Commissioning
Micropilot S FMR533 4 to 20 mA HART
26
Hauser
5.4.5
Function "process cond." (004)
This function is used to select the process conditions.
Selection:
•
standard
• calm surface
• turb. surface
• agitator
• fast change
• heavy conditions
• test: no filter
!
Note!
The phase evaluation of the Micropilot S is only activated if you select the measuring conditions
"standard"
,
"calm surface"
or
"heavy conditions"
. If, however,
"heavy conditions"
is
selected, no index values are stored. We strongly recommend that, in the case of rough product
surfaces or rapid filling, you activate the appropriate application parameters!
⇒
standard
calm surface
For all applications that do not fit into any of the following
groups.
Storage tanks with immersion tube or bottom filling.
The filter and output damping are set to average values.
The averaging filters and output damping are set to high
values.
→
steady meas. value
→
precise measurement
→
slower reaction time