SETTINGS IN THE PROFESSIONAL MODE
58
smart Stove - 0142 - 42WMSUGAT2-C
›High. imm. heater‹: Force start and stop sensor to TS2 for
additional heating. This option shall be activated if the immer-
sion heater is positioned high in the buffer tank.
›Min control PWM‹: Lower PWM speed level for controlling the
stove charging pump
›Step PWM‹: PWM pump speed increment
Systems 2, 3:
›Add. heat enabled‹: Recharging of the tank by the additional
heating can be disabled or enabled (if available)
›Charge start‹: Minimum stove temperature for starting the
loading pump
›Charge offset‹: Temperature offset for starting the
speed control of the loading pump
›Act. ZV below‹: Lower temperature threshold for activation of
zone valve
›Offset ZV act.‹: Temperature offset (hysteresis) for zone valve
activation
›DPD‹: Dynamic pump delay, see page 24
›High. imm. heater‹: Force start and stop sensor to TS2 for
additional heating. This option shall be activated if the immer-
sion heater is positioned high in the buffer tank.
›fix PWM‹: Fixed PWM speed of high efficiency pump for load-
ing domestic hot water
›Min control PWM‹: Lower PWM speed level for controlling the
stove charging pump
›Step PWM‹: PWM pump speed increment
1.3.14 Control para.
17.03.2016
10:44
High. imm. heater
Min control PWM
30%
Step PWM
5%
1.3.14 Control para.
17.03.2016
10:44
Add. heat enabled
Charge start
58°C
Charge offset
5K
Act. ZV below
43°C
Offset ZV act.
2K
1.3.14 Control para.
17.03.2016
10:44
DPD
0min*K
High. imm. heater
fix PWM
100%
Min control PWM
30%
1.3.14 Control para.
17.03.2016
10:44
High. imm. heater
fix PWM
100%
Min control PWM
30%
Step PWM
5%