31
3.
Place the Opacity/ T2 switch on the service module in the Opacity position to observe the correlated
opacity on the digital display.
4.
Swing open the transceiver and initiate a zero with the zero switch on the service module to raise the
zero reflector into place. Observe and record the zero value after 30 seconds. Return the mirror to
normal resting position by
returning the zero switch to
operate position.
5.
Insert a 1/16" Alan wrench
into the adjustment set screw
located on the top of the zero
reflector
(see figure 4)
. Turn
set screw clock-wise 1/8 turn.
6.
Remove the Alan wrench and
initiate a zero utilizing the zero
switch on the service module and
after 15 seconds observe the
reading is moving toward the
desired value. (if value is away
from desired repeat step 4 turn set
screw C.C.W.)
7.
Repeat steps 4 & 5 each time
making small 1/8-turn increments
until the desired value is reached. Cycle 2-3 times more waiting 15 to 20 seconds between cycles to
assure unit repeats desired value +/- 0.5% Opacity. Record the final value, you will need to enter it
into the "ZERO CAL VALUE" in the QUICK MENU.
8.
Swing transceiver into operate position and secure in place.
Span filter VALUE
1.
With the zero switch in zero, place the span switch in span. Span is not adjustable, final value is a
function of filter value, transceiver calibration and OPLR. Record the final value; you will need to
enter it into the "SPAN CAL VALUE" in the QUICK MENU.
2.
Return both zero and span switches to operate, normal/test to normal, T2/Opacity to Opacity.
Record the zero/span values in the quick menu
1.
At the control unit, under the flip down door, press the
EDIT (ESC)
button (the red Edit (ESC)
LED will light). The message display will read QUICK MENU. Press the
ENTER
key, then the
EDIT
key 4 times or hold and scroll down until the Display reads ZERO CAL VALUE. Press the
ENTER
key twice, the Edit Value Light will flash. Press and hold the
EDIT
or
EDIT
key
until the zero value recorded in the previous steps is displayed. Press
ENTER
then Press the
EDIT
key 3 times to return to normal operation.
2.
Press the
EDIT (ESC)
button (the red Edit (ESC) LED will light). The message display will read
QUICK MENU. Press the
ENTER
key, then the
EDIT
key 5 times or hold and scroll down
until the Display reads SPAN CAL VALUE. Press the
ENTER
key twice, the Edit Value Light will
flash. Press and hold the
EDIT
or
EDIT
key until the span value recorded in the previous
steps is displayed. Press
ENTER
then Press the
EDIT
key 3 times to return to normal operation.
Figure 4
Protective Window
Zero Reflector
Summary of Contents for 1304
Page 45: ...44 Section 8 DRAWINGS ...
Page 46: ...45 EMS 1001 Mounting under 6 STACK ...
Page 47: ...46 EMS 1002 Mounting over 6 stack ...
Page 48: ...47 EMS 1024 Air purge Weather cover mech Installation ...
Page 49: ...48 EMS 1078 PANEL cut out for 1304 control unit ...
Page 50: ...49 EMS 1079 1304 control unit dimensions ...
Page 51: ...50 EMS 1077 Terminal identification 1304 control unit ...
Page 52: ...51 EMS 1131 1304 with recorder system wiring ...
Page 54: ...53 EMS1101 Sht 1 of 3 Dual Blower system wiring ...
Page 55: ...54 EMS 1101 Sht 2 of 3 Single Blower system wiring ...
Page 56: ...55 EMS 1101 Sht 3 of 3 Without Blower system wiring ...