VENT EXAMPLES FOR SINGLE FLUE
FLEXIBLE PVC PIPE WITH
1 ½" COUPLING ON EACH END
(MODEL # PVVK-CFA)
FLEXIBLE GAS
LINE
PVC PIPE SWV
(SUPPLIED BY INSTALLER)
(2) - 45 DEG. PVC BENDS
(SUPPLIED BY INSTALLER
IF NECCESSARY)
GALV. SHEET FLASHING
TO SEAL CHIMNEY
(SUPPLIED BY INSTALLER)
VENT CAP (SUPPLIED
WITH VENT KIT MODEL # PVVK-SV)
CUT END
V
H
42”
Figure 11 - Venting for Existing Fireplace Installation
Determining Minimum Vent Height Above the Roof
Figure 12
Single Flue - Vertical Vent Run
with 45 degree elbows
MANTEL
PVC PIPE
(SUPPLIED BY INSTALLER)
2 - 45 DEG. PVC
BENDS (SUPPLIED
BY INSTALLER)
GAS SUPPLY
FLASHING
H
SURROUND
VENT CAP
(SUPPLIED WITH VENT KIT)
MODEL #PVVK-SV
X
12
ROOF PITCH
IS
12
X
FLEXIBLE PVC PIPE
WITH 1 1/2” COUPLING ON EACH END
MODEL #PVVK-CFA
ROOF PITCH
H (Min.)
Flat to 6/12
12” (305 mm)
6/12 to 7/12
15” (381 mm)
Over 7/12 to 8/12
18” (457 mm)
Over 8/12 to 16/12
24” (610 mm)
Over 16/12 to 21/12
36” (914 mm)
Determining Minimum Vent Height Above the Roof
WARNING
Major U.S. building codes specify minimum chimney and/or vent
height above the rooftop. These minimum heights are neces
-
sary in the interest of safety. These specifications are summa
-
rized in Figures 11 and 12.