Min
Default Unit
05.03.CONF. INPUT-X
(
)
Inputs->Conf. input-x
Max
1
2
2
0(dis)
1
0
4
2
0
0
250
0
Sec
0
2
0
28
25
0
001.Dis,user conf.or list
002.Polarity
003.Indication
004.Activation
005.Select from list
006.Active delay
0- Disable
1- User Configured
2- Select From List
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
If Select From List
0-Remote Start On Load
1-Remote Start Off Load
2-Reserved
3-Maintenance Alarm Reset
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Reserved
14-Neutral contactor feedback
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs(Exercise) Inhibited
19-Top priority
20-Generator Breaker Close
21-Generator Breaker Open
22-Remote Inhibit
23-Being Found Alive
24-Unconditional Synchron
25-Emergency Stop (for only input-1)
25-Remote Speed Up (for only input-
2,3,6,7,8,9,10,11,12)
25-Low Oil Pressure (for only input-4)
25-High Temperature (for only input-5)
26-Low Oil Level (for only input-4)
26-Emergency Stop No-Latching (for
only input-1)
26-Remote Speed Down (for only
input-2,3,6,7,8,9,10,11,12)
27-Remote Voltage Up (for only input-
2,3,6,7,8,9,10,11,12)
28-Remote Voltage Down (for only
input-2,3,6,7,8,9,10,11,12)
Input active delay
22
Note-1 :
x = 1(input ), 2(
), 3(
), 4(
), 5(
), 6
input
input
input
input
(input ), 7(input ), 8(input ),
9(input ), 10(input
), 11(input
), or 12(input
)
dis = disable
Note-2 :
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
-11
-12