1. DESCRIZIONE DEI COMPONENTI

GB

GB

Main parts check 
1. Temperature sensor checking

Disconnect the temperature sensor from PCB, measure the resistance value with a tester.

Temperature Sensors. 
Room temperature(T1) sensor, 
Indoor coil temperature(T2) sensor, 
Outdoor coil temperature(T3) sensor, 
Outdoor ambient temperature(T4) sensor, 
Compressor discharge temperature(TP) sensor. 
Measure the resistance value of each winding by using the multi-meter. 

Disconnect the temperature sensor from the PCB, measure the resistance value with a tester.

Temperature sensors:

Indoor temperature sensor (T1)

Evaporator Battery Temperature Sensor (T2)

Condenser Battery Temperature Sensor (T3)

Outdoor temperature sensor (T4)

Compressor Exhaust Temperature Sensor (T5)

9. FUNCTIONAL ANOMALIES

42 Active Frequency Limitations

Bit7

Frequency limit caused by IGBT 

radiator

The displayed value is the hex number. For exam-

ple, display shows 2A, then Bit 5 = 1, Bit 3 = 1, Bit 

1 = 1.It Means the frequency limit caused by T4, 

T3 and current.

Bit6

Frequency limit caused by PFC

Bit5

Frequency limit caused by T4.

Bit4

Frequency limit caused by T2.

Bit3

Frequency limit caused by T3.

Bit2

Frequency limit caused by T5.

Bit1

Frequency limit caused by voltage

Bit0

Frequency limit caused by voltage

43 Average value of  T2

(Sum value T2 of all indoor units) / (Number of internal units in good connection) (cooling: T2B, 

heating: T2)

44 Fan motor status of the outdoor unit

0=off, 1=high speed, 2= midle speed, 3= low speed, 4=Breeze, 5= Super Breeze

45 The last error or security code

00 Means any malfunction and protection

9.3 Check temperature sensors

Summary of Contents for XEVO-0917-M3E

Page 1: ...Air Conditioner Serie XEVO XX17X3E R32 Outdoor Unit INSTALLATION MANUAL AND USING INSTRUCTIONS INSTALLATION MANUAL AND USING INSTRUCTIONS GB GB...

Page 2: ...ecifications and all the information useful for the correct functioning The information contained in this publication may be subject to changes at any time and without any notice whatsoever for techni...

Page 3: ...the units 5 6 Dimensions of the indoor unit 6 EXTERNAL UNIT INSTALLATION 13 6 1 External unit installation 6 2 Outdoor unit condensation drain pipe 6 3 Refrigerating circuit piping 6 4 Electrical sup...

Page 4: ...tion 4 Refrigerating pipe connection 1 4 Product identification table Throughthefollowingtableyoumayidentifythemake upoftheairconditioner Type Power in kBtu h Set UI UE Unit Outdoor Unit Indoor Single...

Page 5: ...rom 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appl...

Page 6: ...dangerous and can cause injury Do not pour or spray water on the air conditioner Do not install the air conditioner near sources emitting excessive vapours moisture oils etc Please use fuses with the...

Page 7: ...dos otocolo di Kyoto No vierta este tipo de gas a la atmosfera Produkt enth lt fluorierte Treibhausgase ch das Kyoto Protokoll abgedeckt werden n Sie Gase nicht in die Atmosph re ab duit contient des...

Page 8: ...re fighting procedures In the event of a fire stop the leak if it is not dangerous Do not extinguish the flames on the leak because there is the possibility of an uncontrolled explosive re ignition Sp...

Page 9: ...ty Inhalation Product difluoromethane LC 0 Rat 4 h 520000 ppm Remarks Gas ECOLOGICAL INFORMATION Bioaccumulation potential Product The product is expected to be biodegradable and it is not expected to...

Page 10: ...h Places with acid or alkaline fumes TV radio acoustic equipment have to remain at a minimum distance of 1 m from the internal unit the external unit the power supply cables pipes otherwise images co...

Page 11: ...d with siphon A D E C B 1 2 1 2 Outdoor Unit Indoor Unit A mm B mm C mm D mm E mm 300 600 300 2000 600 5 3 Distance between the units 5 2 Minimum operational distances OUTDOOR UNIT A Indoor Unit B B M...

Page 12: ...ns of the indoor unit C E H B D A Model E mm D mm H mm C mm A mm B mm XEVO 0917 M3E R32 770 322 555 840 487 298 XEVO 1217 M3E R32 770 322 555 840 487 298 XEVO 1817 D3E dual 800 365 554 860 514 340 XEV...

Page 13: ...s of the companies and of the personnel about fixed units of refrigeration air condition and heating pumps which contain some fluorinated greenhouse gases according to the Regulation EC nr 842 2006 of...

Page 14: ...the CU DHP for UNI EN 12735 1 type The copper pipe for plumbing services is not suitable Refrigerating lines Path and bending of pipelines Define the pipeline path with the fewest possible bends Bend...

Page 15: ...d end and the fitting before they are joined This precaution prevents possible gas leakage Attention Use only synthetic oil in air conditioners which are charged with R 32 refrigerant Inclined profile...

Page 16: ...te core Power supply Power supply of the units For al models power supply is moved to external unit Power supply Magnetothermic switch Please use an exclusive source of electrical power for the air co...

Page 17: ...N S 1 S B N B L B L 1 L S W 2 N 1 L S W 2 N 1 L S W 2 N Signal N L Signal N L Not used Ferrite core Power supply Ferrite core Ferrite core Ferrite core Ferrite core Unit A Power supply 1 L S W 2 N 1 L...

Page 18: ...the same Note the coolant must not be released into the atmosphere as specified in the regulation CE no 2037 2000 of the European Parliament and of the Council 6 EXTERNAL UNIT INSTALLATION 7 CHARGE A...

Page 19: ...then check that the vacuum in the system has been maintained If not look for the cause of the leak For pipelines longer than 5 meters it is necessary to fill the circuit using a measuring cylinder or...

Page 20: ...efrigerant it contains requires a special procedure for dis posal Materials of value in the air conditioner can be recycled Contact local authorities or the waste disposal facility for more informatio...

Page 21: ...nser T3 disconnected short circuit F3 T5 short circuit disconnection temperature sensor F4 External drive EEPROM error F5 External fan speed out of control PO IPM module malfunction or IGBT module ove...

Page 22: ...unit exchanger output temperature E T2B E 22 Ambient Indoor Unit Temperature A T1 A If the temperature is below 9 C 9 will still be displayed If the temperature is above 70 V 70 will still be displaye...

Page 23: ...T4 Compressor Exhaust Temperature Sensor T5 9 FUNCTIONAL ANOMALIES 42 Active Frequency Limitations Bit7 Frequency limit caused by IGBT radiator The displayed value is the hex number For exam ple disp...

Page 24: ...8 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2133 119 246 0 36954 0 32 35 2024 40 104 5 17519 80 176 1 17393 120 248 0 35982 1 34 33 3269 41 106 4 96392 81 178 1 13604 121 250 0 35042 2 36 31 56...

Page 25: ...241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 31 62 78 172 7 321 118 244 2 233 1 30 190 5 39 102 30 36 79 174 7 086 119 246 2 174 0 32 180 9 40 104 29 15 80 176 6 859...

Page 26: ...oor unit 9 12kBtu Yellow Green Optional Yellow Green Blue Yellow Green Blue Brown Red Yellow Green Indoor Unit Power supply 4 Way Valve Heater Compressor Heater Basement Fan DC Blue Red Black Compress...

Page 27: ...temperature sensor Exchanger evaporator Unit A BLUE RED BLACK VALVE EXPANSION ELECTRONICS Valve 4 WAY Heater Compressor Power supply COMPRESSOR Unit B Heater Basement YELLOW GREEN EVA T2B EVA T2B 88 S...

Page 28: ...A core for each indoor unit power cord 4 Way Valve Heater basement Yellow Green WHITE WHITE 4 way Heat 1 Heat 2 Red Black Yellow Green Brown Blue Black Brown fan DC COMPRESSOR BLUE RED BLACK BLUE Rea...

Page 29: ...ure sensor T5 Compressor discharge temperature sensor INDOOR UNIT OUTDOOR UNIT T2 Evaporator temp sensor Liquid side 2 way valve T3 Condensator Temperature sensor T4 Outdoor ambient Condensator Exchan...

Page 30: ...uid Valve A Liquid Valve B T3 Condensator temperature sensor Gas Valve A Gas Valve B 4 way valve T5 Discharge temperature sensor COOLING HEATING Exchanger heat condensator T4 Ambient Temperature senso...

Page 31: ...A Gas Valve B Gas Valve C Expansion valve electronics Heat Exchange capacitor COOLING HEATING T5 Discharge temperature sensor 4 way valve Accumulator Compressor R32 TRIAL INDOOR UNIT OUTDOOR UNIT Hea...

Page 32: ...E Fontanafredda Pn Italy XEVO 0917 M3E 58 XEVO 0917 W43 53 6 1 149 2 6 4 0 875 2 5 0 2 R32 675 675 675 None 2 3 Fontanafredda Pn Italy XEVO 1217 M3E 60 XEVO 1217 W43 54 6 1 195 3 4 4 1 1093 3 2 0 2 R3...

Page 33: ...y XEVO 1817 D3E 61 XEVO 0917 W43 54 7 2 253 5 2 4 0 1680 4 8 1 0 R32 675 675 675 None XEVO 1217 W43 3 9 A Fontanafredda Pn Italy XEVO 2717 T3E 66 54 7 2 399 8 2 4 1 2390 7 0 0 1 R32 675 675 675 None X...

Page 34: ......

Page 35: ...reet Zip Town Country Slip A for user To be kept Please print in block letters GUARANTEE CERTIFICATE Slip A GUARANTEE CERTIFICATE Slip B GUARANTEE CERTIFICATE Slip C Model Serial Number Date installat...

Page 36: ...send part C in a closed envelope to Emmeti Spa post box nr 74 Fontanafredda PN within ten days from the date of installation first startup Should the certificate not be sent within 10 days of the ins...

Page 37: ......

Page 38: ...38 Note...

Page 39: ...39 Note...

Page 40: ...Vigonovo PN Italy Tel 0434 567911 Fax 0434 567901 Internet http www emmeti com E mail info emmeti com Rev 0 07 2017 AM Respect the environment For a correct disposal the different materials must be di...

Reviews: