Maintenance can be carried out by the user. 

Service must be performed only by an authorized installer and in accordance with local rules and regulations. 

Questions regarding installation, use, maintenance and service of the unit should be answered by your installer or place of purchase!

8 MAINTENANCE AND SERVICE

WARNING

Make sure that specific warnings and cautions in Chapter 2 “Precautions” are carefully read, understood and applied!

8.2 Description of Components

Fans 

The fans have external rotor motors of EC type which can be steplessly controlled individually between 10–100%. The motor bearings are life time 

lubricated and maintenance free. It is possible to easily disconnect and replace the fans if necessary. 

 

Filters 

The filters are of filter quality G4 placed on the injection and extraction side. 

The filters need to be cleaned regularly (and replaced when polluted) during maintenance. New sets of filters can be acquired from your installer or 

wholesaler. 

 

Heat exchanger 

The unit  is equipped with a highly efficient, counter-flow plate heat exchanger. Supply air temperature is therefore normally maintained without adding 

additional heat. The heat exchanger is removable for cleaning and maintenance during service. 

 

Condensation drainage 

Depending on the relative humidity in the extract air, condensation may occur on the cold surfaces of the heat exchanger, on one side in winter time, on the 

other side in summer time (fig.6.b). 

The condensate water is led out through drain plugs. 

 

Thermistor 

Temperature probes enable or disable the functions that depend on the combination of external and internal temperatures. 

8.1 Components list

Fig. 8.a

 Internal components

1
2
3
4
5

6

7
8
9

FILTER G4, EXTRACT AIR

FILTER G4, INTAKE AIR 

HEAT EXCHANGER 

CONDENSATION DRAINS

THERMISTOR

FAN, INTAKE AIR
FAN, EXHAUST AIR 

CONDENSATION TRAY

TERMINAL BOX

POWER SUPPLY

CONTROL CABLE

ILLUMINATED PUSH-BUTTON

10

11

12

3

1

2

4

4

5

6

7

8

8

9

10

11

12

Summary of Contents for RECUPERA SLIM B-110

Page 1: ...PERA SLIM B 110 MANUALE INSTALLAZIONE ED ISTRUZIONI PER L USO MANUALE INSTALLAZIONE ED ISTRUZIONI PER L USO IT IT INSTALLATION MANUAL AND USING INSTRUCTIONS INSTALLATION MANUAL AND USING INSTRUCTIONS...

Page 2: ...4 3 4 Spazio richiesto 4 3 5 Etichetta dati 5 4 Trasporto e STOCCAGGIO 5 5 Installazione 5 5 1 Rimozione dell imballo 5 5 2 Dove come installarlo 5 5 3 Installazione a soffitto 6 5 4 Collegamento ele...

Page 3: ...m UTILIZZO L apparecchio non deve essere utilizzato in applicazioni diverse da quelle indicate in questo manuale Questo apparecchio pu essere utilizzato da bambini di et non inferiore ad 8 anni e da p...

Page 4: ...interno Aria estratta dall interno Scarico condensa invernale Scarico condensa estivo 3 4 Spazio richiesto Assicurarsi che attorno all unit vi sia spazio sufficiente per lo svolgimento delle attivit d...

Page 5: ...unit sia completamente posta a livello prima di essere attivata E preferibile posizionare l unit in una stanza separata ad es magazzino lavanderia o similare Scegliendo la zona prestare attenzione ch...

Page 6: ...nch lo scarico condensa funzioni appropriatamente 5 d Collegare i raccordi di scarico della condensa ai 2 punti di drenaggio posti sul pannello di accesso eventualmente chiudere e sigillare il foro ch...

Page 7: ...i e ai regolamenti vigenti Fig 5 g SEL42M SEL4W accessorio su richiesta I II Fig 5 f Collegamento cavi I collegamenti interni del SLIM B 110 sono eseguiti durante l assemblaggio in fabbrica L unit vie...

Page 8: ...di qualsiasi operazione di installazione manutenzione ordinaria o straordinaria o collegamento elettrico ATTENZIONE L installazione e la manutenzione dell unit e del sistema di ventilazione completo...

Page 9: ...egolazioni del segnale 0 10V fornito ai motori L assorbimento indicato si riferisce ai 2 motori La tabella 6 b d un indicazione dell efficienza del pacco scambiatore e della condensa prodotta in diver...

Page 10: ...01 84 0 0 00 79 6 0 00 73 1 0 00 0 60 20 40 93 0 0 06 88 5 0 10 83 0 0 12 79 1 0 12 0 70 20 50 92 8 0 11 87 6 0 19 83 3 0 26 82 2 0 32 10 50 20 40 92 3 0 00 86 0 0 00 80 6 0 00 76 0 0 00 10 60 20 50...

Page 11: ...esterno Exhaust 59 64 68 62 57 57 54 47 71 44 Involucro Breakout 56 61 64 59 58 50 40 35 68 41 Velocit 80 Lw dB LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB A 63 125 250 500 1 K 2 K 4 K 8K Tot...

Page 12: ...alla scatola morsettiera La seconda velocit attivata se necessario tramite un deviatore esterno non fornito o tramite sensori esterni SEHR2M SEHRW SECO2W oppure SEIR2M SEIRW accessori su richiesta Sc...

Page 13: ...essere puliti regolarmente e sostituiti se intasati I filtri di ricambio possono essere acquistati presso il vostro installatore o rivenditore Pacco scambiatore L unit provvista di scambiatore a pias...

Page 14: ...stallazione e la manutenzione dell unit e del sistema di ventilazione completo deve essere eseguito da un installatore autorizzato e in conformit alle leggi e ai regolamenti vigenti 8 3 Manutenzione o...

Page 15: ...Fig 8 g Fig 8 m Pulire lo scambiatore ogni anno con un aspirapolvere La necessit di eseguire questa operazione pu variare da caso in caso a seconda delle condizioni ambientali interne ed esterne e del...

Page 16: ...e l uscita dell aria sono intasati 6 Verificare il sistema di tubazioni in caso sia danneggiato o si sia accumu lato dello sporco Ventilatori rumorosi vibrazioni 1 Verificare le ventole dei ventilato...

Page 17: ...17 2 x 2 x COLLEGAMENTO SCARICO CONDENSA CHIUSURA FORO SCARICO CONDENSA SE NON UTILIZZATO VISTA LATO ESTERNO VISTA LATO INTERNO 8 6 Installazione scarico condensa...

Page 18: ...18...

Page 19: ...to dell apparecchiatura EMMETI in base alle indicazioni presenti nel relativo manuale d installazione procede con la registrazione dei dati sul sito www emmeti com nella sezione GARANZIA e nel caso d...

Page 20: ......

Page 21: ...Space required 23 3 5 Rating Label 24 4 Transport and Storage 24 5 Installation 24 5 1 Unpacking 24 5 2 Where how to install 24 5 3 Ceiling installation 25 5 4 Precabled Electric Connections 26 5 4 1...

Page 22: ...s manual The device is not intended for use by persons including children with reduced physical sensory or mental capacities or those with a lack of experience and knowledge unless they have been give...

Page 23: ...Winter condensation drainage Summer condensation drainage A B D C A B D C F E E F 9 10 3 4 Space required Make sure that enough space is left around the unit to allow easy maintenance access to filter...

Page 24: ...ompletely leveled before it is put into operation Place the unit preferably in a separate room e g storage laundry room or similar When choosing the location it should be kept in mind that the unit re...

Page 25: ...le with the supplied plugs 2 plugs each hole Make sure of water and air tightness of all connections The condensation pipe connection must be done in a way that makes easy to remove the access panel f...

Page 26: ...reen brown yellow white Factory settings speed 1 set at 40 speed 2 set at 70 and speed 3 set at 100 WARNING Make sure that the mains supply to the unit is disconnected before performing any installati...

Page 27: ...ing any installation service maintenance or electrical work WARNING The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accorda...

Page 28: ...system to decide if to connect one or both condensation drainages High production of condensation is the direct consequence of a high efficiency level as well as of the humidity rate Table 6 c indicat...

Page 29: ...1 9 0 01 84 0 0 00 79 6 0 00 73 1 0 00 0 60 20 40 93 0 0 06 88 5 0 10 83 0 0 12 79 1 0 12 0 70 20 50 92 8 0 11 87 6 0 19 83 3 0 26 82 2 0 32 10 50 20 40 92 3 0 00 86 0 0 00 80 6 0 00 76 0 0 00 10 60 2...

Page 30: ...69 64 58 56 49 46 71 45 Supply 56 62 65 61 55 50 40 31 68 41 Extract 57 61 65 60 55 49 41 32 68 41 Exhaust 59 64 68 62 57 57 54 47 71 44 Breakout 56 61 64 59 58 50 40 35 68 41 Speed 80 Lw dB SOUND PO...

Page 31: ...means of remote sensors SEHR2M SEHRW SECO2W or SEIRW which are accessories on request Wiring diagram Fig 5 i Fig 5 j Dip switch configuration X100 Fig 5 l 7 4 Variable speed operation through externa...

Page 32: ...en polluted during maintenance New sets of filters can be acquired from your installer or wholesaler Heat exchanger The unit is equipped with a highly efficient counter flow plate heat exchanger Suppl...

Page 33: ...rk Fig 8 e Fig 8 d Fig 8 c Fig 8 b Fig 8 f Keep the unit surface free from dust Once every 3 months fixed period the unit warns the user to perform the filter maintenance red light The actual need to...

Page 34: ...q Fig 8 r Fig 8 h Fig 8 g Fig 8 m Clean the heat exchanger every year with a vacuum cleaner The actual need to perform this operation may vary depending on indoor and outdoor ambient conditions and o...

Page 35: ...place within the unit Excessive air noise 1 Check setting of fan speed in the terminal box or on the remote controls 2 Check grilles and diffusers Re setting or cleaning of grilles and diffusers requ...

Page 36: ...2 x 2 x WATER DRAINAGE CONNECTION HOW TO CLOSE THE WATER DRAINAGE HOLE IF NOT USED EXTERNAL SIDE VIEW INTERNAL SIDE VIEW 8 6 Installation water drainage 36...

Page 37: ...tion SEC 10 5 34 2 71 0 kWh m2 a Consumo elettrico annuo AEC Annual electricity consumption AEC AEC 3 8 4 2 9 6 kWh a Risparmio di riscaldamento annuo Annual heating saved AHS 19 9 44 1 86 2 kWh a Ins...

Page 38: ...d free of charge The transporting components cost and work costs necessary for replacement activities are not included 2 Any tampering with electrical system or structural part of units will result in...

Page 39: ...e kept Please print in block letters GUARANTEE CERTIFICATE Slip A GUARANTEE CERTIFICATE Slip B Slip C Model Serial Number Date installation first running User Street Zip Town Country Slip B for Distri...

Page 40: ...recchio indica che il prodot to alla fine della propria vita utile dovendo essere trattato separa tamente dai rifiuti domestici deve essere conferito in un centro rac colta differenziata per apparecch...

Reviews: