LOW VOLTAGE TRANSFORMER INSTALLATION GUIDE

Encore Landscape Lighting

2277 Elliott Drive Troy, Michigan 48083

Website: www.encorelandscapelighting.com

Email:

[email protected]

Phone:

248-299-1919

Fax:

248-299-1911

2

FEATURES AND CONTROLS (Below picture is basic on 300W):

① - Warning Label

② - Operating Record

③ - Conduit Cover

④ - Overload Circuit Breaker

⑤ - Photocell Plug

⑥ - Testing Loop

⑦ - Photocell Knockout

⑧ - Timer Receptacle

⑨ - Terminal Block

⑩ - Knockout

⑪ - Mounting Tab

⑫ - Lockable Latch

⑬ - Power Cord

MOUNTING TRANSFORMER:

Mount transformer to solid surface or stand using stainless steel screws and anchors (if needed) (hardware not

included). Screws will pass through keyholes. Use bubble level to ensure vertical mounting. Bottom of transformer

must be at least 1 feet above ground.

TRANSFORMER SIZING:

The total lamp VA (load) of all fixture connected to one transformer must not exceed 70% of the VA capacity of the

transformer. Therefore, the transformer selections is primarily based on Total Fixture Load:

Total Fixture Load (Watts or VA) ÷ 0.7 = Min. Transformer Capacity