background image

INSTALLATION INSTRUCTIONS

serving a separate solid-fuel burning appliance.

Begin the installation by locating the wall studs on the side 
wall of the structure. Find the centerlines between the studs 
where you want the unit to be mounted. Refer to the following 
illustration (Figure 5) for a side view of  how the finished 
installation should look. This appliance is certified for 
installation on walls which are a maximum of 12” (305 mm) 
thick. The vent assembly supplied with the unit will 
accomodate walls up to that thickness.

With the template flat and level against the inside wall, mark 
the location for the opening for the vent assembly as well as the 
location of the two holes for mounting the wall support plate 
and the one for the gas supply, if the supply is to be through the 
wall. If desired, (and in accordance with all applicable 
building and plumbing codes) the gas piping can be brought 
into the room through the floor underneath the unit.

Remove the template from the wall and with a long drill, make 
a hole in the center of the opening for ventilation all the way 
through inside  and  outside  wall.  Trace  the  wall opening in 

Cutting the Vent Hole

Location of Furnace

Locating Wall Opening

Note:

The heater must be on an outside wall in the room to be heated. 
When choosing a location for the furnace please remember 
that the vent cap supplied with the unit must be installed 
without alteration, with the exception of cutting the vent tubes 
and insulation to length, as directed in these instructions. The 
outside vent cap needs to be flush to the wall, so select a 
relatively smooth exterior surface.

Since this appliance is a direct vent (balanced flue) design, all 
combustion and ventilation air is drawn from outside of the 
structure. No special considerations for combustion are 
necessary inside the structure. Once you have determined that 
the exterior vent will meet the clearances above, you must 
locate the heater on the inside wall of the room to be heated. 
Begin the installation by locating the wall studs on the inside 
wall of the structure. Find the centerlines between the studs 
where you want the unit to be mounted.

A full scale template is furnished with the unit which 
illustrates the vent and gas supply openings and mounting 
holes in their correct locations on the wall.

 the figure 4 gives the required dimensions for mounting 

the unit, in the event that the template is unusable or lost.

Place the template on the wall so that the vent opening will be 
located between the studs and, in the case of the MV 130, for 
example, the bracket mounting holes are over the studs (16” / 
406 mm,  on center). DO NOT CUT THE WALL STUDS IN 
ORDER TO INSTALL THE UNIT. Place the bottom edge of 
the template directly on the floor or the floor covering such as 
carpeting or tile.

Make sure that the location you have selected for the furnace 
complies the requirements above before its installation. 

This gas appliance must not be connected to a chimney flue 

Installing the Unit

3/16” (4.7 mm)

Mounting Holes

D

A

C

21

 5/

8

”  (

5

5

0

 m

m

)

FLOOR

Figure 4

CLEARANCES (cont.)

J= 

K=

L= 

M=

clearance to nonmechanical air supply inlet to

     building or the combustion air inlet to 

     any other appliance

 clearance to a mechanical air supply inlet

clearance above paved sidewalk or paved 

      driveaway located on public property

 clearance under veranda, porch deck, or balcony

CANADIAN INSTALLATIONS

1

US INSTALLATIONS

2

6” (15 cm) for appliances  10,000 Btu/h 

(3 kW), 9” (23 cm) for appliances  10,000 

Btu/h (3 kW) and 

0,000 Btu/h (15 kW) 

3 feet (91 cm) above if within 10 feet

(3 m) horizontally

 5

<

clearance in accordance with local

installation codes and the

requirements of the gas supplier

1  In accordance with the current CSA B149.1, 

.

Natural Gas and Propane Installation Code

2  In accordance with the current ANSI Z223.1/NFPA 54, 

.

3  A vent shall not terminate directly above sidewalk or paved driveaway that is located between two 

National Fuel Gas Code

    single family dwellings and serves both dwellings.

4  Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides         

beneath the floor.

6” (15 cm) for appliances  10,000 Btu/h 

(3 kW), 12” (30 cm) for appliances  10,000 

Btu/h (3 kW) and  100,000 Btu/h (30 kW) 

6 feet (1.83 m)

7 feet (2.13 m)

12” (30 cm)

4

 

<

3

Page 8

A

10 1/4” (260 mm)

16” (406 mm)
16” (406 mm)

D

5 1/2” (140 mm)
6 3/4” (171 mm)
8 1/2” (216 mm)

E

6 1/8” (155 mm)

9” (230 mm)

9” (230  mm)

C

4 1/4” (108 mm)
4 1/4” (108 mm)

3 3/4” (98 mm)

MOD

MV 120
MV 130
MV 145

E

MV1XX-1-0603

Summary of Contents for MV 120

Page 1: ...ng Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier callthe fire department Installation and service must be performed by a qualified installer service agencyor thegassupplier This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other ga...

Page 2: ...duction Specifications Gas Supply Clearances Installation Instructions Lighting Instructions Pilot Flame Characteristics Main Burner Flame Characteristics Maintenance How to Order Repair Parts Parts List Parts View Troubleshooting PAGE 3 4 5 5 6 7 8 8 10 11 12 12 12 13 13 14 15 16 Page 2 MV1XX 1 0603 ...

Page 3: ... e n q u e e s t á i n s t al a d o e l a p a r a t o L a r o p au o t r o s m a t e r i a l e s i n f l a m a b l e s n o d e b e n c o l o c a r s e e n ci m a o c e r c a d e e s t e a p a r a t o C u a l q u i e rp a n t a l l a d e s e g u r i d a d o pa n e l q u e s e a r e t i r a d o p a r a r e a l i z a re l s e r v i c i o d e l e q u i p o de b e s e r r e i n s t a l a d o a n t e s ...

Page 4: ...odorlessand colorless You may not know all the following safety pre cautions which can protect both you and your family from an accident Read them carefully now then review them point by point with the members of your household Do not operate electric switches light matches use your phone Donotdoanythingthatcouldignitethegas Get everyone out of the building or area Do that IMMEDIATELY Closeall gas...

Page 5: ... Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shownontherating plate is theresponsibility of theperson andcompanymakingthechange Important Notice Always consult your local Building Department regarding regulations codes or ordinances which apply to the installation of adirectventwallfurnace 1 Installer must leave instructio...

Page 6: ...2 61kPa Propanegas models will have a manifold pressure approximately 10 0 w c 2 49kPa at the valve outlet with the inlet pressure to the valvefromaminimumof11 0 w c 2 739kPa forthepurpose of input adjustment to a maximum of 13 0 w c 3 237kPa A 1 8 3mm N P T plugged tapping accessible for test gauge connection islocatedontheoutletside ofthegascontrol LocatingGas Supply Recommended Gas Pipe Diamete...

Page 7: ...nter of theventcaptothe nearestoutsidecornerorobstruction is 16 407mm 5 The MV 120 MV 130 and MV 145 minimum wall depth is 4 1 2 114 mm and the maximum is 12 305 mm The Figure 3 Vent terminal clearances A A G C F L D E B A B C D E F G H I clearance above grade veranda porch deck or balcony clearance to window or door that may be opened clearance to permanently closed window vertical clearance to v...

Page 8: ...nttheunittobemounted A full scale template is furnished with the unit which illustrates the vent and gas supply openings and mounting holesintheir correctlocationsonthewall the figure 4 gives the required dimensions for mounting theunit intheeventthatthe templateisunusableorlost Place the template on the wall so that the vent opening will be located between the studs and in the case of the MV 130 ...

Page 9: ...comes through the wall It is not where you willcutthepipes It is very important that this be a clean straight cut for the heatertoperformproperly Remember to remove the vent assembly from the wall in ordertocut thetubes Installingtheventassemblyandwallsupportplate the indicated diameter in both walls and cut them Your hole will be about 1 to 2 26 to 52 mm depending on the unit model larger indiame...

Page 10: ...valve or at the gas meter or propane LPtankserving thebuilding Fixtheleaking jointand re testthejoints as directedabove Once the supply is checked and does not leak place the cover on the unit See Figure 10 Be sure the foam packing has been removed Secure the cover with the two nuts at the bottom of theunitwhich youhadremovedwhenunpacking eventualwaterfiltrationortheentranceofbugsisnecessary Press...

Page 11: ...he gas control knob counter clockwise to the PILOT position Depress the gas control knob and push in the Piezo igniter several times until the pilot is lit The pilot flame can be observed by looking down the inside of the heater jacket A small reflector on the right hand side near 1 Setthethermostatto lowestsetting 2 Openthe controlaccess panelonthetop rightside oftheunit 3 Turn the gas knob clock...

Page 12: ...in thesupplypipingleading to theappliance ifinstalled or at the gas meter or propane LP tank 3 Remove the two screws which hold the unit to the wall supportplateandliftandpulltheunitawayfromthewall 4 Carefully examine the interior of the vent pipes both large and small diameter If you notice any blockage or obstruction cleanthepipes 5 Look insidetheopenings of the rear oftheunitandcheckfor any for...

Page 13: ...ine with a soapy water solution Bubbles on any of the joints indicated a leak is present and must be repaired Turn OFF the gas to the unit when performing any repairs to the gas piping system After the pilot lines are checked turn the main burner ON and again check all joints in the piping system for leaks with soapy water Repair any joints which indicate a leak ispresent 12 While the main burner ...

Page 14: ...43018500 SD430185B0 SD442202B0 SK00000048 SK00000051 SD44107500 SD44105800 SD44305500 SD44177000 SD44176900 SD44175800 SD44120800 SA00000263 SD44107002 SD44107100 SD44106900 SD44106801 SK00000053 SK00000054 SD44106100 SD44158001 SD44158102 SD44125500 SD44125200 SD443332C0 SD443332D0 SD44111300 SD44132400 SD44152900 SD44153000 SK00000055 PART MV 145 N SD43018400 SD430184B0 SD44326100 SK00000049 SK0...

Page 15: ...Page 15 PARTS VIEW MV1XX 1 0603 ...

Page 16: ...ning thesmallbrassscrewonthelefthand fronttop of the gas control top plate Backing the screw out counterclockwise increases the pilot flame The pilot flame should contact the thermocouple tip but not excessively long SeeLightingInstructions the thermocouple is a standard 24 millivolt probe Check its effectiveness by removing it from the heater and attach a probe alligator clip to themagnetcontactb...

Reviews: