background image

42603-4-0421

Page 39

1.  Spark ignitor will not light pilot after repeated depressing 

of piezo ignitor button.

a.  Defective ignitor (no spark at electrode) - Check for spark at 

electrode and pilot; if no spark and electrode wire is properly 

connected, replace ignitor.

b.  No gas or low gas pressure. 

  - Check remote shut off valves from stove. Usually there is 

a valve near the main. There can be more than one valve 

between the stove and main.

   - Low pressure can be caused by a variety of situations 

such as a bent line, too narrow diameter of pipe, or low line 

pressure. Consult with plumber of gas supplier.

c.  No Propane in tank. 

  - Check Propane tank. Refill tank.

2.  Pilot will not stay lit after carefully following lighting 

instructions.

a.  Defective thermocouple.

  - Check that pilot flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement.

  - Ensure that the thermocouple connection at the gas valve 

is fully inserted and tight (hand tight plus 1/4 turn) faulty 

thermopile if reading is below specified minimum.

  - Disconnect the thermocouple from the valve, place one 

millivolt meter lead wire on the tip of the thermocouple and 

the other meter lead wire on the thermocouple copper lead. 

Start the pilot and hold the valve knob in. If the millivolt 

reading is less than 15 MV, replace the thermocouple.

b.  Defective valve.

 

- If thermocouple is producing more than 15 millivolts, replace 

faulty valve

3.  Pilot burning, no gas to burner, valve knob "ON", on/off 

switch "ON."

a.  "On/Off" switch, wall switch, or wires defective.

  - Check "on/off" switch and wires for proper connections. 

Place  jumper  wires  across  terminal  at  switch  -  if  burner 

comes on, replace defective switch. If OK, place jumper 

wires across switch wires at gas valve-if burner comes on, 

wires are faulty or connections are bad.

b.  Thermopile may not be generating sufficient milli-voltage.

  -  If  the  pilot  flame  is  not  close  enough  physically  to  the 

thermopile, adjust the pilot flame.

  - Be sure the wire connections from the thermopile at the 

gas valve terminals are tight and the thermopile is fully 

inserted into the pilot bracket.

  - Check the thermopile with a millivolt meter. Take the 

reading at TH-TP & TP terminals of the gas valve. The meter 

should read 325 millivolts minimum, while holding the valve 

knob depressed to the pilot position, with the pilot lit, and 

the ON/OFF switch in the OFF position. Replace the faulty 

thermopile if the reading is below the specified minimum.

  -With the pilot in the ON position, disconnect the thermopile 

leads from the valve. Take a reading at the thermopile leads. 

The reading should be 325 millivolts minimum. Replace the 

thermopile if the reading is below the minimum.

c.  Defective valve.

  - Turn valve knob to "ON." Place ON/OFF switch to "ON." 

Check with millivolt meter at thermopile terminals. Millivolt 

meter should read greater than 100 M.V. If the reading is 

okay and the burner does not come, replace the gas valve.

d.  Plugged main burner orifice.

  - Check main burner orifice for blockage, clean main burner 

orifice.

4.  Frequent pilot outage problem.

a.  Pilot flame may be too high or too low, or blowing (high), 

causing pilot safety to drop out.

  - Clean and adjust flame for maximum flame impingement 

on the thermocouple. Follow lighting instructions carefully.

5.  The pilot and main burner extinguish while in operation.

a.  No Propane in tank.

  - Check Propane tank. Refill fuel tank.

b.  Inner vent pipe leaking exhaust gases back into system.

  - Check for leaks.

c.  Glass too loose, gasket leaks in corners after usage.

  - Be certain glass assembly is installed correctly and tighten 

corner.

d.  Horizontal vent improperly pitched.

  - The horizontal vent cap should slope down only enough 

to prevent any water from entering the unit. The maximum 

downwards slope is 1/4 inch.

e.  Bad thermopile or thermocouple.

  - Replace if necessary.

f.  Improper vent cap installation.

  - Check for proper installation and freedom from debris or 

blockage.

6.  Glass soots.

a.  Flame impingement on logs.

  - Adjust the log set so that the flame does not excessively 

impinge on it. 

7.  Flame lifts off main burner.

a.  Insufficient oxygen being supplied.

  - Check to make sure vent cap is installed properly and free 

of debris. Make sure that vent system joints are tight and 

have no leaks.

  - Check to make sure that no material has been placed at 

the burner base.

  - Be sure glass is tightened properly on unit, particularly on 

top corners.

8.  Doors open on their own.

a.  Casting not level.

 

- Loosen front leveling bolts to elevate front of casting slightly 

above the rear of casting.

With proper installation and maintenance, your new Direct Vent Stove should provide years of trouble-free service. If you do ex

-

perience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis 

of problems and the corrective action to be taken.

MILLIVOLT TROUBLESHOOTING

Summary of Contents for DVP20MS

Page 1: ...tructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier INSTALLER Leave this man...

Page 2: ...erating Instructions 34 Main Burner Flame Characteristics 35 Wiring 36 Millivolt Lighting Instructions 37 Millivolt Wiring 38 Millivolt Troubleshooting 39 IP Operating Instructions 40 IP Electronic Sy...

Page 3: ...ended for use with glass doors or equivalent shall emphasize that the appliance is not for use with glass doors 11 Where applicable provide a means by which the consumer can identify the barrier such...

Page 4: ...b or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a closed area...

Page 5: ...provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be per manently mounted to the exterior of the building at a...

Page 6: ...ch work familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction Commonwealth of Massachusetts The installation must be made by a licensed...

Page 7: ...ermination Kit includes SD46DVA48B 2 ea SD46DVADC SD46DVAF6 SD46DVAFS SD46DVASC SD46DVAHC NOTE On horizontal applications snorkel kits may be used DVP20MS LP NAT and DVP30MSNAT SD 46DVASNK14 14 inch p...

Page 8: ...ed for pressure test Never pressure test with appliance connected control valve will sustain damage NOTE The gas control is equipped with a captured screw type pressure test point therefore it is not...

Page 9: ...with carpeting vinyl wood flooring or other combustible material 6 153mm TO SIDE WALL 6 153mm TO SIDE WALL 6 153mm TO COMBUSTIBLE MATERIAL 6 153mm TO COMBUSTIBLE MATERIAL 36 915mm TO CEILING OR HORIZO...

Page 10: ...tion Kits DVVK 4FRE DVVK 4FREVS Duravent Pro 4 6 5 8 American Metal 4 6 5 8 Selkirk Direct Temp 4 6 5 8 ICC Inc Excel 4 6 5 8 MetalFab SureSeal 4 6 5 8 BDM Manufacturing 4 6 5 8 Olympia VENTIS 4 6 5 8...

Page 11: ...or closer than 1 on the sides and bottom Cutting the Hole After the appliance has been positioned in its permanent location the hole through the exterior wall of the house can be cut This hole needs...

Page 12: ...90 for the second elbow subtract 5 feet from a horizontal run VENTING STOVE CONT D A A Dimension DVP20MS 24 610mm DVP30MS 27 686mm Figure 8 Snorkel Installation VENTING APPLICATIONS INFORMATION Model...

Page 13: ...eet the horizontal run to the outer wall flange of the vent termination must not exceed 4 feet with one 90 elbow EXAMPLE B If the vertical rise from the appliance outlet is 14 feet the horizontal run...

Page 14: ...51 mm on top Important When vent termination exits through foundation less than 20 below siding outcrop the vent pipe must flush up with the siding 46 DVA HC termination cap must also be used Informat...

Page 15: ...tance of 2 feet 61 cm from the center line of the terminal 24 in 61 cm 24 in 61 cm L Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 13 m 7 ft 2 13 m E Clearance to...

Page 16: ...d with four equally spaced indented sections When the internal beads of each starting 6 5 8 inch outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked...

Page 17: ...inch x 11 inch hole for 4 x 6 inch pipe and 10 1 2 x 10 1 2 inch hole for 5 x 8 inch pipe previously cut Secure with nails or screws Continue the vent run through the firestops See Figure 15 11 297 m...

Page 18: ...ews provided Before attachment of the termination run a bead of silicone sealant rated above 250 F on its outside edge too so as to make a seal to that exterior wall NOTE Wood screws can and should be...

Page 19: ...cases increasing the vent height may solve this problem When terminating the vent cap near an exterior wall or overhang maintain minimum clearances as shown in Figure 20 General Maintenance Conduct a...

Page 20: ...Applications Your Gas Stove has been approved for a Vertical installations up to 40 feet of vent run b Two sets of 45 degree elbow offsets within these vertical installations From 0 to a maximum of 8...

Page 21: ...42603 4 0421 Page 21 Log Description Part Number Front View Top View Log A 29790 Log B 29792 Log C 29791 Log D 29793 DVP20MS LOG IDENTIFICATION...

Page 22: ...the two right pins on the burner 3 Place Log C onto the two left pins on the burner 4 Place Log D on the pin on Log A with the fork resting on Logs B and C 5 Place ember material on front burner ports...

Page 23: ...42603 4 0421 Page 23 DVP20MS LOG PLACEMENT 1 Place Log A onto the pins on the Log Support Shelf as shown below TOP VIEW FRONT VIEW...

Page 24: ...42603 4 0421 Page 24 DVP20MS LOG PLACEMENT 2 Place Log B onto the two right pins on the burner as shown below TOP VIEW FRONT VIEW...

Page 25: ...42603 4 0421 Page 25 DVP20MS LOG PLACEMENT 3 Place Log C onto the two left pins on the burner as shown below TOP VIEW FRONT VIEW...

Page 26: ...42603 4 0421 Page 26 DVP20MS LOG PLACEMENT 4 Place Log D on the pin on Log A with the fork resting on Logs B and C as shown below TOP VIEW FRONT VIEW...

Page 27: ...42603 4 0421 Page 27 DVP20MS LOG PLACEMENT 5 Assembly is completed TOP VIEW FRONT VIEW...

Page 28: ...42603 4 0421 Page 28 Log Description Part Number Front View Top View Log A 29795 Log B 29797 Log C 29796 Log D 29798 DVP30MS LOG IDENTIFICATION...

Page 29: ...42603 4 0421 Page 29 DVP30MS LOG PLACEMENT 1 Place Log A onto the pins on the Log Support Shelf as shown below TOP VIEW FRONT VIEW...

Page 30: ...42603 4 0421 Page 30 DVP30MS LOG PLACEMENT 2 Place Log B onto the two right pins on the burner TOP VIEW FRONT VIEW...

Page 31: ...42603 4 0421 Page 31 DVP30MS LOG PLACEMENT 3 Place Log C onto the two left pins on the burner TOP VIEW FRONT VIEW...

Page 32: ...42603 4 0421 Page 32 DVP30MS LOG PLACEMENT 4 Place Log D on the pins on Logs A and C Place ember material on front burner ports as shown in Figure 25 TOP VIEW FRONT VIEW...

Page 33: ...42603 4 0421 Page 33 DVP30MS LOG PLACEMENT 5 Assembly is completed TOP VIEW FRONT VIEW...

Page 34: ...ot flame to operate an additional one to two minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical current to build...

Page 35: ...ith your bare hands Always wear gloves to prevent skin irritation During the annual inspection and maintenanceappointment theservicepersonshouldcleandust lint and any light accumulation from the logs...

Page 36: ...h ons attach to the gas valve An additional green wire and the red wire which are stripped and bare will attach to the 750 millivolt wall thermostat accessory or to one of the other accessories that c...

Page 37: ...thermostat to desired setting A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area...

Page 38: ...WARNING Label all wires prior to disconnection when servicing con trol Wiring errors can cause improper and dangerous op eration Verify proper operation after servicing For Standing Pilot Ignition Wi...

Page 39: ...t and the ON OFF switch in the OFF position Replace the faulty thermopile if the reading is below the specified minimum With the pilot in the ON position disconnect the thermopile leads from the valve...

Page 40: ...l be energized allowing gas to flow to the burner 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for In termittent Pilot controls found in this manual and on labels found in the control compartment loc...

Page 41: ...factured mobile home where not prohibited by local codes This appliance is not convertible for use with other gases unless a certified kit is used CAUTION Do not operate the appliance with panel s rem...

Page 42: ...ration information FOR YOUR SAFETY READ BEFORE LIGHTING A Thisappliance hasapilot whichcanbelighted withthemanual on off switch a remote control or by switching the receiver switch to the ON position...

Page 43: ...ctions on page 31 and Wiring Diagram on page 30 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and...

Page 44: ...ire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness 2 I...

Page 45: ...and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure at...

Page 46: ...ass when glass is hot Failure to follow these warnings could cause a serious safety issue to the operator such as fire or other serious conditions Figure 33 IMPORTANT Turn off gas before servicing app...

Page 47: ...42603 4 0421 Page 47 Figure 35 Figure 36 MAINTENANCE CONT D...

Page 48: ...ualified service person More frequent cleaning might be required due to excessive lint from carpeting bedding material etc Keep burner and control compartment clean Examine venting system periodically...

Page 49: ...ATURAL 9 R7611 R10424 PILOT ASSEMBLY PROPANE 10 R9189 R9189 R9189 R9189 PILOT GASKET 2 REQUIRED FOR DVP20CC70 10 R7617 R7617 PILOT GASKET 11 30457 30457 30457 30457 BURNER ASSEMBLY 12 R5676 R5676 R567...

Page 50: ...1 29791 29791 29791 LOG LEFT 33 29792 29792 29792 29792 LOG RIGHT 34 R3436 R3436 R11558 R11558 REMOTE OFF ON SWITCH 35 30679 30679 30679 30679 WIRE CHANEL RIGHT 36 30680 30680 30680 30680 WIRE CHANEL...

Page 51: ...rt number and description of part coincide IP ONLY IP ONLY IP ONLY IP ONLY 1 1 2 2 3 3 4 4 4 4 5 5 5 5 6 6 7 7 8 8 9 9 9 9 10 10 10 10 10 10 10 10 11 11 13 13 14 14 18 18 15 15 16 16 16 16 17 17 20 20...

Page 52: ...EAR LOG SUPPORT 9 R7612 R10423 PILOT ASSEMBLY NATURAL 9 R7611 R10424 PILOT ASSEMBLY PROPANE 10 R9189 R9189 R9189 R9189 PILOT GASKET 10 R7617 R7617 PILOT GASKET 11 30899 30899 30899 30899 BURNER ASSEMB...

Page 53: ...6 29796 29796 29796 LOG LEFT 33 29797 29797 29797 29797 LOG RIGHT 34 R3436 R3436 R11558 R11558 REMOTE OFF ON SWITCH 35 30679 30679 30679 30679 WIRE CHANEL RIGHT 36 30680 30680 30680 30680 WIRE CHANEL...

Page 54: ...6 6 7 7 8 8 9 9 9 9 10 10 10 10 10 10 10 10 11 11 13 13 14 14 18 18 15 15 16 16 16 16 17 17 20 20 19 19 21 21 23 23 22 22 22 22 23 23 26 26 25 25 27 27 28 28 29 29 DVP30 DVP30 30 30 30 30 31 31 32 32...

Page 55: ...and continue installation with appropriate wire channel shipped with blower See Figure 38 5 Route fan control wires through rectangular notch on wire channel left 6 Attach 1 4 push on terminal from b...

Page 56: ...ccordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized This appli...

Page 57: ...hing 2 R1499 Rubber Grommet 3 31739 Blower Housing 4 R1410 Strain Relief Bushing 5 R12447 Blower Assembly 6 24225 Blower Cover 7 R6159 Cord Set 8 R10363 Wire Harness 9 R2503 Fan Control 10 24222 Fan C...

Page 58: ...nt to the exterior bottom of the appliance 3 Place the large diameter holes in the keyholes over and behind the four hex head screws that were loosened in Step 1 Push inwardontheblowerassemblytolockth...

Page 59: ...ove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be purchased plugged into the ungrounded receptacleanditswireconnectedt...

Page 60: ...R1454 Brass Bushing 4 Required 2 R1499 Rubber Grommet 4 Required 3 CI002 Blower Housing 4 R1517 Tinnerman Clip 4 Required 5 R2804A Blower Assembly 6 CI003 Blower Housing Cover 7 R2099 Cord Set 8 R376...

Page 61: ...se and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model...

Page 62: ...as Inlet Pipe 3 8 3 8 Orifice 2 15mm 55 39 1 55mm Gas Supply Pressure Max 10 5 W C 2 614 kPa 13 0 W C 3 237 kPa 10 5 W C 2 614 kPa 13 0 W C 3 237 kPa Gas Supply Pressure Min 4 5 W C 1 121 kPa 11 0 W C...

Page 63: ...tile wood flooring or other combustiblematerialastheappliance s base extends the width and depth of the appliance 6 153mm TO SIDE WALL 6 153mm TO SIDE WALL 6 153mm TO COMBUSTIBLE MATERIAL 6 153mm TO C...

Page 64: ...42603 4 0421 Page 64 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 65: ...42603 4 0421 Page 65 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 66: ...42603 4 0421 Page 66 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 67: ...orkmanship within one year from the date of purchase Empire will repair or replace it at Empire s option Duties of the Owner Have the appliance installed by a qualified installer and operate and maint...

Page 68: ...ww empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question plea...

Reviews: