Empire DVC55IPXLP-1 Installation Instructions And Owner'S Manual Download Page 16

37403-5-0620

Page 16

GENERAL: 

 

All furnaces have been fire-tested to check for proper 

operation.    This  includes,  main  burner  flame,  pilot  flame,  fan 

operation, fan control, limit control and automatic valve operation.  

If the furnace fails to function on initial installation, it is advisable to 

re-check the following: 

1.  115 volts to the junction box.

2.  Inlet gas pressure.

3.  The 24 volt system.

4.  Type of gas being used and that shown on the rating label.

Servicing the Pilot and Main Burners, Pilot Orifice, and Main 

Burner Orifices: 

 Disconnect the gas supply at the inlet to the 

control valve.  Then remove the burner door to which the above 

components are attached.

Servicing  The  Fan  Motor:

  The upper front panel, the shroud 

surrounding the fan blade and fan blade must be removed. 

Replacing Fan  and Oiling the Motor

The fan motor should be cleaned and oiled once each heating season.  

To reach the motor, withdraw the metal shroud surrounding the fan 

blade by removing the screws on each side.  Oil holes are located 

on the top at each end of the motor.  Use a few drops of #10 motor 

oil.  To clean the motor, blow air through its ventilation openings 

with a vacuum cleaner or low pressure air source.
If fan motor is replaced, the silicone rubber gaskets, see Page 20, 

Index No. 4, Part No. M147, should also be replaced.  The gaskets 

must be stretched to fit the motor bolts into the gasket holes and 

then the motor and gaskets installed on the motor mounting bars.

S8600H INTERMITTENT IGNITION MODULE SPECIFICATIONS

Lockout timing is 90 seconds.  Ignition timing is until pilot lights or 

lockout occurs.

Module shuts down and cuts power to gas control on flame failure.  

Gas control closes to provide 100 percent lockout on flame failure.  

Manual reset required.

ELECTRICAL RATINGS:

Voltage and frequency:  20.5 to 28.5V (24V nom.) 60 Hz.

Current rating:  0.2 A.

Valve contact ratings (at 24 Vac):

   Run 

Inrush

 

Pilot   1.0 A 

10.0 A

 

Main  1.0 A 

10.0 A

SPARK GENERATOR OUTPUT:  13kV peak at 25 pf load.

ANTICIPATOR SETTING:  0.2 A plus pilot valve rating plus main 

valve rating.  

COMPATIBILITY:  Standard models compatible with all open-close 

switch type 24 Vac capable of supplying rated voltage and current 

to the module.

AMBIENT TEMPERATURE RATING:  Minus 40 F to plus 175 F 

(minus 40 C to plus 79 C).

RELATIVE HUMIDITY RATING:  5 to 90 percent RH at 95 F.

FLAME FAILURE RESPONSE TIME:  0.8 seconds at 1.0 uA flame 

current.

FLAME CURRENT:  1 uA, min.

CHECKOUT

Check out the gas control system:

  1.  At initial installation of the appliance.

  2.  As part of regular maintenance procedures.

  3.  As the first step in troubleshooting.

  4.  Any time work is done on the system.

STEP 1:  Perform Visual Inspection.

  A.  With power off, make sure all wiring connections are clean and 

tight.

  B.  Turn on power to appliance and ignition module.

  C.  Open manual shutoff valves in the gas line to the appliance.

  D.  Do gas leak test ahead of gas control if piping has been disturbed.

  GAS LEAK TEST

:  Paint pipe joints with rich soap and water 

solution.  Bubbles indicate gas leak.  Tighten joints to stop leak.

STEP  2:    Review  Normal  Operating  Sequence  and  Module 

Specifications.

STEP 3:  Reset the Module.

  A.  Turn the control valve to off.

  B.  Wait one minute.

  

As you do Steps 4 and 5, watch for points where operation 

deviates from normal.  Refer to Troubleshooting Chart to correct 

problem.

STEP 4:  Check Safety Lockout Operation.

  A.  Turn gas supply off.

  B.  Watch for spark at pilot burner.   

  C. Time length of spark operation.  Maximum spark time is 90 

seconds.

  D.  Open manual gas cock and make sure no gas is flowing to pilot 

or main burner.

  E.  Wait one minute before continuing.

STEP 5:  Check Normal Operation.

  A.  Turn contol valve on to call for heat.  

  B. Make sure pilot lights smoothly when gas reaches the pilot 

burner.

  C.  Make sure main burner lights smoothly without flashback.  Make 

sure burner operates smoothly without floating or lifting.

  D.  If gas line has been disturbed, complete gas leak test.

    GAS LEAK TEST:  

Paint gas control gasket edges and all pipe 

connections downstream of gas control, including pilot tubing 

connections, with rich soap and water solution.  Bubbles indicate 

gas leaks.  Tighten joints and screws or replace component to 

stop gas leak.

  E.  Turn control valve off.  Make sure main burner and pilot flames 

go out.

OPERATION

Module operation can be conveniently divided into two phases for 

S8600H.  The phases are trial  for ignition and main burner operation.

SERVICE & MAINTENANCE SUGGESTIONS

Summary of Contents for DVC55IPXLP-1

Page 1: ...cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier INSTALLER Leave this manual with the appl...

Page 2: ...7 Specifications 7 Gas Supply 8 9 Clearances 9 Installation Instructions 10 12 Lighting Instructions 13 Pilot Flame Characteristics 14 Main Burner Flame Characteristics 14 Wiring 15 Service and Maint...

Page 3: ...The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpet ing bedding materials etc It i...

Page 4: ...can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a c...

Page 5: ...oxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be pe...

Page 6: ...k and light colored tile Installation in Residential Garages Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less th...

Page 7: ...ntal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 and these instructions Determine that there is no blockage or restr...

Page 8: ...e vicinity of the unit Where none exists or where its size or location is not adequate contact your local authorized installer for installation or relocation Compounds used on threaded joints of gas p...

Page 9: ...nter a building The bottom of the vent terminal and the air intake shall be located at least 12 inches above grade WARNING The nearest point of the vent cap should be a minimum horizontal distant of s...

Page 10: ...es using the register as a template 4 Drill 2 1 8 diameter holes in cabinet side and fasten the register in place with 2 10 x 1 screws provided Side outlet kit 10 boot assembly with register SOK 1 for...

Page 11: ...ed to the furnace INSTALLATION INSTRUCTIONS CONT D Cutting Vent Tubes This is the most important part of the installation With the furnace installed on wall the 6 diameter air inlet tube and the 4 dia...

Page 12: ...or on Siding vinyl aluminum etc Direct vent furnaces are designed to be installed on a uniform outside wall When the wind comes from any angle up down or from either side it must hit the vent cap equ...

Page 13: ...s control which has been under water OPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE 1 Turn off all electric power to the appliance if service is to be performed 2 Remove control access panel lowe...

Page 14: ...pilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue ou...

Page 15: ...ian Electrical Code CSAC22 1 if an external electrical source is utilized This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged di...

Page 16: ...h all open close switch type 24 Vac capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5...

Page 17: ...ety lockout Lockout de energizes the first main valve operator and closes the first main valve in the gas control stopping pilot gas flow The control system must be reset by turning the valve off for...

Page 18: ...made from ignition cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module WARNING Whenperformingthefollowingsteps donott...

Page 19: ...37403 5 0620 Page 19 TROUBLESHOOTING CONT D...

Page 20: ...ation after a one minute delay Check transformer and AC line for prop er input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout...

Page 21: ...se and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model...

Page 22: ...ng 29 DV824 Front Burner 30 P8842 Main Burner Orifice Natural Gas Two Required 30 P8853 Main Burner Orifice Propane Gas Two Required 31 DV687 Manifold and Plate Assembly 32 M148 Manifold Gasket 33 M15...

Page 23: ...37403 5 0620 Page 23 PARTS VIEW...

Page 24: ...a qualified installer and operated in accordance with the instructions furnished with the appliance A bill of sale cancelled check or payment record should be kept to verify purchase date and establis...

Page 25: ...impossible de joindre le fournisseur de gaz appeler le service d incendie L installation et l entretien doivent tre ex cut s par un installateur qualifi une agence de service ou par le fournisseur de...

Page 26: ...ventiler l appartement dans lequel l unit est install e Installation sur un Tapis ou Tuile Si cet appareil est install directement sur un tapis tuiles ou tout genre de mat riel combustible autre qu un...

Page 27: ...ts d un syst me de ventilation de taille inad quate formation de condensat fuite d versement etc et doivent sp cifier la proc dure d essai suivante AVERTISSEMENT DANGER D EMPOISONNEMENT AU MONOXYDE DE...

Page 28: ...ou les endroits bas Attendez que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le...

Page 29: ...d sir e pour la sortie d air et marquer les trous de montage en utilisant le registre comme guide 10 Percer 2 trous de 1 8 3 2mm de diam tre dans le mur et attacher le registre avec 2 vis 10 x 1 2 54c...

Page 30: ...placement de l Alimentation de Gaz Lalignedegazpeutentrerdansl appareilsoitenvenantduplancher ou du mur ext rieur L ouverture pour la ligne de gaz doit tre faite ce moment L emplacement de l ouverture...

Page 31: ...tre ait une l g re pente descendante vers l ext rieur La pente descendante est n cessaire pour pr venir l entr e de la pluie Attacher la plaque ext rieure de montage au mur ext rieur avec 4 vis 10 x 1...

Page 32: ...xtention du capuchond ventpourrev tementenvinylenedoitpasexc derune paisseurtotalede13 33 02cm pourleDVC 55 voirFigure5a AVERTISSEMENT Lorsque l ensemble d vent pour le rev tementenvinyleDV 822oulacon...

Page 33: ...taller un collecteur de s diment avec un adapteur en T L emploi des connexions de gaz suivantes est recommand ANS Z21 24 Connexions d appareil de tuyaux et de raccords en m tal ondul ANS Z21 45 Connex...

Page 34: ...ch e dans l adapteur La bo te de jonction est munie d un trou de 7 8 22 2mm pour utiliser un raccord conducteur si les codes locaux exigent ce genre de protection Installation d un dispositif de march...

Page 35: ...nneau d acc s la commande panneau du bas avant 3 Tourner le bouton de contr le de gaz dans le sens horaire la position ferm Ne pas forcer 4 Replacer le panneau d acc s la commande panneau du bas avant...

Page 36: ...z allant la veilleuse ou au br leur principal E Attendre une minute avant de continuer TAPE 5 V rifier le fonctionnement normal A R gler plus lev e que celle de la chambre pour obtenir de la chaleur B...

Page 37: ...nt tre identifi s avant de les d brancher Une erreur de filetage piut entra ner un mauvais et dangereux fonctionnement V rifier que le fonctionnement soit convenable apr s l entretien STAGE 1 TRIAL FO...

Page 38: ...p riode d essai d allumage Lorsque le module d allumage se verrouille le syst me doit tre remis z ro en r glant le temp rature plus basse que celle de la chambre pour au moins une minute avant de cont...

Page 39: ...s il y a lieu V rifier l enveloppe du c ble d allumage pour des signes de fonte ou de d formation Prendre les moyens pour prot ger le c ble et l enveloppe contre les temp ratures excessives V rifier q...

Page 40: ...2147 Valve de gaz VR8204C 1126 gaz propane 10 0 41 R 2149 Valve de gaz VR8204C 1001 gaz naturel 3 5 42 UH 810 Support de montage pour transformateur 43 R 1995 Transformateur 44 UH 451 Couvercle pour b...

Page 41: ...37403 5 0620 Page 17...

Page 42: ...37403 5 0620 Page 18 MAINTENANCE HISTORIQUE DE L APPAREIL Date Nom du distributeur Nom du technicien de service Entretien effectu notes...

Page 43: ...37403 5 0620 Page 19 MAINTENANCE HISTORIQUE DE L APPAREIL Date Nom du distributeur Nom du technicien de service Entretien effectu notes...

Page 44: ...Empire Comfort Systems Inc Belleville Illinois Pour toute question g n rale concernant nos produits veuillez nous envoyer un courriel info empirecomfort com Pour toute question d entretien ou de r pa...

Reviews: