background image

30259-0-0212

Page 22

45° ELBOW

47.5”

(1.2m)

Horizontal Venting Maximum 47.5” (1.2 m) with 45° elbows. 

Inner 1-1/2 inch pipe and outer 3 inch pipe 45° elbows can be 

purchased from a local hardware store.

47.5”

(1.2m)

Maximum Horizontal Venting - 47 1/2” (1.2 m)

Minimum Horizontal Venting - 4” (10.2 cm)

EXHAUST OPENING MUST

BE POINTED DOWNWARD.

Direct Vent System Building Exterior View

PVVK-24H AND PVVK-48H CO-AXIAL VENT KIT (cont.)

1 9/16”

4 3/32”

Figure 24

Figure 21

Figure 22

Figure 23

Summary of Contents for P)-5

Page 1: ...ny other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or...

Page 2: ...AMING DIMENSIONS 24 INSERT INTO MASONRY FIREPLACE 25 BAY WINDOW MANTIS CLEARANCE TO COMBUSTIBLES 26 FIREPLACE MANTIS CLEARANCE TO COMBUSTIBLES 27 BAY WINDOW MANTIS SPECIFICATIONS 28 29 FIREPLACE MANTIS SPECIFICATIONS 30 31 GAS CONNECTION INSTALLATION 32 BAY WINDOW MANTIS LOG SET INSTALLATION INSTRUCTIONS 33 34 FIREPLACE MANTIS LOG SET INSTALLATION INSTRUCTIONS 35 WIRING 36 START UP CHECK LIST 37 L...

Page 3: ...r WARNING Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean DO NOT put a...

Page 4: ... gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air there may be more odor at lower levels Always be sensitive to the slightest gas odor If you detect any odor...

Page 5: ... IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR ...

Page 6: ...odes Always consult with local authorities be fore installing any gas appliance Combustion and Ventilation Air U S National Fuel Gas Code NFPA 54 ANSI Z223 1 NFGC Air for Combustion and Ventilation Electrical Connections U S National Electrical Code NEC ANSI NFPA 70 Gas Piping and Gas Pipe Pressure Testing U S NFGC and National Plumbing Codes General Installations U S Current edition of the NFGC a...

Page 7: ...2 inch diameter schedule 40 PVC pipe 40 feet maximum equivalent length with 3 90 elbows ACCESSORIES Common Part Number Description TRW Wall Thermostat Wireless Remote FRBTP Battery Operated Remote with Programmable Thermostat PVCA Colinear Adapter PVCT Colinear Transition Kit PVVK CFA Flex Vent Kit PVVK FC Single Flue Horizontal Vent Kit PVVK SV Single Flue Vertical Vent Kit PVVTC Vertical Termina...

Page 8: ...inst shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle purchase an adapter with two prongs and a wire for grounding Note Under no circumstances should the fireplace be installed under conditions that would not allow for easy removal of the fireplace to carry out routine in...

Page 9: ...warnings exactly could result in serious injury death or property damage After gas piping to the fireplace is complete all connections must be tested for gas leaks This includes pipe connections at the main gas valve emergency shutoff valve and flexible gas connectors if applicable The soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observe...

Page 10: ...egulator vent outlet J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btu h 3 kW 9 in 23 cm for appliances 10 000 Btu h 3 kW and 50 000 Btu h 15 kW 12 in 30 cm for appliances 50 000 Btu h 15 kW K Clearance to a mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3 m horizontally L Clearance above...

Page 11: ...ng for venting is 1 7 8 inch in diameter for 1 1 2 inch PVC pipe The minimum distance from the center of the vent cap to the near est outside corner or obstruction is 12 inches The flue outlet must be at least 12 inches from any opening which flue gases could en ter the building See Figure 1 The flue outlet must be a minimum distance of 6 feet from any pressure regulator The bottom of the exhaust ...

Page 12: ... installing a Mantis into an existing fireplace The flex vent kit can be cut down but can only be cut from one end Cement PVC Joints Cut End Cement PVC Joints Once length is determined install two 2 10 x 1 2 screws into the adaptor assembly to secure the adaptor assembly to the flex hose Using PVC cement cement all PVC joints of the flex vent kit to the remaining PVC vent run VENTING REQUIREMENTS ...

Page 13: ...ble from Empire Comfort Systems Inc Termination Cap PVVTC Vertical exhaust cap used with 1 1 2 PVC pipe installation Termination cap can also be used with colinear transition plate model PVCT Refer to Figures 10 13 15 19 and 20 for venting examples PVC CEMENT ...

Page 14: ...t is below the level of the floor 90 ELBOW 2 61 0cm 27 8 2m 5 1 5m VENT TERMINAL 90 ELBOW NOT COUNTED 3 FEET FIRST 90 DOES NOT GET COUNTED WHEN WITHIN 6 15 2cm OFF BACK OF HEATER ELBOW SLOPE Figure 8 Single Flue Horizontal Tall Vent Run Example Calculation Max Vent Run 40 feet H 5 2 7 V 27 2 90 6 Total 40 90 ELBOW FLUE CENTER 6 15 2cm MIN 1 4 DOWNWARD SLOPE PER FOOT TO OUTSIDE 12 MIN TO GRADE RECO...

Page 15: ...n with 45 degree elbows MANTEL PVC PIPE SUPPLIED BY INSTALLER 2 45 DEG PVC BENDS SUPPLIED BY INSTALLER GAS SUPPLY FLASHING H SURROUND VENT CAP SUPPLIED WITH VENT KIT MODEL PVVK SV X 12 ROOF PITCH IS 12 X FLEXIBLE PVC PIPE WITH 1 1 2 COUPLING ON EACH END MODEL PVVK CFA ROOF PITCH H Min Flat to 6 12 12 305 mm 6 12 to 7 12 15 381 mm Over 7 12 to 8 12 18 457 mm Over 8 12 to 16 12 24 610 mm Over 16 12 ...

Page 16: ...ce with two 2 screws 2 When adapter is connected continue with your vent run Cementing PVC joint is recommended but not required on colinear fresh air intake adaptor Colinear adaptor Colinear adaptor to be used in conjunction with single flue horizontal vent kit PVVK FC The two attachments are used for colinear direct vent installation 4 13 16 3 11 16 6 1 8 7 5 16 ...

Page 17: ...ECTED SNOW LEVEL Installation of the Colinear Transition Plate 1 Attach the plate to chimney chase flat roof or outside wall with four 4 screws Use outdoor sealant to seal the transition plate to the surface 2 Cut inlet air pipe and flue exhaust pipe to correct lengths For vertical terminations through the roof or chimney the air intake and exhaust pipe termination must be a minimum of 12 inches a...

Page 18: ...total vertical length is 20 feet The three 90 elbows are equivalent to 9 feet bringing the total to 40 feet Note The exhaust must be a minimum of 3 inches above the inlet air pipe The flue must be at least 12 inches from the roof line and it is recommended to be at least 12 inches above the maximum expected snow level as indicated in Figures 7 9 13 14 16 and 20 Note On horizontal runs a P V C supp...

Page 19: ...cations a colinear transition plate model PVCT can be used to minimize clearances between intake and exhaust pipes For exhaust and intake air cap pipes with any of the following Vertical termination cap model PVVTC PTrap or two 90º el bows When transition plate model PVCT is used two termina tion caps model PVVTC may NOT be used Note If transition plate model PVCT is used the measurement for cente...

Page 20: ...BOVE THE EXPECTED SNOW LEVEL 3 24 OPTION OPTION AIR INTAKE PTRAP 2 90 ELBOWS SUPPLIED BY INSTALLER OR TERMINATION CAP MODEL PVVTC PTRAP TO FACE AWAY FROM ROOF EXHAUST TERMINATION CAP MODEL PVVTC PTRAP OR 2 90 ELBOWS SLOPE Colinear Direct Vent Insert Installation Figure 19 Colinear Direct Vent Pitched Roof Installation Figure 20 Determining Minimum Vent Height Above the Roof ROOF PITCH H Min Flat t...

Page 21: ...nlet duct to rear of fireplace 6 screws Step 4 Install silicone around connection between co axial adaptor and co axial air inlet duct 4 1 2 MINIMUM VENT LENGTH 3 13 16 MINIMUM TUBE LENGTH Step 5 Slide co axial vent pipes into co axial adaptor Cut the PVC co axial pipes at this time Minimum horizontal vent length 4 1 2 11 4 cm Minimum tube length 3 13 16 9 7 cm Step 6 Direct vent co axial venting ...

Page 22: ...ch pipe 45 elbows can be purchased from a local hardware store 47 5 1 2m Maximum Horizontal Venting 47 1 2 1 2 m Minimum Horizontal Venting 4 10 2 cm EXHAUST OPENING MUST BE POINTED DOWNWARD Direct Vent System Building Exterior View PVVK 24H AND PVVK 48H CO AXIAL VENT KIT cont 1 9 16 4 3 32 Figure 24 Figure 21 Figure 22 Figure 23 ...

Page 23: ...um Exterior Grade Dimension EXTERIOR GRADE FLUE CENTER 12 30 5cm MIN Figure 26 Minimum Exterior Grade Dimension Existing Fireplace Installation PVVK 24H AND PVVK 48H CO AXIAL VENT KIT cont DIRECT VENT FLUE KIT FLUE CENTER 12 30 5 cm MINIMUM EXTERIOR GRADE GAS SUPPLY SURROUND MANTEL Figure 27 Horizontal Venting ...

Page 24: ...mum 12 5 8 minimum 17 7 8 minimum B 25 1 4 minimum 27 maximum when using PVE 1 or PVE 2 Surround Kits C 28 1 2 minimum 33 minimum recommended for service 34 1 2 maximum when using PVE 1 Surround Kit 37 maximum when using PVE 2 Surround Kit When using a 90 elbow on the flue exhaust Single Vent Direct Vent and Colinear Vent Co axial Vent Flex Vent Fireplace Mantis A 19 1 2 minimum 19 1 2 minimum 18 ...

Page 25: ... B 25 1 4 minimum 27 maximum when using PVE 1 or PVE 2 Surround Kits C 28 1 2 minimum 33 minimum recommended for service 34 1 2 maximum when using PVE 1 Surround Kit 37 maximum when using PVE 2 Surround Kit When using a 90 elbow on the flue exhaust Single Vent Direct Vent and Colinear Vent Flex Vent Fireplace Mantis A 19 1 2 minimum 19 1 2 minimum 23 3 4 minimum B 25 minimum 27 3 4 maximum when us...

Page 26: ...iency Fireplace has been tested and approved for zero clearance to combustible materials It is recommended that clearances as listed above should be maintained to allow for removal of the product for servicing C C A B B ACCESS PANEL Figure 31 Figure 32 Mantel and Ceiling Clearances Figure 34 Co axial Venting Installation Shown Single Flue requires surround for combustion air Figure 33 12 18 24 8 6...

Page 27: ...replace has been tested and approved for zero clearance to combustible materials It is recommended that clearances as listed above should be maintained to allow for removal of the product for servicing Mantel and Ceiling Clearances Figure 38 12 18 24 8 6 4 COMBUSTIBLE TRIM AND MANTELS ALLOWED IN SHADED AREA 44 3 4 CEILING 4 3 4 Figure 35 Figure 37 A B B 6 1 4 MIN ACCESS PANEL ACCESS PANEL Figure 3...

Page 28: ... Pedestal and Single Flue Adaptor Figure 39 28 25 1 4 27 3 4 FLUE OUTLET 16 15 16 17 5 8 3 9 16 9 0cm Bay Window Mantis without pedestal Figure 40 6 17 13 16 6 1 2 PVE 1 or PVE 2 SURROUND PVVK CFA FLEX VENT PVVK FC VENT ADAPTOR 11 3 32 12 3 4 6 1 2 PV 4H SHORT TOP COVER KIT PV 2H SLIM TOP COVER KIT Bay Window Mantis Insert with Slim and Short Top Cover Kits and Flex Kits Figure 41 ...

Page 29: ...VER 29 3 4 5 15 16 23 13 16 PV 2H SLIM TOP COVER KIT 11 5 16 3 3 9 16 6 Bay Window Mantis Fireplace with PVE 1 Mantel Surround with PV 2H Slim Top Cover Kit Figure 42 Bay Window Mantis Fireplace with PVE 1 Mantel Surround with PV 4H Short Top Cover Kit Figure 43 Rear View Figure 44 FLUE OUTLET AIR INLET ELECTRIC CORD 13 16 1 7 5 16 2 13 16 1 7 16 3 9 16 1 1 2 6 1 8 GAS LINE OPENING ...

Page 30: ... Kit FFK28 BL CM HP SS Contains surround hood lower front Figure 47 Fireplace with Flex Vent PVVK CFA FLEX VENT KIT 23 1 2 24 3 4 MIN 6 1 2 17 3 16 3 9 16 FLUE OUTLET 24 3 4 MIN Figure 46 16 15 16 11 16 1 3 8 24 3 4 MIN 3 9 16 42 7 8 32 1 2 Figure 45 Figure 48 Fireplace 42 7 8 inch Louverless Surround Kit FHK28 BL SS Contains surround brackets and air deflector FIREPLACE MANTIS SPECIFICATIONS ...

Page 31: ...ith 38 Inch Surround FIK28 BL CM HP SS Contains surround hood lower front Figure 51 4 8 Figure 52 Clearance for Access Panel In Wall Units See Gas Connection Instructions FLUE OUTLET AIR INLET ELECTRIC CORD GAS LINE OPENING 1 1 8 7 5 16 4 3 16 2 5 8 6 1 8 3 9 16 13 16 1 28 Figure 53 ...

Page 32: ...ible line can be pushed back into the fireplace 3 Place rubber grommet that is supplied in hardware packet over the flexible gas line and secure in the hole in the back of the fireplace Gas Connection In Wall Units Fireplace Mantis ONLY 1 Remove the access plate on the left side of the cabinet by removing three screws as shown in Figure 56 Put the screws aside 2 Push the factory supplied flexible ...

Page 33: ...T FLAME SENSOR REAR BURNER FRONT BURNER Firebox Layout Figure 57 Installation Sequence 1 To access the log set parcel lift off the top panel 2 Pivot the left and right panels open 3 Unhook the main door latches located on the right and left side of the fireplace then remove the door 4 Place the Rear Right Log B and the Rear Left Log A behind the rear burner all the way against the back of the fire...

Page 34: ... F Log to ensure proper alignment of A and D Logs See Figure 5 F G A B D C E Figure 62 10 Verify that the Rear Logs A and B are still against the back of the firebox 11 Verify that the logs are not in contact with the flame sensor Interference with the flame sensor will effect the operation 12 Place the door assembly on the fireplace and secure with the main door latches located on the right and l...

Page 35: ... front log support shelf The charred portion of log must face inward See Figure 65 5 Place the Front Right Log F on the right side of firebox bot tom The notch in the bottom of Front Right Log fits over the front flame sensor The log should be positioned fully forward and to the right against the Right Log C See Figure 64 6 Place the Front Left Log E on left side of the firebox bottom The notch in...

Page 36: ...erify the incoming neutral line is connected to the white wire and the incoming hot line is con nected to the black wire The fireplace will not operate properly unless the polarity and ground are correct Figure 68 Figure 69 WARNING Potential risk of fire electric shock and personal injury Take precautions to reduce such risks CAUTION Label all wires prior to disconnection when servicing controls W...

Page 37: ... place correctly See pages 33 to 35 The logs must be in the correct position or the fire place will not operate correctly DO NOT light fireplace without the logs installed the fireplace will not operate properly 6 Verify that all panels are secured in place and that the glass assembly door has been locked in position 7 Verify the two burner switches are in the OFF position before applying power an...

Page 38: ...y gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above on this la bel 2 Set the thermostat if used to the lowest setting 3 Turn off all electric power to the appliance Turn off electrical control switches to O 4 This appliance is equipped with an ignition device that automatically lights the burner Do not try to light the burner by hand 5 Remove the...

Page 39: ...ont burner and back burner will flash 2 The inducer will activate immediately and will prove the pres sure switch within 16 seconds This will initiate the ignition sequence 3 The rear igniter HSI will energize and start to glow red 4 Within 3 to 5 seconds the gas valve will open and ignite the rear burner The flame sensor will verify the flame is present within 2 to 5 seconds 5 The igniter for the...

Page 40: ...n the outlet side of the gas control Blower Operation The circulating air blower will automatically engage and increase in speed depending on the operation of the burners In most cir cumstances the circulating blower will start 3 to 5 minutes after ignition of the burners Once the fireplace is turned off or the call for heat has been sat isfied the circulating blower will continue to run The blowe...

Page 41: ...ce system when a potentially unsafe condition exists The remote control system offers the user a battery operated remote control The transmitter operates on 2 1 5V AAA batteries It is recommended that ALKALINE batteries always be used for longer battery life and maximum operational performance Before using the transmitter install the 2 AAA transmitter batteries into the battery compartment Use cau...

Page 42: ...HERMOSTAT MODE and DESIRED room temperature Press the MODE key until the LCD screen shows the word ROOM then the remote is in the thermostatic mode Press and hold the SET key until the desired set temperature is reached By pressing and holding the set key the LCD screen set numbers will increase from 45 to 99 then restart over at 45 Next release the SET key The LCD screen will display the set temp...

Page 43: ...longer battery life and maximum microprocessor performance IMPORTANT New or fully charged batteries are essential for proper operation of the remote receiver The remote receiver houses the microprocessor that responds to commands from the transmitter to control system opera tion It emits one beep when it receives an ON or OFF command manually but no beep when cycling on and off automati cally in T...

Page 44: ...TION SAFETY TRANSMITTER C S TX This ECS remote control has a COMMUNICATION SAFETY function built into its software It provides an extra margin of safety when the TRANSMITTER is out of the normal 20 foot operating range of the receiver The COMMUNICATION SAFETY feature operates in the following manner in all OPERATING MODES ON ON THERMOSTAT At all times and in all OPERATING MODES the transmitter sen...

Page 45: ...nt temperature drops below 120 F When the temperature drops below 120 F the beeping will cease providing the user has reset the THERMISTOR by pushing the MODE button to ON to operate the fireplace either manually or thermally Allow sufficient time for the receiver to cool below 120 F and then press MODE button to stop beeping MATCHING SECURITY CODES Each transmitter can use one of 1 048 576 unique...

Page 46: ...wing manner Make sure the batteries are correctly installed in the RECEIVER One reversed battery will keep receiver from operating properly Check battery in Transmitter to make sure contacts are touching and ends of battery Bend metal contacts in for tighter fit Be sure RECEIVER and Transmitter are within 20 25 operating range Keep RECEIVER from temperatures exceeding 130 F Battery life shortened ...

Page 47: ... and is transfer ring the condensate there may be a noticeable hissing sound This is normal and the sound should persist for less than 30 sec onds The amount of condensate created will vary based on several factors including but not limited to location of fireplace air tem perature length of venting and whether the vent pipe is horizontal or vertical The humidifier will operate intermittently whil...

Page 48: ...te Press the red button so it is not illuminated then the fireplace will return to normal operation Battery Operated Controls This unit is equipped with a factory installed wireless remote All Remote Controls are all battery operated devices Optional Battery Operated Control FRBTP Battery Operated Remote with Programmable Ther mostat TRW Battery Operated Wireless Remote Wall Thermostat Note These ...

Page 49: ... door latches on both the left and right sides of the firebox 4 Carefully grab the glass frame and pull towards you Do not damage or remove the gasket from the door FIREPLACE MANTIS MODELS Removing the Glass Door 1 Remove the lower louvered panel by lifting up then pulling out 2 Release the two hinge clips on underside of firebox 3 Angle the bottom of glass assembly approximately 60 de grees out f...

Page 50: ...eplaces equipped with FIK FFK or FWK Surrounds or on the inside bottom flange of the surround FHK Surrounds To clean the filter on fireplaces equipped with the lower louver panel simply remove the panel and disengage the filter rod from its retaining holes Figures 78 and 79 For fireplaces equipped with louverless FHK surrounds the en tire surround must be removed from the fireplace This is accom p...

Page 51: ... the flue and inlet pipes do not have any cracks or holes X Verify burner flame X Clean the blower compartment X Clean the burner X Verify the condensate system is clean and leak free X Clean the filter X X Clean the glass X X If service is needed to the condensate pump the wires must be attached in the same order they were removed Figure 81 If the pump is replaced follow the wire connection instr...

Page 52: ...20 R10491 GASKET INLET AIR DUCT 21 21641 BRACKET ASSEMBLY THERMISTER SPRING CLIP INCLUDED 22 R4053 CLAMP DOOR 4 USED ON UNIT 23 22773 THERMISTER ASSEMBLY 24 R10488 3 8 ELBOW 90 2 REQUIRED 25 21640 BRACKET ASSEMBLY SPRING CLIP INCLUDED 26 21665 RIGHT SIDE DOOR ASSEMBLY 27 21651 TUBING FIREBOX TO PRESSURE SWITCH 28 R8835 FITTING BARBED HOSE 29 22865 IGNITOR HOT SURFACE ASSEMBLY 30 21611 BRACKET IGNI...

Page 53: ...6582 FRONT PANEL ASSEMBLY INCLUDES 82 83 59 R8840 WIRE HARNESS ASSEMBLY WITH ECONOMY SWITCH 60 R8809 SWITCH DOUBLE ROCKER 61 R8904 CIRCUIT BOARD 62 25226 CIRCUIT BOARD PLATE 63 R10759 RIBBON CABLE 64 R11043 CIRCUIT BOARD WIRE HARNESS 65 R10182 WIRE HARNESS 120V 66 R10183 WIRE HARNESS 12V 67 R10190 WIRE HARNESS 12V 68 29355 PUMP ASSEMBLY INCLUDES 14 55 69 R10489 AIR PRESSURE SWITCH 70 R8881 CAPACIT...

Page 54: ...30259 0 0212 Page 54 BAY WINDOW MANTIS PARTS VIEW 1 3 2 4A 4B 4C 5 6 8 25 22 5 17 21 18 22 15 10 8 36 12 20 19 14 7 11 28 27 13 81 ...

Page 55: ...e 55 BAY WINDOW MANTIS PARTS VIEW 77 73 74 75 76 72 78 59 43 40 41 46 47 46 44 49 48 41 40 45 31 32 33 34 30 38 39 37 35 42 29 50 51 24 9 63 64 57 82 48 83 56 52 16 69 70 67 66 65 71 58 60 55 68 54 53 23 61 62 79 80 36 ...

Page 56: ...SENSOR 2 REQUIRED 33 25210 AIR DUCT CHANNEL 34 25214 PANEL RIGHT SIDE 35 25222 DOOR BRACKET 2 REQUIRED 36 R4053 DOOR CLAMP 2 REQUIRED 37 25225 LATCH BRACKET 2 REQUIRED 38 26087 SUMP ASSEMBLY INCLUDES 62 64 39 26089 FLEX PIPE ASSEMBLY REQUIRES 2 65 40 29721 HEAT EXCHANGER ASSEMBLY INCLUDES 39 62 65 41 25204 PANEL BACK 42 R10796 ORIFICE HOLDER REAR 43 R10182 WIRE HARNESS 120V 44 R10190 WIRE HARNESS ...

Page 57: ...ACE MANTIS PARTS VIEW 51 58 53 54 52 57 55 56 1 2 3 4 5 6 7 8 9 11 12 13 14 17 18 19 20 21 22 23 44 43 46 45 24 25 26 27 28 50 33 49 35 40 38 63 65 41 37 36 35 32 10 31 31 30 59 60 61 34 15 16 48 32 37 36 42 29 47 62 65 59 39 64 ...

Page 58: ...treet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTRIBUTOR LIST Parts Not Under Warranty Parts can be ordered through your Service Person Dealer or a Master Parts Distributor See this page for the Master Parts Distribu tors list For best results the s...

Page 59: ...of purchase Empire will repair or replace at Empire s option Duties Of The Owner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Dama...

Page 60: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer www empirecomfort com ...

Reviews: