ISO 2037 and BS 4825 Part 1 2 Tri clamp only possible with prote...

Page 31: ...to DIN 11866 series C 68 mm 2 67 in OD 3 73 mm 2 87 in OD 3 76 2 mm 3 in OD 3 to OD 4 10 bar 145 psi OD 4 97 6 mm 3 84 in OD 4 101 6 mm 4 in Type F according to DIN 11866 series C 50 mm 1 97 in OD 1...

Page 32: ...ID 1 6 35 mm in Reduced tip with 4 76 mm in 3 mm 0 12 in 2 9 53 mm in Reduced tip with 4 76 mm in Straight tip 3 mm 0 12 in 6 35 mm in or 6 mm 0 24 in 3 12 7 mm in Reduced tip with 4 76 mm in Straigh...

Page 33: ...heads IEC 61326 1 Electromagnetic compatibility electrical equipment for measurement control and laboratory use EMC requirements Parts in contact with the medium Parts of the thermometer in contact w...

Page 34: ...tube as per DIN43772 Ordering information Detailed ordering information is available from the following sources In the Product Configurator on the Endress Hauser website www endress com Click Corpora...

Page 35: ...717 1 FDA compliant 1 A seal is included in the delivery Weld in adapter for FTL31 33 20 50 2 0 26 1 0 21 0 8 32 1 3 G ISO 228 A0008810 G d 50 mm with flange Material 316L Roughness in m in 0 8 31 5 O...

Page 36: ...L Roughness in m in 0 8 31 5 Order number 52001051 without inspection certificate EN10204 3 1 material Order number 52011896 with inspection certificate EN10204 3 1 material Order number seal 5 pc set...

Page 37: ...For details see Technical Information TI00429F and Operating Instructions BA00371F Wireless HART adapter SWA70 Is used for the wireless connection of field devices The WirelessHART adapter can be eas...

Page 38: ...specific documentation is available for every device over the entire life cycle The application already contains the data of your Endress Hauser device Endress Hauser also takes care of maintaining an...

Page 39: ...TI01022R Hazardous area supplementary documentation iTHERM TM412 Intrinsically safe Ex ia IIC XA01024T iTHERM TM412 Dust explosion protection Ex ta tb XA01023T iTEMP temperature head transmitter TMT8...

Page 40: ...www addresses endress com...

Reviews: