CG Drives & Automation 01-5965-01r1
Dual-Pump System Installation
35
7.1.3
Dual-pump alarm relay connection (ALARM & C)
Terminals 6 and 7 on the DCM SLAVE are the alarm relay connections. These
terminals indicate an alarm if a fault is detected by the DCM MASTER or the
DCM SLAVE. See Fig. 16. When powered off, the alarm relay is NC (normally
closed). When powered on, NC or NO (normally open) can be selected. See
Table 8, page 53, window 51.
7.1.4
Dual-pump communication and digital input
connection (DIG & SGND)
Terminals 3 (DIG) and 4 (SGND) are connections for closing contacts and for
communicating between the DCM MASTER and the DCM SLAVE. The digi-
tal input can be used for high-level switch or external reset. The high-level
switch must be connected in series with the DCM MASTER terminal 6
(ALARM) and terminal 3 (C). When external reset is chosen use the pulse sig-
nal. Connect terminal 3 (DIG) on the DCM MASTER to terminal 3 (DIG) on
the DCM SLAVE. Connect terminal 4 (SGND) on the DCM MASTER to ter-
minal 4 (SGND) on the DCM SLAVE. See Fig. 16 and Table 8, page 53, win-
dow 53.
7.1.5
Dual-pump operation relay connection (PUMP)
Connect the control signals for the start and stop equipment for each pump to
the respective DCM as described in Section 6.1.4, page 29. See Fig. 16.
7.1.6
Dual-pump temperature-measuring input
connection (TEMP & SGND)
Connect the temperature sensor and/or motor protection for each pump to the
respective DCM as described in Section 6.1.6. See Fig. 16.
Summary of Contents for DCM
Page 1: ...Emotron DCM Control Unit Instruction manual English...
Page 2: ......
Page 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Page 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Page 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Page 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Page 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Page 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Page 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Page 62: ...58 Service CG Drives Automation 01 5965 01r1...
Page 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Page 65: ......