HART Loop Converter HMX50
LED-Anzeigen
Display Indicators
In normal operation, the display shows:
• the current values of the HART variables PV, SV, TV, QV in the selected unit
• the present current output values for the three current outputs in mA
• the current device status
This display shows information about the device status of the field device (1 byte) and
about the response code (1 byte) of the field device. These two bytes are displayed in the
first line of the display in hexadecimal form with the code RC on the left side.
• the current setting of the type of communication
• LOOP Locate
The isolated barrier reestablishes the HART circuit. The isolated barrier performs the field
device query using the HART command 3.
LED
Status
Description
Green LED
Off
No power supply
Flashes regularly
Start-up phase, self-test
On
Normal function
Red LED
Flashes briefly
Displays a single HART fault message received by the
field device
Flashes regularly
Invalid HART data (missing communication or fault in
the field
device)
On
Device self-test of isolated barrier detected a fault
On
Isolated barrier is in reset state, all other LEDs are off
Yellow
LEDs
On
• Output Out 1, relay energized
• Output Out 2, relay energized