Min
Default
Unit
5
CANBUS ERROR SET (
Engine->CanBus error set
)
*
Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
0
0
2
0
0(dis)
4
CAN fault activation
CAN fault actions
Sec
Can Fault Delay
10
2
250
CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0
2
0
0(dis)
4
Amber warn.activation
Amber warn.actions
Sec
J1939 Amber Warning Lamp Delay
2
0
250
Amber warn.delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning (Alarm Only, No Shutdown)
3- Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
4- Shutdown (Alarm And Shutdown)
2
0
2
0
0(dis)
4
Red stop activation
Red stop actions
Sec
J1939 Red Stop Lamp Delay
2
0
250
Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
12
Note:
= Parameters in this table are only available at Trans-MiniAMF.CAN
dis = disable
5
*