Appendix
EngyVolt RV12
40
Address
(Register)
Parameter
number
Parameter
Holding register
Modbus start
address Hex
Valid range
Mode
High
Byte
Low
Byte
40021
11
Note address
00
14
Write the network port node address.
Default: 1
Valid range 1 to 247.
Requires a restart to become effective. Note,
both the Modbus Protocol and Johnson
Controls node addresses can be changed via
the display setup menus.
r/w
40023
12
Relay pulse divisor
00
16
Write pulse divisor index:
N = 2 to 6 in Wh/10
N
.
Default: 3
r/w
40025
13
Password
00
18
Write password for access to protected
registers.
Default: 0000
Read zero. Reading will also reset the
password timeout back to one minute.
r/w
40029
15
Network baud rate
00
1C
Write the network port baud rate for Modbus
Protocol.
Valid values:
0 = 2400 baud
1 = 4800 baud
2 = 9600 baud (default)
3 = 19200 baud
4 = 38400 baud
Requires a restart to become effective.
r/w
40031
16
Energy units prefix
00
1E
Write the units prefix for energy output
values.
0 = no prefix (e.g. Wh)
1 = k prefix (e.g. kWh)
2 = M (e.g. MWh)
r/w
40033
17
Low power limit override
00
20
0 = limit on 1% symbol off
1 = limit off 1% symbol on
Default = 0
r/w
40037
19
System power
00
24
Read the total system power,
e.g. 3p4w returns System Volts x System
Amps x 3.
ro
40041
21
Register order
00
28
Write: 2141 only
r/w
40043
22
High serial number
00
2A
0 - 16,777,215
ro
40045
23
Low serial number
00
2C
0 - 16,777,215
ro
40087
44
Relay1 energy type
00
56
Modbus Protocol input parameter for pulse
relay 1:
0 = relay off
37 = Import Wh
38 = Export Wh
39 = Import varh
40 = Export varh
Default = 38
r/w
40217
109
Reset logged data
00
D8
Write 1 to reset energy
r/w
Register order
Register order controls the order in which the device receives or sends floating-point
numbers: - normal or reversed register order. In normal mode, the two registers that make
up a floating point number are sent most significant register first. In reversed register
mode, the two registers that make up a floating point number are sent least significant
register first. To set the mode, write the value '2141.0' into this register - the instrument