P14 – Instrument powering-on delay:
It delays the process start to avoid several devices turn on at the same time. The ideal is to
configure different times when there are a lot of products installed on the same power network.
no
no
240
Minutes
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
P15 - Extra time for the first cycle:
Sets an extra run time for the first refrigeration cycle.
no
no
240
Minutes
Standard value
Minimum
Maximum
Unid
Operating mode
Cooling
P17 - Compressor ON time (defective sensor P16):
This will be the minimum time the compressor will be on, in case of defective
sensor and P16 = [2].
1
15
999
Minutes
Standard value
Minimum
Maximum
Unid
Operating mode
Cooling
P18 – Compressor OFF time (defective sensor P16):
This will be the minimum time the compressor will be off, in case of defective
sensor and P16 = [2].
1
15
999
Minutes
Standard value
Minimum
Maximum
Unid
Operating mode
Cooling
P20 – Function blocking time:
This function activates the permission to block or not the functions through the Easy Key.
Check item 3.3 on how to activate / deactivate the block.
▶ Option [No]: It does not allow the [Loc] function in the Emicol Easy Menu to block the control functions.
▶ Option >15: Allows the [Loc] function in the "Easy Menu" to block the control functions. Pressing the “down” key with the time> 15
programmed in this function.
no
no
60
Seconds
Standard value
Minimum
Maximum
Unid
Operating mode
Heating | Cooling
P16 – Compressor situation with damaged sensor:
If the temperature sensor is short-circuited or disconnected, the load output
assumes the configured state:
▶ Option [0]: Turn off the compressor
▶ Option [1]: Keeps the compressor on
▶ Option [2]: Cycles according to the times of P17 and P18
Note:
In heating mode if an error occurs, the output is turned off.
0
0
2
Standard value
Minimum
Maximum
Operating mode
Cooling
P19 – Sensor thermal inertia:
This parameter simulates an increase in thermal mass in the sensor, delaying the response time (thermal
inertia). As higher the value set in this parameter, greater the response delay of the sensor.
no
no
9
Standard value
Minimum
Maximum
Operating mode
Heating | Cooling