5. Specifications
35
Equipment use
Housing & Mounting
Panel Cut-Out
Protection
Weight
Environmental rating
Operating/Storage Temperature
Operating/Storage Humidity
Installation Over Volt. Category
Pollution Degree
Mode of Operation
Cranking Dropouts
Battery Voltage Measurement
Busbar Voltage Measurement
Busbar Frequency
Generator Voltage Measurement
Generator Frequency
Magnetic Pickup Input
CT secondary
Governor Output
AVR Output
Charge Generator Excitation
Charge Gen. Vol. Measurement
Sender Measurement
Cabin Temp. Measurement
Communication interface
Optional Expansion I/O Module
Optional Comm. Modules
Relay Outputs
Transistor Outputs
Approvals
: Electrical control equipment for generating sets.
: 276 mm x 189 mm x 45 mm. (including connectors)
.
: 223mm x 162mm.
:
: Approximately 0,82 Kg.
:
with non-condensing humidity
: -20°C to +70°C / -30°C to +80°C
: 95 % max. (non-condensing)
: II Appliances, portable equipment
: II, Normal office or workplace, non conductive pollution
: Continuous.
: 8 to 32 V
(Peak: 36 V
). Max. operating current is 860 mA.
: Battery voltage can be “0” VDC for max. 50 ms during
cranking (battery voltage should be at least nominal
voltage before cranking).
: 8 to 32 V
, Accuracy: 1 % FS, Resolution: 0,1 V
: 3
Resolution: 1 V.
: 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
: 3
Resolution: 1 V.
: 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
: 35 to 10000 Hz (1 to 35 volts peak continuously).
Accuracy: 0,25 % FS.
: 5A.
:+/-10V
, Accuracy: 0.1%, Resolution: 12bit, Isolation:1000V
:+/-10V
, Accuracy: 0.1%, Resolution: 12bit, Isolation:1000V
: 210mA @12V, 105mA @24V.
Nominal 2.5W.
: 8 to 32 V
, Accuracy: 1 % FS, Resolution: 0,1 V.
: 0 to 1300 ohm, Accuracy: 1 % FS, Resolution: 1 ohm.
: -50 to +100 ºC, Accuracy: 1 % FS, Resolution: 1 ºC.
: USB programming and communication port,
CanBus communication with 1939 ECU, CanOpen, Ethernet,
RS485.
: Expansion I/O module including 8 inputs and 8 outputs.
: GSM/GPRS and Web Server modules.
: Generator contactor output 8A at DC supply voltage
Configurable output-10 8A at DC supply voltage
: Fuel or Configurable output-1 15A at DC supply voltage
Crank or Configurable output-2 15A at DC supply voltage
Configurable output-3,4,5,6,7,8,9 1A at DC supply voltage
:
. Plastic
housing for panel mounting
IP65 at front panel.
Standard, indoor at an altitude of less then 2000 meters
.
to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
DC Battery Supply Voltage
Z
Z
Z
Z
Z
Z
Z
Z
,