11
Hauser
HART Loop Converter HMX50
3.2 Mounting
Snap the device onto the DIN mounting rail in a
vertical
downward
movement.
A0034620
CORRECT: Device snapped on vertically.
INCORRECT: Device snapped on from the side. Can damage the contacts and cause the
device to fail.
Mounting the Terminal Blocks
The insulation of the removable terminal blocks protect against direct contact. If you
replace the terminal blocks, observe the rated insulation voltage. If the rated voltage
greater than 50 V AC, proceed as follows:
1. Switch off the voltage.
2. Connect the terminal blocks or disconnect the terminal blocks.
BA00371FEN_1417.fm Page 11 Tuesday, August 15, 2017 4:08 PM