DVC-35IPT INTERMITTENT PILOT SEqUENCE OF OPERATION

START

System Check

Trial for

Ignition

Main Burner

Operation

END


Pilot Valve Opens

Ignitor Powered

Flame Signal

Detected

Thermostat

Calls for Heat


Ignitor OFF

Main Valve Opens

Internal Check

OK

Pilot Light and Flame is

Sensed During Trial For

Ignition (1)

Apply 24 VAC

To Appliance

Main Pilot Valves

Close

Thermostat Call for Heat

Ends

Flame Signal

Lost?


Pilot Valve Ignition OFF

Wait for Flame Signal to

Disappear


Pilot Valve Closes

Ignition OFF

Main Pilot

Valves Close

Flame Lost More

Than 5 Times in

One Call for Heat

5 Minute Retry Delay

3 Second Flame Recycle

Delay

YES

NO

NO

YES

NO

YES

YES

NO

YES

NO

(1) Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame has not lit. It will turn back ON for the final 30 seconds of 

the 90 second trial for ignition. The pilot will be energized during the entire trial for ignition. This is normal operation for this gas ignition 

system.

Summary of Contents for DVC-35IPT-1

Page 1: ...ss a certified kit is used Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the...

Page 2: ...C 35T Standing Pilot Lighting Instructions 12 DVC 35IPT Intermittent Pilot Lighting Instructions 13 Pilot Flame Characteristics 14 Main Burner Flame Characteristics 15 Wiring 15 16 Service and Mainten...

Page 3: ...g system periodically and replace damaged parts Do make a periodic visual check of pilot and burners Clean and replace damaged parts CAUTION Pilot hole cover must be kept tightly closed during operati...

Page 4: ...t lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorpti...

Page 5: ...requiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the ex...

Page 6: ...tallation and replacement of gas piping gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term qualified agency means any...

Page 7: ...iance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve...

Page 8: ...l depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DVC 35T and DVC 35IPT can be attached to the wall or recessed into the wal...

Page 9: ...h two 2 10 x 1 provided screws 9 Installation of SOR 1 is completed Side outlet kit SOK 1 10 boot assembly with register for warm air discharge into an adjoining room may be installed on either side o...

Page 10: ...tlet box with four 4 10 x 1 2 screws Attention Do not overtighten screws because outlet box must be able to move as flue tube expands and contracts Place collar on six inch air tube against air drop A...

Page 11: ...ist page 16 to order tubes Figure 10 Figure 11 appropriate vent kit for measured wall depth the vent tubes will fit together 1 Place caulking not provided beneath the collar of the outside mounting pl...

Page 12: ...l knob slightly and turn clockwise to OFF Do not force 5 Replace control access panel lower front panel Lighting Instructions 1 Stop Read the safety information above 2 Set the thermostat to lowest se...

Page 13: ...artofthecontrolsystem and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 Th...

Page 14: ...in turn lights the main burner The gas valve used in this system is a step opening which opens at a lower pressure for ignition and then steps to a full inlet pressure of 4 pressure on Natural gas and...

Page 15: ...er heater etc including walls and doorways with a heat source in an adjoining room Do Not Install Thermostat on Outside Wall CAUTION Label all wires prior to disconnection when servicing controls Wiri...

Page 16: ...ASSY PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW OUTLET PRESSURE TAP TO 24V HOT ON TRANSFORMER CONTROL IGNITOR CONTROL IGNITOR WIRING 40 VA TRANSFORMER 120 VAC 24 VAC FAN SWITCH MOTOR 120 VAC VALVE...

Page 17: ...for being in the Pilot position 2 Checkpilotadjustmentforbeingfullopen counterclockwise to open 3 Ifgasisavailableinthesupplytubing thepilotorificeand or pilot burner is probably restricted by a spide...

Page 18: ...all for Heat Ends Flame Signal Lost Pilot Valve Ignition OFF Wait for Flame Signal to Disappear Pilot Valve Closes Ignition OFF Main Pilot Valves Close Flame Lost More Than 5 Times in One Call for Hea...

Page 19: ...Burner Cable Check that Pilot Gas is Flowing Wait to Assure Pilot Gas Tubing is Purged Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control Must Measure at Least 19 5 VAC with Ig...

Page 20: ...3163 FILTER RETAINER 26 R 3232 PILOT NAT IP ONLY 26 R 3233 PILOT LPG IP ONLY 27 P 88 52 ORIFICE NAT 3 REQUIRED 27 P 88 60 ORIFICE LPG 3 REQUIRED 28 DV 1236 MANIFOLD 29 DV 1259 FRONT PANEL 30 P 112 MA...

Page 21: ...13119 10 0709 Page 21 PARTS VIEW...

Page 22: ...13119 10 0709 Page 22 SERVICE NOTES...

Page 23: ...13119 10 0709 Page 23 SERVICE NOTES...

Page 24: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: