Empire Heating Systems DV-55IPT-1 Installation Instructions And Owner'S Manual Download Page 15

13281-9-0709

Page 15

GENERAL:  

All furnaces have been fire-tested to check for proper 

operation.  This includes, main burner flame, pilot flame, fan operation, 

fan control, limit control and automatic valve operation.  If the furnace 

fails to function on initial installation, it is advisable to re-check the 

following: 

1.  115 volts to the junction box.

2.  Inlet gas pressure.

3.  The 24 volt system.

4.  Type of gas being used and that shown on the rating label.

The  Service  Department  at  empire  Comfort  Systems,  Inc.  may 

be  contacted  to  assist  in  servicing  furnace  or  call  a  qualified 

serviceman.

Servicing the Pilot and Main Burners, Pilot orifice, and Main 

Burner orifices: 

 Disconnect the gas supply at the inlet to the control 

valve.  Then remove the burner door to which the above components 

are attached.

Servicing  The  Fan  Motor:

    The  upper  front  panel,  the  shroud 

surrounding the fan blade and fan blade must be removed. 

Replacing Fan  and Oiling the Motor

The fan motor should be cleaned and oiled once each heating season.  

To reach the motor, withdraw the metal shroud surrounding the fan 

blade by removing the screws on each side.  Oil holes are located on 

the top at each end of the motor.  Use a few drops of #10 motor oil.  

To clean the motor, blow air through its ventilation openings with a 

vacuum cleaner or low pressure air source.
If fan motor is replaced, the silicone rubber gaskets, see Page 19, Index 

No. 4, Part No. 712059, should also be replaced.  The gaskets must be 

stretched to fit the motor bolts into the gasket holes and then the motor 

and gaskets installed on the motor mounting bars.

S 8 6 0 0 H   I N T E R M I T T E N T  I G N I T I O N   M O D U L E 

SPECIFICATIONS

Lockout timing is 90 seconds.  Ignition timing is until pilot lights or 

lockout occurs.

Module shuts down and cuts power to gas control on flame failure.  

Gas control closes to provide 100 percent lockout on flame failure.  

Manual reset required.
eLeCTRICaL RaTINGS:

Voltage and frequency:  20.5 to 28.5V (24V nom.) 60 Hz.

Current rating:  0.2 a.

Valve contact ratings (at 24 Vac):

 

 

Run 

Inrush

 

Pilot   1.0 a 

10.0 a

 

Main  1.0 a 

10.0 a

SPaRK GeNeRaTOR OUTPUT:  13kV peak at 25 pf load.

THeRMOSTaT aNTICIPaTOR SeTTING:  0.2 a plus pilot valve 

rating plus main valve rating.  

THeRMOSTaT COMPaTIBILITY:  Standard models compatible with 

all open-close switch type 24 Vac thermostats capable of supplying 

rated voltage and current to the module.

aMBIeNT TeMPeRaTURe RaTING:  Minus 40 F to plus 175 F 

(minus 40 C to plus 79 C).

ReLaTIVe HUMIDITY RaTING:  5 to 90 percent RH at 95 F.

FLAME FAILURE RESPONSE TIME:  0.8 seconds at 1.0 uA flame 

current.

FLaMe CURReNT:  1 ua, min.

ChECKoUt

Check out the gas control system:

  1.  at initial installation of the appliance.

  2.  as part of regular maintenance procedures.

  3.  As the first step in troubleshooting.

  4.  any time work is done on the system.
STeP 1:  Perform Visual Inspection.

  a.  With power off, make sure all wiring connections are clean and 

tight.

  B.  Turn on power to appliance and ignition module.

  C.  Open manual shutoff valves in the gas line to the appliance.

  D.  Do  gas  leak  test  ahead  of  gas  control  if  piping  has  been 

disturbed.

    GaS LeaK TeST:  Paint pipe joints with rich soap and water 

solution.  Bubbles indicate gas leak.  Tighten joints to stop leak.

STeP  2:    Review  Normal  Operating  Sequence  and  Module 

Specifications.

STeP 3:  Reset the Module.

  a.  Turn the thermostat to its lowest setting.

  B.  Wait one minute.

   

As  you  do  Steps  4  and  5,  watch  for  points  where  operation 

deviates from normal.  Refer to Troubleshooting Chart to correct 

problem.

STeP 4:  Check Safety Lockout Operation.

  a.  Turn gas supply off.

  B.  Set thermostat above room temperature to call for heat.

  C.  Watch for spark at pilot burner.   

  D.  Time  length  of  spark  operation.    Maximum  spark  time  is  90 

seconds.

  E.  Open manual gas cock and make sure no gas is flowing to pilot 

or main burner.

  F.  Set  thermostat  below  room  temperature  and  wait  one  minute 

before continuing.

STeP 5:  Check Normal Operation.

  a.  Set thermostat above room temperature to call for heat.  

  B.  Make  sure  pilot  lights  smoothly  when  gas  reaches  the  pilot 

burner.

  C.  Make sure main burner lights smoothly without flashback.  Make 

sure burner operates smoothly without floating or lifting.

  D.  If gas line has been disturbed, complete gas leak test.

    GaS LeaK TeST:  Paint gas control gasket edges and all pipe 

connections downstream of gas control, including pilot tubing 

connections, with rich soap and water solution.  Bubbles indicate 

gas leaks.  Tighten joints and screws or replace component to stop 

gas leak.

  e.  Turn thermostat below room temperature.  Make sure main burner 

and pilot flames go out.

OPERATION

Module  operation  can  be  conveniently  divided  into  two  phases 

for  S8600H.    The  phases  are  trial    for  ignition  and  main  burner 

operation.

SERVICE & MAINTENANCE SUGGESTIONS

Summary of Contents for DV-55IPT-1

Page 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Page 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Page 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Page 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Page 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Page 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Page 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Page 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Page 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Page 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Page 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Page 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Page 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Page 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Page 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Page 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Page 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Page 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Page 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Page 20: ...13281 9 0709 Page 20 PARTS VIEW...

Page 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Page 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Page 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Page 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: