Deltabar S PROFIBUS PA
Commissioning
Hauser
35
MEASURING MODE
Select "Level" option.
WARNING
!
Changing the measuring mode affects the span (URV)!
This situation can result in product overflow.
‣
If the measuring mode is changed, the span setting (URV) must be verified in the "Calibration"
"Basic Setup"
operating menu and, if necessary, reconfigured!
LEVEL SELECTION
Select level mode.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option, i. e. you assign the value 0.0 to the pressure present.
EMPTY CALIB.
1)
Enter level for the lower calibration point.
For this parameter, enter a level value which is assigned to the pressure present at the device.
FULL CALIB.
1)
Enter level for the upper calibration point.
For this parameter, enter a level value which is assigned to the pressure present at the device.
On-site operation
DAMPING TIME
Enter damping time (time constant
). The damping affects the speed at which all subsequent elements, such as the
on-site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.
1)
– LEVEL SELECTION "Level Easy Pressure" and CALIBRATION MODE "Wet"
– LEVEL SELECTION "Level Standard", LEVEL MODE "Linear" and CALIBRATION MODE "Wet"
(Menu path for CALIBRATION MODE: GROUP SELECTION
OPERATING MENU
SETTINGS
BASIC
SETTINGS)
On-site operation