background image

29210-0-0911

Page 35

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free 

service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified 

service person in the diagnosis of problems and the corrective action to be taken.

1.  Spark ignitor will not light pilot after repeated triggering 

of piezo ignitor button.

a.  Ensure the elctrode wire (piezo wire) is properly connected 

to the piezo and electrode.

b.  Defective ignitor (no spark electrode) 

 

—Check for spark at electrode and pilot; if no spark and 

electrode wire is properly connected, replace ignitor.

c.  No gas or low gas pressure.

 

—Check  remote  shut  off  valves  from  fireplace.  Usually 

there is a valve near the main. There can be more than 

one (1) valve between the fireplace and main.

 

—Low pressure can be caused by a variety of situations 

such as a bent line, too narrow diameter of pipe, or low 

line pressure. Consult with plumber or gas supplier.

d.  No LP in tank. 

  —Check LP (propane) tank. Refill tank.

2.  Pilot  will  not  stay  lit  after  carefully  following  lighting 

instructions.

a.  Defective thermocouple.

 

—Check that pilot flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement.

 

—Ensure the thermocouple connection at the gas valve 

is fully inserted and tight (hand tight plus 1/4 turn). Faulty 

thermocouple if reading is below specified minimum of 15 

millivolts.

 

—Disconnect the thermocouple from the valve, place one 

millivolt meter lead wire on the end of the thermocouple 

and the other millivolt meter lead wire on the thermocouple 

copper wire. Start the pilot and hold the valve knob in. If 

the millivolt reading is less than 15 millivolt, replace the 

thermocouple.

b.  Defective valve.

 

—If thermocouple is producing more than 15 millivolts, 

replace faulty valve.

3.  Pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.”

a.  REMOTE/OFF/ON switch, wall switch, remote control or 

wires defective.

 

—Check REMOTE/OFF/ON switch and wires for proper 

connections. Place jumper wires across terminal at switch. 

If burner comes on, replace defective switch. If OK, place 

jumper wires across switch wires at gas valve-if burner 

comes on, wires are faulty or connections are bad.

b.  Thermopile may not be generating sufficient millivolts.

 

—If the pilot flame is not close enough physically to the 

thermopile, adjust the pilot flame.

 

—Be sure the wire connections from the thermopile at the 

gas valve terminals are tight and the thermopile is fully 

inserted into the pilot bracket.

 

—Check the thermopile with a millivolt meter. Take the 

reading at TH-TP & TP terminals of the gas valve. The 

meter should read 350 millivolts minimum, while holding the 

valve knob depressed in the PILOT position, with the pilot 

lit, and the REMOTE/OFF/ON switch in the OFF position. 

Replace the faulty thermopile if the reading is below the 

specified minimum. 

 

—With the pilot in the ON position, disconnect the thermopile 

leads from the valve. Take a reading at the thermopile leads. 

The reading should be 350 millivolts minimum. Replace 

the thermopile if the reading is below the minimum.

c.  Defective valve.

 

—Turn valve knob to ON. Place REMOTE/OFF/ON switch 

to ON. Check with millivolt meter at thermopile terminals. 

Millivolt meter should read greater than 200 millivolts. If 

the reading is okay and the main burner does not ignite, 

replace the gas valve.

d.  Plugged main burner orifice.

 

—Check main burner orifice for blockage and remove.

4.  Frequent pilot outage problem.

a.  Pilot flame may be too high or too low, or blowing (high), 

causing pilot safety to drop out.

 

—Clean and adjust flame for maximum flame impingement 

on the thermocouple. Follow lighting instructions 

carefully.

5.  The pilot and main burner extinguish while in operation.

a.  No LP (Propane) in tank. 

 

Check LP (Propane) tank. Refill fuel tank.

b.  Inner vent pipe leaking exhaust gases back into system.

 

—Check for leaks.

c.  Glass too loose, gasket leaks in corners after usage.

 

—Be certain glass assembly is installed correctly.

d.  Horizontal vent improperly pitched.

 

—The horizontal vent cap should slope down only enough 

to prevent any water from entering the unit. The maximum 

downwards slope is 1/4 inch.

e.  Bad thermopile or thermocouple.

 

—Replace if necessary.

f.  Improper vent cap installation.

 

—Check for proper installation and freedom from debris 

or blockage.

6.  Glass soots, and/or soot deposits collected internally.

a.  Flame impingement on decorative glass.

 

—Check and adjust glass positioning. See Page 32. Contact 

Empire Comfort Systems, Inc.

b.  Debris around throat of main burner.

 

—Inspect the opening at the base of the main burner. It is 

imperative that NO material be placed in this opening.

7.  Flame burns blue and lifts off main burner.

a.  Insufficient oxygen being supplied.

 

—Check to make sure vent cap is installed properly and 

free of debris. Make sure that vent system joints are tight 

and have no leaks.

 

—Check to make sure that no material has been placed 

at the main burner base.

STANDING PILOT TROUBLESHOOTING

Summary of Contents for DVL25FP32(N,P)-1

Page 1: ...he information in these instruc tions are not followed exactly a fire or explo sion may result causing property damage personal injury or loss of life WARNING HOT GLASS DO NOT TOUCH NEVER WILL CAUSE B...

Page 2: ...tical Termination 26 27 Alternate On Off Switch Installation 28 Surround Panel Installation 29 Optional Blower Accessory Information 30 Optional Decorative Glass Placement 31 Operating Instructions 32...

Page 3: ...he glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment c...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...2nd St New York N Y 10036 Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the...

Page 6: ...lt Battery Remote ON OFF FWS 1 Millivolt Wall Switch Venting Options Description DVVK 4TSP Top vent kit horizontal 4 1 2 to 6 114 3mm to 152mm wall thickness DVVK 4TP Top vent kit horizontal 8 to 12 2...

Page 7: ...trol are desired Electrical supply requirements for optional blower Properly framed opening size required for installation of the fireplace DV FIREPLACE DIMENSIONS MODEL A B C D E F G H I J K L M N O...

Page 8: ...SIDE WALL FROM EDGE OF DOOR FRAME 3 MIN 3 MIN 3 MIN TOP VIEW NON COMBUSTIBLE AREA TO SIDES AND BACK OF FIREPLACE Figure 3 3 MIN CLEARANCE ABOVE VENT SYSTEM 1 MIN CLEARANCE FROM FRAMING TO VENT SYSTEM...

Page 9: ...ails in Venting Section When you install your Direct Vent Fireplace in D Room divider or E Flat on wall corner positions a minimum of 6 inches clearance must be maintained from the perpendicular wall...

Page 10: ...dures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have...

Page 11: ...appliance 4 Install the side Framing brackets 1 per side using the pi lot holes provided behind the side flanges on the fireplace outer wrap Two setback locations are provided for locating the framin...

Page 12: ...aled Surround Installation To complete the installation of the Loft fireplace a Surround Kit specifically designed for use with these fireplaces must be in stalled prior to use Surround options shown...

Page 13: ...1 4 to 15 3 4 362 mm to 400 mm 7 3 4 to 9 1 4 197 mm to 235 mm 12 17 1 4 to 18 3 4 438 mm to 476 mm 10 3 4 to 12 1 4 273 mm to 311 mm INSTALLATION continued CORNER INSTALLATION VERTICAL 90 ELBOW TO H...

Page 14: ...g Codes before beginning the installation WARNING THIS GAS FIREPLACE AND VENT ASSEMBLY MUST BE VENTED DIRECTLY TO THE OUTSIDEAND MUST NEVER BE ATTACHED TO A CHIMNEY SERVING A SEPARATE SOLID FUEL BURNI...

Page 15: ...ing out at joints or seams Condensate can cause corrosion of caps pipe and fittings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold weather...

Page 16: ...does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example According to the chart the maximum horizontal vent length is 20 and if...

Page 17: ...m above grade level a snorkel kit is recommended It allows installation depth down to 7 178 mm below grade level The 7 178 mm is measured from the center of the horizontal vent pipe as it penetrates t...

Page 18: ...OP OF FIREPLACE SEE FIGURE 17 VENTING CHART FOR PERMISSIBLE H AND V DIMENSIONS VENTING FIREPLACE TOP continued Positioning the Fireplace Determine the exact position of the appliance so the direct ven...

Page 19: ...re 25 Figure 26 EXAMPLES TOP VENT RUN 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 H2 H1 V1 Example H2 2ft 2 90 90 6ft H 8ft V 15ft 3 ft 914 mm H3 1 ft 305mm 4 ft 122mm 6 ft 1 83M 21 ft 6 4M 10 ft 3M V 21f...

Page 20: ...lace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flu...

Page 21: ...center line of the regulator I clearance to service regulator vent outlet 6 feet 1 89 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appl...

Page 22: ...e internal beads of each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked together Continue adding components per the pre planned vent sy...

Page 23: ...ANCE TO COMBUSTIBLES FROM VERTICAL VENT 12 MIN 304 8mm CLEARANCE TO COMBUSTIBLES 3 MIN 76 2mm CLEARANCE TO COMBUSTIBLES Figure 30 Installing Firestops Firestops are required for safety whenever the ve...

Page 24: ...r any obstructions such as wiring or plumbing runs Reposition the appliance and vent system if necessary to accommodate ceiling joists and or obstructions Cut a 10 inch x 10 inch hole through the ceil...

Page 25: ...tside edge too so as to make a seal to the exterior wall NOTE Wood screws can and should be replaced with appropriate fasteners for use on stucco brick concrete or other types of siding CAUTION Ifexte...

Page 26: ...s holes These components should immediately be replaced 2 Remove the cap and shine a flashlight down the vent Remove any bird nests or other foreign material 3 Check for evidence of excessive condensa...

Page 27: ...daptoronfireplace Replace the horizontal and vertical pipe lengths elbows and horizontal or vertical termination kit All vent system components lock into place by sliding the concentric pipe section w...

Page 28: ...ermi nals on the front terminal block of the gas valve See Figure 40 3 Run the low voltage alternate switch wires over to the right or left surround panel Then secure the wires with wire clips provide...

Page 29: ...TO SIDE FLANGES ON INSERT BACK SIDE NOTE INSTALL SURROUND ASSEMBLY SO THAT THE REAR FLANGE OF THE TOP PANEL SETS OVER THE TOP EDGE OF THE TOP SUPPORT BRACKET CENTER SURROUND LEFT TO RIGHT THEN SWING...

Page 30: ...ollows From a cold start the temperature activated fan control switch will normally take 5 10 minutes to heat up and energize the blower Once the blower is energized adjust the blower speed control as...

Page 31: ...only be performed after the DVL Fireplace has been fully installed secured and tested for leaks If operating the burner with a Remote Control make sure all batteries are installed and that the burner...

Page 32: ...our pilot flame to operate an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical curren...

Page 33: ...ed setting THERMOCUPLE ELECTRODE THERMOPILE PILOT FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage pe...

Page 34: ...VE WILL BE DESTROYED WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROL WIRING ERRORS CAN CAUSE IM PROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING For Standin...

Page 35: ...the pilot flame Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt...

Page 36: ...f the appliance 2 During the operating season or in power outage periods it is recommended that the pilot remain in the CPI standing pilot mode to reduce cold start issues and or conserve battery back...

Page 37: ...t is used CAUTION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation...

Page 38: ...structions for detailed operation information FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage person...

Page 39: ...ions on page 24 and Wiring Diagram on page 23 Troubleshooting Before proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and th...

Page 40: ...ire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness 2 I...

Page 41: ...and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure at...

Page 42: ...manufacturing processes fingerprints along with excess sealing materials may be present and should be removed When cleaning do not use abrasives on the porcelain liners or the glass door assembly Clea...

Page 43: ...al information beyond what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 OPTIONAL DECORATIVE GLASS ACCESSORIES Accessory Model Number...

Page 44: ...7155 17155 17155 FLUE OUTLET ASSEMBLY 5 M163 M163 M163 M163 GASKET FLUE CONNECTOR 6 16223 27718 16223 27718 SPRING RETAINER ASSEMBLY 7 27652 27652 27652 27652 NAILING FLANGE 8 R10854 R10854 R10854 R10...

Page 45: ...NAT GAS 25b P182 55 P208 1 45mm P182 55 P208 1 45mm ORIFICE LP GAS 26 R7624 R7624 R7624 R7624 AIR SHUTTER 27 R 10732 R10879 R 10732 R10879 TUBE BURNER 28 11269 11269 11269 11269 GAS LINE BRACKET 29 2...

Page 46: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 47: ...29210 0 0911 Page 47 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 48: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: