ENDA EUP1122 PID UNIVERSAL CONTROLLER 

    MODBUS PROTOCOL ADDRESS MAP

1.1 Memory Map for Thermostat Holding Registers.

Data

Type

Parameter

Number      

Holding Register 

Adress

Decimal    (Hex)      

Read / Write

Permission

Default

Value

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

R / W

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

Word

0000d   (0000h)

400

0

600

4.0

2

4.0

1.00

1

0

0

0

500

500

0

600

600

500

0.0

2

2

3

0.0

0.0

1

0

0

0

0

0

4

60

20

0

0

0002d   (0002h)

0003d   (0003h)

0004d   (0004h)

0005d   (0005h)

0006d   (0006h)

0007d   (0007h)

0008d   (0008h)

0009d   (0009h)

0010d   (000Ah)

0001d   (0001h)

0011d   (000Bh)

0012d   (000Ch)

0013d   (000Dh)

0014d   (000Eh)

0015d   (000Fh)

0016d   (0010h)

0017d   (0011h)

0018d   (0012h)

0019d   (0013h)

0020d   (0014h)

0022d   (0016h)

0021d   (0015h)

0023d   (0017h)

0024d   (0018h)

0025d   (0019h)

0026d   (001Ah)

0027d   (001Bh)

0028d   (001Ch)

0029d   (001Dh)

0030d   (001Eh)

0031d   (001Fh)

0032d   (0020h)

0033d   (0021h)

H0

H1

H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

H12

H13

H14

H15

H16

H17

H18

H19

H20

H21

H23

H22

H24

H25

H26

H27

H28

H29

H30

H31

H32

H33

Control output, temperature setpoint value

Alarm1 output temperature setpoint value

Control output, time period setpoint value (Adjustable between 1 and 125 second)

Control output, soft start value

Control output, 2nd temperature setpoint value

Alarm1 output type selection  (Values can be given from 0 to 6) 
0 = Independent alarm,
1 = Deviation alarm, 
2 = Band alarm, 
3 = Active alarm after in band time,
4 = Alarm1 output, cooling control selection,
5 = Alarm1 output, heating setpoint dependent cooling control.
 

Control output, minimum setpoint value

Alarm1 output minimum setpoint value limit

Control output, maximum setpoint value

Alarm1 output maximum setpoint value limit

Control output, proportional band setpoint value (Adjustable between 0.0% and 100.0%)

Alarm1 output proportional band set value (Adjustable between 0.0% and 100.0%)

Control output, set value power ratio (Adjustable between 0% and 100%)

Control output, hysteresis value (Adjustable between 1 and 50 °C or °F)

Alarm1 output hysteresis value (Adjustable between 1 and 50 °C or °F)

Control output, integral time (Adjustable between 0.1  and 100.0 minute)

Control output, derivative time (Adjustable between 0.01  and 10.00 minute)

Alarm1 output, integral time (Adjustable between 0.1  and 100.0 minute)

Alarm1 output, derivative time (Adjustable between 0.01  and 10.00 minute)

Alarm1 output, time period setpoint value (Adjustable between 1 and 125 second)

Alarm1 output, set value power ratio (Adjustable between 0% and 100%)

Alarm1 output, set value power ratio in case of sensor failure (Adjustable between %0 and %100)

Control output energy percentage in case of sensor error (can be set between 0% to 100%)

Analog output minimum out percentage

ATTENTION !! H42 parameter will be 0 if this parameter set to different from 0.

Alarm2 output type selection  (Values can be given from 0 to 3)
0 = Independent alarm,
1 = Deviation alarm, 
2 = Band alarm, 
3 = Active alarm after in band time.

Modbus communication speed (Baudrate).
0 = 2400bps, 1 = 4800bps, 2 = 9600bps, 3 = 19200bps, 4 =38400bps, 5 = 38400bps, 6 = 115200bps.

ATTENTION !!

User must set Parity = None, Stop Bit = 1 and Data Length = 8 on the device that provides the Modbus 
connection. In EUP1122 these settings are set as factory default and can not be changed by the user.
Baud rate can be set with the dip switches on the device.

Please see 1.2 DIP Switch Settings for details.

Input 

Type S

election 

N

umber

.

0 = PT100 Decimal, 

    

1 = PT100 Non-decimal, 

2 = J Decimal,

              

3 = J Non-decimal,

              

4 = K Decimal,

             

5 = K Non-decimal,  

6 = L Decimal,  

            

7 = L Non-decimal,

              

8 = T Decimal,

             

9 = T Non-decimal, 

10= S Non-decimal, 

   

11 = R Non-decimal, 

          

12 = 0-20mA,

              

13 = 4-20mA, 

14 = 0-10V, 

                

15 = 2-10V, 

                        

16 = 0-25mV, 

              

17 = 0-

5

0mV

Alarm2 output, temperature setpoint value

Alarm2 output minimum setpoint value limit

Alarm2 output maximum setpoint value limit

Alarm2 output, hysteresis value (Adjustable between 1 and 50 °C or °F)

Digital filter coefficient (Adjustable between 1 and 100, 1 = filter is disable)

Control output, selection value.

0 =

 C/A2 

Output is 

Control output,   

    

 

,                 

4 =

 SSR/ANL is 0-10V,   

5 =

 SSR/ANL is 2-10V.

1 =

 SSR/ANL is SSR,

2 =

 SSR/ANL is 0-20mA, 

3 =

 SSR/ANL is 4-20mA

Heating control output duration. Heating control not performed if set to 0. Up to 1000 seconds can be set. 
Error message is generated at the end of time if no temperature value is change.

C

o

n

tr

o

O

u

tp

u

P

a

ra

m

e

te

rs

A

1

 O

u

tp

u

P

a

ra

m

e

te

rs

A

O

ut

pu

t P

ar

am

et

er

s

C

o

n

fi

g

u

ra

ti

o

n

 P

a

ra

m

e

te

rs

EUP1122-EN-01-220120

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

ENDA

TM

4

/

8

Data Content

Summary of Contents for EUP1122

Page 1: ...act output triggering feature at profile steps Timer or Thermostat feature can be used during profile controlling Modbus addressing baud rate settings or default settings can be applied via DIP Switch...

Page 2: ...Error codes 0 No Error 1 2 3 Upper scale 4 No communication with the sensor 5 Short circuit Lower scale Heater Heating output error I2 1 Sensor short circuited or temperature too low Err Led 60ms 186...

Page 3: ...START START Time Themperature Time Time PH2 PH4 PH4 PH4 PH4 PH4 PH2 Themperature Fig 3 PROFILE CONTROL OUTPUT SAMPLES PH1 1 PH1 1 PC35 1 PC35 0 PH3 PH3 PC33 1 PC33 1 START START PH2 PH2 PH4 PH4 PH4 P...

Page 4: ...0 0 minute Control output derivative time Adjustable between 0 01 and 10 00 minute Alarm1 output integral time Adjustable between 0 1 and 100 0 minute Alarm1 output derivative time Adjustable between...

Page 5: ...ters continue Analog output maximum out percentage Offset value Function control parameter 23040d 5A00h Self tune stops when this value is entered 23041d 5A01h Self tune starts when this value is ente...

Page 6: ...usted between H2 and H3 parameter 3rd Time value can be set from 0 to 9999 seconds or minutes changes with the depending on PH0 parameter 4th Step target temperature set value can be adjusted between...

Page 7: ...rol is done with the value of the proportional control Alarm1 condition 0 Alarm is ON at below setpoint value 1 Alarm is OFF at above setpoint value Alarm1 output status in case of probe failure 0 OFF...

Page 8: ...rform for any reason operating error occurs EUP1122 realizes error and sends error message Most significant bit of function is changed 1 to indicate error in error message by EUP1122 Error code is sen...