Page 7

20248-2-0806

Figure 1

WARNING:  Rework worksheet, adding the space of the 

adjoining unconfined space. The combined spaces must have 

enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling 

and one with 12" of the floor. Connect these items directly to the 

outdoors  or  spaces  open  to  the  outdoors. These  spaces  include 

attics and crawl spaces. In most cases for direct communication 

with the outdoors or direct communication through a vertical duct 

a free area opening of one square inch per 4,000 BTU/HR of heater 

input rating for each grill. If a horizontal duct is used, a grill free 

area or duct opening shall have a free area opening of one square 

inch per 2,000 BTU/HR for each grill. Follow the 

National Fuel 

Code NFPA 54/ANSI Z223.1, Section 5.3 Air for Combustion and 

Ventilation

 for required size of ventilation grills or ducts.

IMPORTANT:

  Do  not  provide  openings  for  inlet  or  outlet  air 

into attic if attic has a thermostat-controlled power vent. Heated 

air entering the attic will activate the power vent.

Figure 2

3.  Add the BTU/Hr of all fuel burning appliances in the space.

 Vent-free heater    

 BTU/Hr

 Gas water heater   

 BTU/Hr

 Gas furnace 

 

 BTU/Hr

 Vented gas heater  

 BTU/Hr

 Gas fireplace logs  

 BTU/Hr

 Other gas appliances*  +   

 BTU/Hr

 Total 

 

 BTU/Hr

Example:  Vented gas heater   

20,000 

BTU/Hr

  

  Vent-free heater  

18,000 

BTU/Hr

  

  Total 

 

38,000 

BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4. Compare the maximum BTU/Hr the space can support with the 

actual amount of BTU/Hr used.

 

 BTU/Hr (maximum the space can support)

 

 BTU/Hr (actual amount of BTU/Hr used)

  Example: 

    25,600 

BTU/Hr (maximum the space can support)

    38,000 

BTU/Hr (actual amount of BTU/Hr used)

Warning:

 If the area in which the heater may be operated is smaller 

than that defined as an unconfined space or if the building is of 

unusually  tight  construction,  provide  adequate  combustion  and 

ventilation air by one of the methods described in the National Fuel 

Gas Code, ANSI Z223.1, Section 5.3 or applicable local codes.
The space in the above example is a confined space because the 

actual BTU/Hr used is more than the maximum BTU/HR the space 

can support. You must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an adjoining room. If 

the extra space provides an unconfined space, remove door to 

adjoining room or add ventilation grills between rooms. See 

Ventilation Air From Inside Building.

 

B.  Vent room directly to the outdoors. See 

Ventilation Air From 

Outdoors.

C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes 

room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

WARNING: You must provide additional ventilation air 

in a confined space.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. 

When  ventilating  to  an  adjoining  unconfined  space,  you  must 

provide two permanent openings: one within 12" of the ceiling 

and one within 12" of the floor on the wall connecting the two 

spaces (see options 1 and 2, Figure 1). You can also remove door 

into adjoining room (see option 3, Figure 1). Each ventilation grill 

or opening shall have a minimum free area of one square inch per 

1,000 BTU/HR of the total input rating of the gas equipment in 

the confined space.

Summary of Contents for VF24FP2-1

Page 1: ...s of gas input per hour Refer to page 6 WARNING If not installed operated and main tained in accordance with the manufacturer s in structions this product could expose you to sub stances in fuel or fr...

Page 2: ...Placement 12 Placement of Glowing Embers Rock Wool 12 Operation Instructions Flame Appearance 12 VF24FP3 1 Lighting Instructions 13 VF24FP2 1 Lighting Instructions 14 Pilot Flame Characteristics 15 16...

Page 3: ...azard of high surface temperature and should stay away to avoid burns or clothing ignition Young childrenshould becarefullysupervisedwhen they are in the same room with the appliance Do not place clot...

Page 4: ...ight pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or...

Page 5: ...your gas company before changing spud ori ce size WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage Instructions to Installer 1 Installe...

Page 6: ...s water vapor retarder with a rating of one perm or less with openings gasketed or sealed and b Weatherstripping has been added on openable windows and doors and c Caulking or sealants are applied to...

Page 7: ...ount of BTU Hr used BTU Hr maximum the space can support BTU Hr actual amount of BTU Hr used Example 25 600 BTU Hr maximum the space can support 38 000 BTU Hr actual amount of BTU Hr used Warning If t...

Page 8: ...nectors of Other Than All Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a exible appliance connector c...

Page 9: ...place opening to any combustible wall or material should not be less than 4 inches 2 Clearances from the top of the replace opening to the ceiling should not be less than 30 inches Mantel Clearances f...

Page 10: ...g ange will secure the replace 6 Placeleftmantelsideagainstbase Insertdowelsinbreastboard into left mantel side 7 Use four 4 pre drilled screw holes on back of breastboard to secure breastboard to man...

Page 11: ...the appliance the gas supply will enter on right hand side See Gas Supply Page 8 3 Insert replace into enclosure 4 Attach nailing anges to framing with a screw or nail 5 Finishedwallsurfacewillbe ush...

Page 12: ...ttle is necessary to cover this area Excess ember material causes the yellow ame to become orange and stringy Apply just enough to obtain slow glow and a gold yellow ame Avoid any drafts that alter bu...

Page 13: ...Turn ON OFF switch to OFF position and or set thermostat if present to lowest setting If applicable Turn off all electric power to the heater 1 STOP Read the safety information label 2 Make sure the m...

Page 14: ...FF GAS TO APPLIANCE 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable LIGHTING INSTRUCTIONS 7 Turn gas control...

Page 15: ...re 15 If pilot ame pattern is incorrect as shown in Figure 14 See Troubleshooting page 18 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip ame clean t...

Page 16: ...8 Remove air shutter from ori ce tting 9 ForNaturalgasonly remove20 000BTUmainburnerori ce marked 49 from ori ce tting and replace with 10 000 BTU VF24FP3 1 Main Burner Operation The gas control modul...

Page 17: ...be checked with a millivolt meter 0 1000 MV range Remote Receiver Use the following steps to place the remote receiver adjacent to the gas valve Attention The remote receiver bracket is not used in t...

Page 18: ...rrect Replace gas regula tor 7 ODS pilot lights but ame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enough...

Page 19: ...ITCH WIRE HARNESS NOT SHOWN P 263 NIPPLE 8 NOT SHOWN 15465 TUBING VALVE TO PILOT REGULATOR NAT NOT SHOWN 15466 TUBING PILOT REGULATOR TO PILOT NAT NOT SHOWN R 7063 PILOT REGULATOR NAT VF24FP2 1 ONLY 1...

Page 20: ...Page 20 20248 2 0806 PARTS VIEW 10 27 26 25 VF24FP2 28 VF24FP3 31 29 32 30 1 7 2 4 5 6 8 9 10 11 12 13 25 26 27 28 29 30 31 32 24 3 14 15 16 17 18 19 23 20 21 22...

Page 21: ...box 5 Place the 2 liner mounting brackets over the front edges of the 2 side brick liners Attach liner mounting brackets to outer casing with 4 four 10 x 1 2 screws from Step 4 6 Replacelogsintoburner...

Page 22: ...motor Align and attach blower assembly to outer casing side See Figure 2 10 Snap Heyco into blower shield side 11 Placeblowershieldsideadjacenttomotor Routeblowermotor wires through Heyco on blower s...

Page 23: ...d on left front of valve cover on burner assembly Insert blower shield front adjacent to blower motor and blower shield side Align clearance hole on blower shield front with left front screw hole on v...

Page 24: ...screws at interior top of inner casing that were loosened in Step 6 30 Attach burner assembly to inner bottom with three 3 10 x 1 2 screws from Step 5 31 Attach rear log support to inner casing with t...

Page 25: ...the ground the appliance cord plug can be plugged into the adapter and be electrically grounded CAUTION Labelallwirespriortodisconnectionwhenservic ing controls Wiring errors can cause improper and d...

Page 26: ...part number and description coincide 1 2 3 Index Number Part Number Description VPF24BR Brass Trim Kit 1 11328 Trim Top 2 11326 Trim Left 3 11327 Trim Right VPF24SS Stainless Steel Trim Kit 1 20227 Tr...

Page 27: ...Page 27 20248 2 0806 SERVICE NOTES...

Page 28: ...Page 28 20248 2 0806 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: