12. ELECTRICAL DIAGRAMS AND CONNECTIONS
Parameter 25
Wired control
CONTACT WINDOW / PRESENCE
3
(factory setting)
White 2
White 3
The unit turns off
White 2
White 3
Unit is in stand-by
(can be turned on only trough IR control/wired control)
4
White 2
White 3
The unit turns off
White 2
White 3
Unit turns on in the previous
operating mode
确定
2. Factory setting / Factory settings
The configuration n. 3 in the table.
It is possible to change the default settings using the X-REVO WC1 wire
command (accessory not supplied with the unit, code 07917515).
Error indicator
Parameter code
Function code
NB: When using this input, the red wire must not be connected
Procedure:
Press and hold the “MODE” and “ADD.FUNC.” Buttons for 3 seconds
buzzer will emit a sound and the symbol and the code of the para-
meter will flash simultaneously on the display.
Press:
the parameter number increases or decreases
of 1 unit (from 0 to 25). Press until
parameter 17
is displayed and ENTER
to confirm.
The symbol stops flashing, the parameter code flashes again.
Press
and enter
parameter 25
, ENTER to confirm.
The symbol and the number 25 no longer flash, the function code
starts to flash.
Press:
the function code increases or decreases by 1.
Select the desired configuration (
3 or 4
- see table), press ENTER to
confirm.
Following confirmation
, the symbol no longer flashes and the
number 25 starts to flash again.
Press the “ON / OFF” key or the “CANCEL” key to exit.