background image

EMK

 

Operating and maintenance guidelines 

7

Motive

In many cases, low-voltage motors are stored for lon-
ger periods of time before assembly and commissio-
ning, sometimes for several years.

In order to prevent premature damage, our customers 
must be informed about this topic and, if necessary, 
also about the following measures:

» 

Storage

When storing the motors, the supplied operating inst-
ructions must always be followed:

»

 

Storage room

The motors must be stored in a dry, ventilated, dust-
free, and vibration-free room. Further, the storage 
temperature should not be below -15°C (according to 
EN60034-1) and the relative humidity should be below 
60%. 

If this is guaranteed, no special protective packaging 
is required. 

In all other cases, special packaging with plastic bags 
and humidity indicators and a regular inspection will 
be necessary.

»

 

Anti-rust

All exposed, outer components (e.g. shaft end, flanges, 
feet) have a protective coating for 6 months storage 
under dry conditions.

In order to secure a longer storage period, all accessib-
le bare parts must be provided with a long-term corro-
sion protection coating (e.g. Tectyl 506), provided this 
has not already been applied by the factory.

Measures

 

» 

For prolonged storage and before commissioning of low-voltage motors

EA regular inspection of the corrosion coating and, if 
necessary, a renewal is necessary.

»

 

Rotor holding device

The rotor holding device serves as a protection of the 
bearings during transport and / or in the case of non-
vibration-free mounting (danger of brinelling). If a 
rotor retaining device has been mounted on the drive 
end of the shaft (DE shaft end) by the factory (e.g. for 
designs with roller bearings), this must not be remo-
ved.

If the disassembly of the rotor retaining device is un-
avoidable (e.g. during inspections, tests, etc.), it must 
be reattached before dispatch or during further sto-
rage. This also applies in particular to motors in which 
a coupling half must be mounted on the DE shaft end. 
The coupling half must be removed again after the ad-
justment, the rotor holding device must be reassem-
bled and the coupling half must be supplied or stored 
separately.

»

 

Condensation water

If condensation drain holes are present on the motor, 
any condensation water must be drained off by remo-
ving the plugs.

Commissioning

The operating instructions of the EMK motor as well 
as the safety information „Warnings“ which are sup-
plied with each motor or can be downloaded from the 
Internet must be observed entirely.

»

 

Bearings / Lubrication

The rolling bearings must be relubricated if the time 
between delivery and commissioning is more than 2 
years.

Summary of Contents for KHF 100

Page 1: ...Operating and maintenance guidelines EMK motors...

Page 2: ...d maintenance guidelines EMK motors Operating and maintenance guidelines EMK motors 3 Spare Parts 5 Lubrication periods 6 Measures 7 Operating and maintenance guidelines spring operated brake 9 Table...

Page 3: ...ations are to be adhered to Every EMZ motor is dispatched only after the specifi cations on the order have been checked and a trial run had been carried out Until installed the motor is to be stored d...

Page 4: ...ractical all possible overloads Maintenance For motors up to and including size 132 it is sufficient to keep the cooling passages cleaned and to check the bearings These motors have bearings with serv...

Page 5: ...ot start Fuse burnt out Replace the fuse Motor protection switch has tripped Check protection switch for correct setting and adjust Motor contactor inoperative Control fault Check contactor operation...

Page 6: ...4500 4800 40 NU317 430 2200 3700 4900 40 NU319 330 1800 3300 4600 50 NU320 240 1600 3300 4600 60 NU322 120 1300 2800 4100 70 NU324 110 1100 2300 3600 80 Motortype KAE BG AS BS BG AS BS 56 6201 2RZ 620...

Page 7: ...torage and before commissioning of low voltage motors EA regular inspection of the corrosion coating and if necessary a renewal is necessary Rotor holding device The rotor holding device serves as a p...

Page 8: ...windings to ground must be measured before commissioning of the mo tors If the minimum values specified by the manufac turer are not observed the motor windings must be dried The following conditions...

Page 9: ...locking The brake is released electromagneti cally During the braking process the brake disc is pressed against the counter friction surface by the compression springs In the braked state there is an...

Page 10: ...age the wiring The friction surface of the brake must be free of oil and grease Maintenance The motor should be checked and cleaned regularly The intake port of the fan cover should be cleaned of dirt...

Page 11: ...2 0 3 0 8 40 1 0 0 25 0 60 132 0 4 0 9 80 1 2 0 25 0 60 IEC frame size Brake type d1 d2 d3 d4 d5 d6 d L1 L2 L3 L h1 h2 h b 80 DLTZ3 08 117 105 92 65 3xM5 10 20 54 3 31 3 20 124 71 21 6 6 0 3 90 DLTZ3...