EMKO TRANS-SYNCRO Manual Download Page 26

26

100-REMOTE START PRESENT
101-REMOTE STOP DELAY IN PROGRESS
102-SHORT CIRCUIT
103-SMOKE LIMITING
104-STARTING ALARM
105-STARTING ALARMS ARMED
106-STOP RELAY ENERGISED
107-SYSTEM IN AUTO MODE
108-SYSTEM IN MANUAL MODE
109-SYSTEM IN STOP MODE
110-SYSTEM IN TEST MODE
111-UNDER CURRENT PRE-ALARM
112-UNDER CURRENT
113-UNDER POWER PRE-ALARM
114-UNDER POWER ALARM
115-UNDERSPEED PRE-ALARM
116-UNDERSPEED SHUTDOWN
117-WAITING FOR GENERATOR
118-
119-LOAD SUPPLY FROM GENERATOR
120-
121-CONFIGURABLE ANALOG INPUT 1 LOW PRE-ALARM
122 CONFIGURABLE ANALOG INPUT 1 LOW ALARM
123-CONFIGURABLE ANALOG INPUT 2 LOW PRE-ALARM
124-CONFIGURABLE ANALOG INPUT 2 LOW ALARM
125-CONFIGURABLE ANALOG INPUT 2 HIGH PRE-ALARM
126-CONFIGURABLE ANALOG INPUT 2 HIGH ALARM
127-CHOKE ACTIVE
128-REMOTE CONTROL ACTIVE
129-REVERSE POWER ALARM
130-CABIN TEMPERATURE LOW PRE-ALARM
131-CABIN TEMPERATURE LOW SHUTDOWN
132-CABIN TEMPERATURE HIGH PRE-ALARM
133-CABIN TEMPERATURE HIGH SHUTDOWN
134-HEATER CONTROL
135-REMOTE OUTPUT
136-UNBALANCE LOAD
137-WATER PUMP
138-BUS NOT ALIVE
139-SYNCHRONIZATION FAIL
140-LOAD SHEDDING CONTROL-1
141-LOAD SHEDDING CONTROL-2
142-LOAD SHEDDING CONTROL-3
143-LOAD SHEDDING CONTROL-4
144-LOAD SHEDDING CONTROL-5
145-GOVERNOR MAXIMUM LIMIT ALARM
146-AVR MAXIMUM LIMIT ALARM
147-
148-
149-
150-GENERATOR UNDER VOLTAGE COIL
151-SPEED DOWN PULSE OUTPUT
152-SPEED UP PULSE OUTPUT
153-VOLTAGE DOWN PULSE OUTPUT
154-VOLTAGE UP PULSE OUTPUT
155-REVERSE POWER PREALARM
156-J1939 OIL PRESS. LOW PREALARM
157-J1939 OIL PRESS. LOW ALARM
158-J1939 COOLANT TEMP. HIGH PREAL
159-J1939 COOLANT TEMP. HIGH ALARM
160-J1939 OIL LEVEL LOW PREALARM
161-J1939 OIL LEVEL LOW ALARM
162-J1939 COOL. LEVEL LOW PREALARM
163-J1939 COOL. LEVEL LOW ALARM
164-J1939 COOL. LEVEL HIGH PREAL.
165-J1939 COOL. LEVEL HIGH ALARM
166-J1939 OVER SPEED PREALARM
167-J1939 OVER SPEED ALARM

BUSBAR READY

RESERVED

-

RESERVED
RESERVED
RESERVED

Summary of Contents for TRANS-SYNCRO

Page 1: ...lts frequency and phase matching Synchroscope display Logic Controller functionality for PLC Black or gray theme selection for 4 3 TFTLCD screen General Specifications 1 2 Warranty EMKO Elektronik war...

Page 2: ...t please read the instruction manual and warnings below carefully 2 Installation indekiler 2 1 Unit Configuration indekiler 2 2 Panel Mounting The unit is designed for panel mounting Fixing is by two...

Page 3: ...52 51 TRANSISTOR OUTPUT MAX 1 A BATTERY Conf Output 9 Conf Output 8 Conf Output 7 Conf Output 6 Conf Output 5 Conf Output 4 Conf Output 3 22 D W L Charge Alt 23 Cabin Temp Conf Input 13 24 Conf Input...

Page 4: ...section you wish to view change When the Prog button is pressed the parameters section is asked for accessing to parameters Operation Screen Press the Enter button to confirm password If the password...

Page 5: ...with Up and Down buttons Press the Enter button to view parameter value V1 V 230 V2 V 230 V3 V 230 GENERATOR I1 A 170 0 I2 A 170 0 I3 A 170 0 V12 V 400 V23 V 400 V31 V 400 A 0 0 Ie Hz 50 0 Phase seq...

Page 6: ...0 58 0 Hz 01 5 Over freq set Over Frequency Set 30 0 Min Default Max 003 Under current prealarm reset 006 Over current set 007 Over current prealarm 008 Over current prealarm reset 012 Earth fault cur...

Page 7: ...1 100 kVA kW Voltage Transformer Primary Voltage Transformer Secondary 0 1 Phase 2 Wire 1 3 Phase 4 Wire 2 2 Phase 3 Wire L1 L2 3 2 Phase 3 Wire L1 L3 Phase Sequence Generator kVA Rating Set Power Uni...

Page 8: ...GS System Password settings Max Operator Password Technician Password 0 0 9999 0 9999 0 001 Operator password 002 Technician password Min Default Unit 01 08 DEFAULT SETTINGS System Default settings Ma...

Page 9: ...ask byte3 010 Subnet mask byte4 011 Gateway address byte1 012 Gateway address byte2 013 Gateway address byte3 014 Gateway address byte4 015 DNS address byte1 016 DNS address byte2 017 DNS address byte...

Page 10: ...0 Hz 001 Nominal frequency 011 Under freq set Under Frequency Set 30 0 25 0 0 0 Under Frequency Actions Delay 2 0 013 freq actions delay Under Sec 01 actions 2 Under freq 0 dis 3 3 Under Frequency 0...

Page 11: ...utdown 0 1 2 3 Over Current Set Over Current Pre Alarm Over Current Pre Alarm Reset Over Current Actions Delay Time Short Circuit Current Set Earth Fault Current Set Earth Fault Current Actions Delay...

Page 12: ...ss Set Excitation Loss Actions Delay Time 9999 0 dis 0 0 3 99 100 0 dis 2 KVAr Sec Excitation Loss 0 1 2 3 Actions Disable Warning Electrical Trip Shutdown 014 Excitation loss set 01 Excitation loss 5...

Page 13: ...m Under Speed Prealarm Reset dis Over Speed Shutdown 500 dis 5000 500 dis RPM 500 500 5000 Over Speed Prealarm Reset 500 RPM RPM RPM RPM RPM 5000 500 dis 5000 5000 5000 Over Speed Prealarm 002 Under s...

Page 14: ...set point 1500 1500 1800 Speed Set Point Selection RPM ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL DISBL J1939 ECU Type Selection 0 Disable 1 Standard 2 Volvo EMS1 3 Volvo EMS2 4 Volv...

Page 15: ...le 1 Warning Non Latching 2 Warning 3 Electrical Trip 4 Shutdown 2 0 2 0 0 dis 4 005 Amber warning activation 004 Amber warning actions Sec J1939 Amber Warning Lamp Delay 2 0 250 006 Amber warning del...

Page 16: ...day Exercise Stop Time on Sunday 001 Disable enable select 002 Start time on monday 003 Stop time on monday 004 art tuesday St time on 005 tuesday Stop time on 006 art wednesday St time on 007 wednesd...

Page 17: ...User Configured VDO 120 C VDO 1 0 C 0 dis 0 dis Oil Press Unit ure 001 Oil pressure unit BAR BAR PSI KPA Coolant Temp Unit erature 006 Temperature unit C C F 0 dis 0 dis 300 C 013 Heater control ON 0...

Page 18: ...larm Low Reset 2 0 250 Sec 046 Conf AI1 low prealarm delay Conf AI1 Low Prealarm Delay 048 actions Conf AI1 low 0 dis 3 3 Conf AI1 Low Actions Disable Warning Electrical Trip Shutdown 0 1 2 3 2 0 250...

Page 19: ...Conf AI2 Low Set 056 2 actions Conf AI low 0 dis 3 0 dis Conf AI2 Low Actions Disable Warning Electrical Trip Shutdown 0 1 2 3 2 0 250 Sec 057 2 actions Conf AI low delay Conf AI2 Low Actions Delay 2...

Page 20: ...ressure 014 7 Oil pressure 016 8 Oil pressure 018 9 Oil pressure 020 0 Oil pressure 1 022 Temperature 1 024 Temperature 2 026 Temperature 3 028 Temperature 4 030 Temperature 5 032 Temperature 6 034 Te...

Page 21: ...070 Conf AI2 value 5 072 Conf AI2 value 6 074 Conf AI2 value 7 076 Conf AI2 value 8 078 Conf AI2 value 9 080 Conf AI2 value 0 1 Conf Analog Input 1 Sender Point 6 Conf Analog Input 1 Sender Point 7 C...

Page 22: ...rt Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Reserved 14 Neutral contactor feedback 15 Auto Restore Inhibit 16 Auto Start Inhibit 17 Panel Lock 18 Sched...

Page 23: ...Reset Button 6 Simulate Auto Button 7 Simulate Test Button 8 Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Reserved...

Page 24: ...Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Reserved 14 Neutral contactor feedback 15 Auto Restore Inhibit 16 Auto...

Page 25: ...XPANSION INPUT 7 ALARM 43 EXPANSION INPUT 8 ALARM 44 EARTH FAULT 45 EMERGENCY STOP 46 FAIL TO START ALARM 47 FAIL TO STOP ALARM 48 CONF AI1 CONTROL 49 FUEL RELAY ENERGISED 50 GAS ENGINE IGNITION OUTPU...

Page 26: ...ARM 131 CABIN TEMPERATURE LOW SHUTDOWN 132 CABIN TEMPERATURE HIGH PRE ALARM 133 CABIN TEMPERATURE HIGH SHUTDOWN 134 HEATER CONTROL 135 REMOTE OUTPUT 136 UNBALANCE LOAD 137 WATER PUMP 138 BUS NOT ALIVE...

Page 27: ...put 1 options 0 Normally Open Close To Activate 1 Normally Close Open To Activate The same as Configurable Output 1 options 0 Normally Open Close To Activate 1 Normally Close Open To Activate The same...

Page 28: ...ose Open To Activate Min Min Min Min Default Default Default Default Unit Unit Unit Unit Max Max Max Max 0 0 0 0 1 1 1 1 0 0 0 0 167 167 167 167 0 0 0 0 12 12 12 12 06 14 CONF EXP OUTPUT 4 Outputs Con...

Page 29: ...0 0 0 0 00 0 00 0 00 10 0 0 0 10 0 00 002 Manual frequency set 003 Minimum output value 004 Maximum output value 005 Initial value 006 Output direction 007 Proportional 008 Integral 009 Derivative 01...

Page 30: ...control Voltage Control Selection 0 Disable 1 Analogue 2 Digital Up Down 1 0 2 016 Up Down pulse period 017 Up Down pulse time 018 Up Down voltage deadband 0 1 0 01 0 10 10 0 5 00 9 9 9 1 0 0 50 1 00...

Page 31: ...set 002 Maximum voltage difference 003 Positive frequency difference 004 Negative frequency difference 005 Maximum positive phase angle 006 Maximum negative phase angle 007 GCB relay closing time 008...

Page 32: ...re outputs 001 Configurable output 1 00 Configurable output 2 2 00 Configurable output 3 3 00 Configurable output 4 4 00 Configurable output 5 5 00 Configurable output 6 6 00 Configurable output 7 7 0...

Page 33: ...100 9999 9999 9999 9999 9999 9999 9999 9999 10 04 CONF LOGIC FUNCTIONS Logic controller Conf logic functions 001 Start request in auto 00 Stop request in auto 2 00 Load dependent start stop 3 00 Chan...

Page 34: ...offset Oil Pressure Offset Coolant Temperature Offset Configurable Analog Input 1 Offset Configurable Analog Input 2 Offset 2 0 20 200 20 BAR C C 4 2 10 User Adjustment Min Default Unit 11 04 BATTERY...

Page 35: ...ltage should be at least nominal voltage before cranking 8 to 32 V Accuracy 1 FS Resolution 0 1 V 3 Resolution 1 V 5 to 99 9Hz min 20 VAC Ph N Accuracy 0 25 FS Resolution 0 1 Hz 3 Resolution 1 V 5 to...

Page 36: ...Phone 90 224 261 1900 Fax 90 224 261 1912 Repair and maintenance service information Emko Elektronik Sanayi ve Ticaret A Demirta Organize Sanayi B lgesi Karanfil Sk No 6 16369 BURSA TURKEY Phone 90 22...

Reviews: