Or
SET
SET
SET
SET
SET
Used for
displaying and configuring the selected parameter value
.
Programming
key
When held down for a few seconds,
configured numeric value increases faster.
.
Used for increasing the setpoint value
and changing parameters.
When held down for a few seconds,
configured numeric value decreases faster.
Used for decreasing the setpoint value
and changing parameter.
Increment
key
Decrement
key
EPV
2
41
A
PROGRAMMING DIAGRAM
pressed
,
upper limit
value can be adjusted.
If both keys are
Measur
ement value
If this key is pressed
,
upper limit value
appears.
If this key is pressed
,
upper limit value
appears.
If both keys are
pressed
,
lower limit
value can be adjusted.
ADJUSTING
THE
ALARM VALUE
B
y using and
keys
,
upper limit value
can be adjusted between -500V and 500V.
If
C.Inp
;it is 50
,
this parameter adjustable between -50.00V-50.00V.
This parameter can’t be lower than
(
) value.
lo.l1
+
HYS.l
+
HYS.U
B
y using and
keys
,
upper limit value
can be adjusted between -500V and 500V.
If
C.Inp
;it is 50
,
this parameter adjustable between -50.00V-50.00V.
This parameter can’t be lower than
(
UP.L1
) value.
-
HYS.l
-
HYS.U
Loc mode; the menu can not be accessed and other functions.
It can be seen only the measured value
Loc
Measurement value
If key is pressed, “unL” mode is entered.
uNL mode; the menu and other functions can be accessed.
unL
Measurement value
&
&
If these keys are pressed together, revision date appears as day and month.
12.03
2013
If key is pressed, revision date is displayed as year.
Measurement value
If
key is pressed, “Loc” mode is entered.
&
If both & keys are pressed and held for
3
seconds,
programming mode is entered
. If keys are pressed while parameter names are displayed, then it returns to measured
value made.
Upper limit
value
SET
B
y using and
keys
,
upper limit value can be adjusted between -500V and 500V.
(
This parameter can’t be lower than (
) value.
lo.l1
+
HYS.l
+
HYS.U
If this key is pressed
,
upper limit value
appears.
SET
If key is pressed, it returns to parameter name.
Hysteresis value
for upper limit
SET
B
y using and keys
,
hysteresis value for upper limit can be adjusted between 0.0V and
20.0V.
This parameter can’t be higher than (
-
-
) value.
Up.l1 Lo.l1 Hys.l
If this key is pressed
,
hysteresis value
for upper limit appears
SET
If key is pressed, it returns to parameter name.
Delay time for
upper limit alarm
SET
B
y using and keys
,
delay time for upper limit alarm can be adjusted between 0 and
900 seconds.
delay time
for upper
limit appears
If this key is pressed
,
SET
If key is pressed , it returns to parameter name.
Lower limit
value
SET
B
y using and keys
,
lower limit value can be adjusted between -500V and 500V.
This parameter can’t be
highe
r than (
) value.
UP.l1
-
HYS.U
-
HYS.L
If this key is pressed
,
lower limit value
appears.
SET
If key is pressed, it returns to parameter name.
SET
B
y using and keys
,
hysteresis value for lower limit can be adjusted between 0.0V and
20.0V.
This parameter can’t be higher than (
-
-
) value.
Up.l1 Lo.l1 Hys.U
If this key is pressed
,
hysteresis value
for lower limit
appears
SET
If key is pressed,it returns to parameter name.
Delay time for
lower limit alarm
SET
B
y using and key
,
s delay time for lower limit alarm can be adjusted between 0 and
900 seconds.
delay time for lower
limit appears
If this key is pressed
,
SET
If key is pressed ,it returns to parameter name.
Alarm
output position
SET
B
y using and keys
,
alarm output
state
can be adjusted
to
or
If
it is adjusted
no
at alarm condition.
n.o.
N.c.
,
output relay is powered
If this key is pressed
,
alarm output
state
appears.
SET
If key is pressed ,it returns to parameter name.
If
C.Inp
;it is 50
,
this parameter adjustable between -50.00V-50.00V.
10.0
If
C.Inp
;it is 50
,
this parameter adjustable between 0.00 and 20.00.
If
C.Inp
;it is 50
,
this parameter adjustable between -50.00V-50.00V.
If
C.Inp
;it is 50
,
this parameter adjustable between 0.00 and 20.00.
10.0
Hysteresis value
for lower limit
V
SET
ENDA
ACDC
DC
AC
OUT
EPV 141
V
SET
ENDA
ACDC
DC
AC
OUT
EPV 141
SET
SET
EPV 241A
ENDA
OUT AC DC ACDC
V
PROGRAMMING MODE
3/
5
EPV
2
41
A
-E-0
2-R-201307