Emotron AB 01-3991-11r2
Programming instructions and menu list
49
218
External control opera-
tion mode
000: Forward/ Stop-Reverse/Stop
001: Run/ Stop-Forward/Reverse
002: 3-wire-Run/ Stop
000
219
Remote keypad con-
trol selection
000: Disable (no signal loss detection)
001: Enable. On signal loss stop accord-
ing to [337]
002: Enable. Runs at the last set fre-
quency. On signal loss Stop is according to
[213] setting or Stop key on keypad.
000
Stop VSD
then
connect
remote
keypad
for
proper
opera-
tion *4
Main setup, Motor data
221
Rated motor voltage
*4
222
Rated motor power
*4
223
Rated motor current
*4
224
Rated motor frequency
*4
225
Rated motor speed
0 to 120 (x 100 RPM)
*4
226
Carrier frequency
004 to 016
010
4–16K
Main setup, Motor protection
231
Run stall-prevention
000: Run stall prevention available
001: Run stall prevention unavailable
000
232
Run stall-prevention
level (%)
050 to 300
200
233
Stall prevention time
during run
000: According to dec. time set in [332]
001: According to dec. time set in [239]
000
234
Electronic thermal
relay protection for
motor (OL1)
000: Enable motor protection
001: Disable motor protection
000
235
Acceleration stall-pre-
vention
000: Acceleration stall prevention enable
001: Acceleration stall prevention disable
000
236
Acceleration stall-pre-
vention level (%)
050 to 300
200
237
Deceleration stall-pre-
vention
000: Deceleration stall prevention enable
001: Deceleration stall prevention disable
000
Table 23
Menu Function Description
Range/ Code
Factory
Default
Remarks