background image

12429-10-0408

Page 9

Vent Safety Shutoff System

This appliance must be properly connected to a venting system.  This 

appliance is equipped with a vent safety shutoff system.

Warning:  Operation of this wall furnace when not connected 

to  a  properly  installed  and  maintained  venting  system  or 

tampering with the vent safety shutoff system can result in 

carbon monoxide (CO) poisoning and possible death.

This furnace is equipped with a manual reset vent safety switch.  The 

manual reset vent safety switch will cause gas flow to the main burners 

to “shut off” due to improper venting or a blocked flue.
To reset the manual reset vent safety switch:

 

1.  Remove upper front panel.

 

2.  Depress red manual reset button.  The manual reset vent safety 

switch is located on the draft diverter.

 

3.  Replace upper front panel. 

If the manual reset vent safety switch continues to “shut off” the gas 

flow to the main burners a qualified service person must be contacted 

to inspect for improper venting, blockage in the vent pipe or the manual 

reset vent safety switch for being  defective.

             Figure 9 

Figure 10

Wiring

The  appliance,  when  installed,  must  be  electrically  grounded  in 

accordance with local codes or, in the absence of local codes, with 

the 

National Electrical Code, ANSI/NFPA 70 or Canadian Electrical 

Code, CSA C22.1

, if an external electrical source is utilized.  

This 

appliance is equipped with a three-prong [grounding] plug for your 

protection against shock hazard and should be plugged directly 

into a properly grounded three-prong receptacle.  Do not cut or 

remove the grounding prong from this plug. 

 For an ungrounded 

receptacle, an adapter, which has two prongs and a wire for grounding, 

can be purchased, plugged into the ungrounded receptacle and its wire 

connected to the receptacle mounting screw.  With this wire completing 

the ground, the appliance cord plug can be plugged into the adapter 

and be electrically grounded.  A 7/8” (22mm) hole is provided in the 

junction box for use with a conduit connector if local codes require 

this type of protection.

Thermostat Installation

The thermostat should be installed in the same room as the furnace 4’ 

(1.2m) to 5’ (1.5m) above the floor and away from another heat source 

(cooking stove, hot water heater,  etc.) including walls and doorways 

with a heat source in an adjoining room.   

Do Not Install  Thermostat 

on Outside Wall.
Insulated Vent Enclosure

Vented wall furnaces installed in buildings with flat roofs can have 

poor venting.  The cold vent pipe will have a delay in proper venting 

and cause the wall furnace to shut “OFF” by the vent safety switch. 

To prevent delayed venting as well as condensation of flue products 

an insulated vent enclosure is recommended.
Use type B vent pipe and maintain at least a one inch (25mm) clearance 

to combustibles.
Use  metal  thimble  to  protect  vent  pipe  as  it  passes  through 

combustibles.

Figure 8

INSTALLATION

(3m)

(.6m)

(3m)

More than 10”

Summary of Contents for FAN TYPE VENTED WALL FURNACE FAW-55IP

Page 1: ...tions If you cannot reach your gas supplier call the re department Installation and service must be performed by a quali ed installer service agency or the gas supplier WARNING If the information in t...

Page 2: ...3 SAFETY INFORMATION FOR USERS OF LP GAS 4 INSTALLATION 5 9 LIGHTING INSTRUCTIONS 10 SERVICE AND MAINTENANCE SUGGESTIONS 11 12 TROUBLESHOOTING 13 S8600H TROUBLESHOOTING GUIDE 14 15 PARTS LIST 16 PART...

Page 3: ...t less than 18 457mm above the oor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehicle Speci cations Due to high temperatures the appliance should...

Page 4: ...pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adso...

Page 5: ...chimney for residential type or low heat gas utilization equipment shall extend at least 3 feet 914mm above the highest point where it passes through a roof of a building and at least 2 feet 610mm hi...

Page 6: ...of wall opening is 8 1 2 216mm C Wall opening width is 12 1 8 308mm 2 Remove outer casing knockout from outer casing back 3 Remove inner casing knockout from inner casing 4 Attach furnace to wall see...

Page 7: ...type of gas supply line required On Natural gas lines less than 15 4 5m long use 1 2 13mm pipe on longer runs use 3 4 19mm iron pipe or equal On LP gas lines please consult LP gas supplier Installing...

Page 8: ...nimum of 5 0 w c 1 24kPa for the purpose of input adjustment to a maximum of 10 5 w c 2 615kPa Propanegasmodelswillhaveamanifoldpressureapproximately10 0 w c 2 49kPa at the valve outlet with the inlet...

Page 9: ...This applianceisequippedwithathree prong grounding plugforyour protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the g...

Page 10: ...to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3...

Page 11: ...ny time work is done on the system STEP 1 Perform Visual Inspection A With power off make sure all wiring connections are clean and tight B Turn on power to appliance and ignition module C Open manual...

Page 12: ...e main burner where it is ignited by the pilot burner The ame current also holds the safety lockout timer in the reset normal operating condition When the call for heat ends both main valve operators...

Page 13: ...n cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module WARNING Whenperformingthefollowingsteps donottouchstripped end...

Page 14: ...12429 10 0408 Page 14 S8600H TROUBLESHOOTING GUIDE...

Page 15: ...ormerandAClineforproper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled C...

Page 16: ...r Casing Bottom USA 39 15670 Outer Casing Bottom Canada 40 8720148 Bushing 41 872053 Cord Set 42 872087 Bushing 43 DV 671 Manifold Support 44 DV 765 Gasket for Chamber Air Inlet Top Bottom Two Require...

Page 17: ...12429 10 0408 Page 17 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529 PARTS VIEW...

Page 18: ...pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the rst oor ceiling and one pair of re stop spacers at each successive ceiling l...

Page 19: ...12429 10 0408 Page 19 SERVICE NOTES...

Page 20: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: