Integration into a FOUNDATION Fieldbus network
Micropilot FMR53, FMR54 FOUNDATION Fieldbus
26
Hauser
7.4
Block model
7.4.1
Blocks in the device software
The device has the following blocks:
• Resource block (device block)
• Transducer blocks
• Setup transducer block (TRDSUP)
• Advanced setup transducer block (TRDASUP)
• Display transducer block (TRDDISP)
• Diagnostic transducer block (TRDDIAG)
• Advanced diagnostic transducer block (TRDADVDIAG)
• Expert configuration transducer block (TRDEXP)
• Expert information transducer block (TRDEXPIN)
• Service sensor transducer block (TRDSRVSB)
• Service information transducer block (TRDSRVIF)
• Data transfer transducer block (TRDHROM)
• Function blocks
• 2 AI blocks (AI)
• 1 discrete input block (DI)
• 1 multiple analog output block (MAO)
• 1 multiple discrete output block (MDO)
• 1 PID block (PID)
• 1 arithmetic block (AR)
• 1 signal characterizer block (SC)
• 1 input selector block (ISEL)
• 1 integrator block (IT)
• 1 analog alarm block (AAL)
In addition to the pre-instantiated blocks already mentioned, the following blocks can also be
instantiated:
• 3 AI blocks (AI)
• 2 Discrete Input Blocks (DI)
• 1 PID block (PID)
• 1 arithmetic block (AR)
• 1 signal characterizer block (SC)
• 1 input selector block (ISEL)
• 1 integrator block (IT)
• 1 analog alarm block (AAL)
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated. For instantiating blocks, see the appropriate Operating Instructions of the
configuration program used.
Hauser Guideline BA00062S.
The guideline provides an overview of the standard function blocks that are described in
FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed as an aid when using
these blocks that are implemented in the Hauser field devices.