Proline Promass 80
XA00097D
Hauser
33
Terminal assignment and
connection data for signal
circuits (intrinsically safe
circuits)
!
Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
For a graphic representation of the electrical connections:
Terminal assignment of transmitter 80***-***********S+#**#
Terminal assignment of transmitter 80***-***********T+#**#
Terminal assignment and
connection data for signal
circuits (non-intrinsically
safe circuits)
!
Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
For a graphic representation of the electrical connections:
Terminal assignment
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
Pulse/frequency output,
passive
Current output HART,
active
Electric circuit
–
–
Ex ia
Ex ia
Safety-related
values
–
–
U
i
I
i
P
i
L
i
C
i
30 V DC
500 mA
600 mW
negligible
6 nF
U
o
I
o
P
o
L
o
IIC/IIB
C
o
IIC/IIB
1)
L
o
IIC/IIB
1)
C
o
IIC/IIB
U
i
I
i
P
i
L
i
C
i
21.8 V DC
90 mA
491 mW
4.1 mH/15 mH
160 nF/1160 nF
2 mH/10 mH
80 nF/300 nF
30 V DC
2)
10 mA
2)
0.3 W
2)
negligible
6 nF
Functional
values
–
–
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
active: 0/4 to 20 mA
R
L
< 400
R
L
HART
250
1)
Permitted values in the event of simultaneous occurrence of concentrated inductances and capacitances.
2)
The interconnection must be assessed according to the valid construction provisions.
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
Pulse/frequency output,
passive
Current output HART,
passive
Electric circuit
–
–
Ex ia
Ex ia
Safety-related
values
–
–
U
i
I
i
P
i
L
i
C
i
30 V DC
500 mA
600 mW
negligible
6 nF
U
i
I
i
P
i
L
i
C
i
30 V DC
100 mA
1.25 W
negligible
6 nF
Functional
values
–
–
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
passive: 4 to 20 mA
voltage drop
9 V
R
L
< [(V
p. supply
– 9 V) ÷ 25 mA]
Order
characteristic
"Inputs/outputs"
Terminal no. (inputs/outputs)
20 (+)
21 (–)
22 (+)
23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
A
–
–
Pulse/
frequency output
Current output
HART
D
Status input
Relay output
Pulse/
frequency output
Current output
HART
8
Status input
Pulse/
frequency output
Current output 2
Current output 1
HART
Summary of Contents for ATEX II1/2GD
Page 20: ...0ATEX II2GD II1 2GD IECEx Zone 1 Zone 21 Zone 0 1 Proline Promass 80 20 Endress Hauser ...
Page 21: ...Proline Promass 80 ATEX II2GD II1 2GD IECEx Zone 1 Zone 21 Zone 0 1 0 Endress Hauser 21 ...
Page 49: ...Proline Promass 80 XA00097D Endress Hauser 49 ...
Page 50: ...www endress com worldwide XA00097D 06 A3 14 12 71146622 FM SGML 9 0 ...