SET

SET

C.s.lo.

= Control set point lower limit.(for 

selected output)

  

Adjustable between 0 and 

C.s.Hi.

C.s.Hi.

= Control setpoint upper limit.(for 

selected output)

 

Adjustable between 

C.s.Lo.

 and Upper scale 

value. 

a2.s.l

= Alarm

2

 

set value lower limit.

 

Adjustable between 0

 

and

 

A2.S.H

parameter value.

 

a2.s.H

= Alarm

2

 

set value upper limit.

Adjustable between 

A2.S.L 

parameter value and upper scale 
value. 

a2.Hy

Hysteresis of the Alarm2 

output

Adjustable between 1 and 50 °C.

A2.st.

 

= The state of Alarm2 output.

Hi

If A2 output is above the set 

value. (on)

lo

If A2 output is above the set 

value.(off)

A2.Er.

 

State of Alarm2 output in the 

case of sensor failure.

on

= A

2 output is probe failure (on).

off

= A

2

 

output is probe faiure (off).

A2.tp

 

=  Function of Alarm

2

 type.

Four kinds of functions can be 
selected. 

indE.

Independdnt 

 alarm 

(Independent) 

dE.

 

= Deviation 

bAnd 

= Band alarm (Band) 

bAn.i

 

= Band with inhibition

 

inp.t.

 

Input type selection.

  

FE.cn.

= J type ,

nc.nA.

= K type  

c.cn.

= T 

type 

p10.r.

=S type ,

 P13.r.

= R type 

thermocouple selection.
       This parameter varies when changing
        some parameters.

Unit

 

The temperature unit.

 

°

C

= °C,

°F

= °F      

       (This parameter varies when 
changing some parameters.)

C.o.sE

 

Control output selection

C-A2

= C/A2 (Relay) output selection

SSR

 = SSR output selection

      

F.kE.C.

 

=

 Function key setting parameter 

nonE

= Function key is off.

C2.S.A.

= The function key with 2.set value is used.

manu.

 = Manual mode can be achieved with the 

function key.

dSP.o

.

= Only the temperature display mode is 

entered with function key.

C. Pb

 = 

Proportional band.(for selected 

output)
Adjustable between 

%0

.0

 

and 

%100

.0.

C. Pb

= %0

.0,

On-Off 

control is selected.

       

C. ti

 = 

Integral time.(for selected output)

Adjustable between 0 and 100.0 minutes.

C. ti 

0.0,integral impact is disable.

       

 

parameter is different from “0”,this 

parameter appears.

C. Pb

C.Hys

 = 

Hysteresis of the output.(for 

selected output)
 Adjustable between  1 and 

 

50 °C.

       

= 0,this parameter is active.

C. Pb

C. td

 = 

Derivative time.(for selected output)

Asjustable between 0.00 and 

 

25.00 minutes.

C. td 

0.0, derivative time is disable.

       

parameter is different from”0”,this 

parameter appears.

C. Pb 

C. Ct.

 = 

Period time.(for selected output)

Adjustable between 1 and 

 

250 second.

       

 

parameter is different is different 

from“0”,this parameter appears.

C. Pb

C.p.st

 = 

The ratio of output power at the 

setpoint.Adjustable between  %0 and %100. 

C.E.P.s

.

 = 

The percentage of faulty sensor 

selected output power.Adjustable between 

%0 and %100.

C.typ.

 = Control output type

C.typ.

 = 

HEAt 

means heatign control.

C.

typ

.

 = 

CooL

 

means cooling control.

While the parameter names appear,if         and
keys are pressed together, returns to the program 
mode.

S.Cod

 = 

Security menu access 

code

.  

It should be 2011.

Cosc.

 = 

Parameters of 

CoN.o.

 

menu security access level code.

nonE

 = 

Invisible.

P.yEs

 = 

Modification can be done.

P. no 

= Only visible.

m.SEt.

 = 

The percentage of manual output parameter.

Adjustable between %0 and %100.

This parameter allows manual adjustment of the output 
power when the manual output selection.

          

C. Pb.

=

 0

,

 

this parameter is not seen.

         

If 

co.SE 

parameter is different 

from C-A2,this parameter is seen.

a.2.sc.

 = 

Parameters of 

al2.o.

 

menu security access level code.

nonE

 = 

Invisible.

P.yEs

 = 

Modification can be done.

P. no

 = Only visible.

Co.sc.

 = 

Parameters of 

Conf.

 

menu security access level code.

nonE

 = 

Invisible.

P.yEs

 = 

Modification can be done.

P. no

 = Only visible.

S.t.Sc.

 = 

Parameters of 

S.tun.

 

men

u security access level code.

nonE

 = 

Invisible.

P.yEs

 = 

Modification can be done.

Co.sc.

 = 

Parameters of 

Conf.

 

m

enu security access level code.

no

 =

 Parameter settings are not 

change.

yEs

 = 

Parameter setting will be 

restored.

 2/

4

C.s.Lo.

C.s.Hi.

C. pb

C. ti

C. td

C.p.st

C.Hys

C. Ct.

C.typ

s.s.t.s.

C.E.p.s.

Con.o.

AL2.o.

ConF.

S.tun.

SEcu.

S.Cod.

Co.sc.

m.SEt.

a.2.sc.

Cn.sc.

S.t.sc.

dEF.P.

inp.t.

Unit

fltr.

C.o.sE

offs.

s.t.Co.

F.k.E.C.

A2.S.L

A2.S.H

A2.HY

A2.tP

A2.St.

A2.Er.

ET

2011

-

E

-0

4-R

SET

SET

SET

SET

SET

F

Programming mode

 
This parameter indicates the time to reach set point 
value when the device is first enegised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the 
device reaches set point value quickly.

 

     

Setting 

Pb = 0, so

ft

 start feature will be disable.

Sst

.S

 

=Sofy starter timer set value

fLtr.

= Coefficient of digital filter.

Filter for display value.
Adjustable between 1 and 

200

. If this parameter is 1,

 digital filter runs most quick. If the parameter is 

200

,

 the filter run most slow. The value of parameter should
 be increased in interference.

oFfS.

 

Offset value is added to the measurement value. 
Adjusted between -100 and +100°C.The normal value is 0. 

 

Offset value.

St.Cu

 

=

 Self tune control

no

= Self tune is stopped.

yES

= Self tune is started.

Pressing        key after the 

yes

 or no 

selection, selt tune is started or 
stopped.

  

         
Selt tune begins when the measurement,
 

PIdt.

 message

 and measurement value

 are shown alternately.Self tune process 
completed automatically after  the 

stco 

parameter is done no and is entered to the 
working mode. Self tune process begin when
 the measured temperature is expected fall 
below 90% of the set value the display shows 

te.HI

message alternately.Expected to fall

 below the temperature set point 60% evolved 
and then self tune process starts automatically.
If asked to abort  the self tune process,

St.Co

 

parameter  is done 

no 

and         key is

pressed.  
  

SET

 If             key is pressed while holding         key, the programming mode is enabled.

SET

F

Entering from the programming mode to the run mode:            
If no key is pressed within 20 seconds during programming mode, the data is  stored automatically and the run mode is entered.

Alternatively, the  same function occurs first pressing           key and        key is pressing programming mode is entered.Then           and       keys are pressing
together,data is recorded and running mode is entered.

Modification Of Parameter Diagram

                    When holding          key, the value of parameter flashes and using
                                           
                                        keys the requested value can be adjusted.

If             key is pressed and held 0.6 seconds, the value of the selected 

            

parameter changes rapidly. If  waited enough,the value increases 100 at each 
step. After 1 second following the release of the key, initial condition  is 
returned.The same procedure is valid for the decrement key.   

Chys

      6        5       6 

SET

SET

SET

SET

C.s.lO

.

inp.t.

A2.s.l

Co.sc.

C1.sE.

C.s.Hi

.

Unit

A2.s.H

A2.Sc.

C2.SE.

C. PB

Fltr.

A2Hy.

Cn.Sc.

A2.SE.

C.HyS

C.o.SE.

A2.tp

S.t.Sc.

C. ti

offs.

a2.st.

dEf.P.

C. td

f.k.E.C.

a2.Er.

a2.Er.

C. Ct

.

m.sEt.

C.P.St

.

C.EP.S

.

S.s.t.S

.

C.typ

.

TC input

TC input

TC input

TC input

TC input

Pt100 input

Pt100 input

Pt100 input

Pt100 input

Pt100 input

0

FE.cn.

0

0

25

2

2

C-A2

indE

P.yEs

P.yEs

400

P.yEs

400

P.yEs

500

4.0

0

Hi

no

1.00

nonE

on

no

20

50

0
0
0

HEat

-200

 

Pt.

-200

 600

 

°

C

 600

DEFAULT PARAMETERS

Set parameters

Control output
  parameters

Alarm2 output
  parameters

Configuration
  parameters

Self tune
parameters

Security
parameters