background image

13281-9-0709

Page 7

Locating Gas Supply

The gas line can enter the unit either through the floor or outside 

wall. The gas line opening should be made at this time. Location 

of the opening will be determined by the position of floor joists 

and the valve and union used for servicing.

Note:

 Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:

—  aNS Z21.24 appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  aNS  Z21.45 assembled  Flexible appliance  Connectors  of 

Other Than all-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flexible 

appliance connector cannot exceed three feet in length.

Figure 1 

Consult the current National Fuel Gas Code, aNSI Z223.1 CaN/

CGA-B149 (.1 or .2) installation code. 

Installing a New Main Gas Cock

each appliance should have its own manual gas cock.

a  manual  main  gas  cock  should  be  located  in  the  vicinity  of 

the unit. Where none exists, or where its size or location is not 

adequate, contact your local authorized installer for installation 

or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

a gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required 

by the National Fuel Gas Code that a drip line be installed near 

the gas inlet. This should consist of a vertical length of pipe tee 

connected into the gas line that is capped on the bottom in which 

condensation and foreign particles may collect. 

Figure 2

Method of Installing a Tee Fitting Sediment Trap

Pressure Testing of the Gas Supply System

1.  To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must be 

placed immediately upstream of the gas supply connection to 

the appliance.

2.  The  appliance  and  its  individual  shutoff  valve  must  be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 1/2 

psig (3.5 kPa).

3.  The  appliance  must  be  isolated  from  the  gas  supply  piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

3/4" Recommended Gas Pipe Diameter

Pipe Length

(Feet)

Schedule 20 Pipe

Inside Diameter

Tubing, Type L

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10

1//2"

12.7mm

3/8"

9.5mm

1/2"

12.7mm

3/8"

9.5mm

10-40

1/2"

12.7mm

1/2"

12.7mm

5/8"

15.9mm

1/2"

12.7mm

40-100

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm

1/2"

12.7mm

100-150

3/4"

19mm

1/2"

12.7mm

7/8"

22.2mm

3/4"

19mm

GAS SUPPLY

Summary of Contents for DV-55IPT-1

Page 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Page 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Page 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Page 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Page 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Page 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Page 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Page 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Page 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Page 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Page 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Page 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Page 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Page 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Page 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Page 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Page 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Page 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Page 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Page 20: ...13281 9 0709 Page 20 PARTS VIEW...

Page 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Page 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Page 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Page 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: