P14 – Instrument powering-on delay: 

It delays the process start to avoid several devices turn on at the same time. The ideal is to 

configure different times when there are a lot of products installed on the same power network.

no

no

240

Minutes

Standard value

Minimum

Maximum

Unid

Operating mode

Heating | Cooling

P15 - Extra time for the first cycle: 

Sets an extra run time for the first refrigeration cycle.

no

no

240

Minutes

Standard value

Minimum

Maximum

Unid

Operating mode

Cooling

P17 - Compressor ON time (defective sensor P16): 

This will be the minimum time the compressor will be on, in case of defective 

sensor and P16 = [2].

1

15

999

Minutes

Standard value

Minimum

Maximum

Unid

Operating mode

Cooling

P18 – Compressor OFF time (defective sensor P16): 

This will be the minimum time the compressor will be off, in case of defective 

sensor and P16 = [2].

1

15

999

Minutes

Standard value

Minimum

Maximum

Unid

Operating mode

Cooling

P20 – Function blocking time: 

This function activates the permission to block or not the functions through the Easy Key.

Check item 3.3 on how to activate / deactivate the block.

▶ Option [No]: It does not allow the [Loc] function in the Emicol Easy Menu to block the control functions.

▶ Option >15: Allows the [Loc] function in the "Easy Menu" to block the control functions. Pressing the “down” key with the time> 15 

programmed in this function.

no

no

60

Seconds

Standard value

Minimum

Maximum

Unid

Operating mode

Heating | Cooling

P16 – Compressor situation with damaged sensor: 

If the temperature sensor is short-circuited or disconnected, the load output 

assumes the configured state:

▶ Option [0]: Turn off the compressor

▶ Option [1]: Keeps the compressor on

▶ Option [2]: Cycles according to the times of P17 and P18

Note: 

In heating mode if an error occurs, the output is turned off.

0

0

2

Standard value

Minimum

Maximum

Operating mode

Cooling

P19 – Sensor thermal inertia: 

This parameter simulates an increase in thermal mass in the sensor, delaying the response time (thermal 

inertia). As higher the value set in this parameter, greater the response delay of the sensor.

no

no

9

Standard value

Minimum

Maximum

Operating mode

Heating | Cooling

Summary of Contents for STORM ST101 2HP

Page 1: ...T101 2HP HEATING OR COOLING WITH NATURAL DEFROST THROUGH COMPRESSOR SHUTDOWN FRONT PANEL IP65 PROGRAMABLE BY NFC APP EVEN UNPLUGGED SHORTCUT KEY EASY TO PROGRAM POWERFUL 2HP RELAY AUTOMATIC BIVOLT 85...

Page 2: ...2 3 Con guration With Frontal Keys 2 3 1 Adjustment Of The Setpoint Temperature 2 3 2 Advanced Operations Access The Full Menu 3 Easy Menu Features 3 1 Manual Defrost Cycle Forced Defrost 3 2 Functio...

Page 3: ...FC communication and active internet plan for sharing settings if applicable 1 1 APPLICATIONS The ST101 2HP Temperature Controller it s compatible with applications that requires ON 0FF control and te...

Page 4: ...in a space as indicated in the table of item 1 3 Avoid installing in places exposed to high humidity and dirt that can cause condensation and the introduction of substances or particles Make sure that...

Page 5: ...wer Parameters from P02 to P24 Edit the parameters Compare Compare two settings and list their differences Send NFC Send the parameters from P02 to P24 to the controller even if disconnected from the...

Page 6: ...ustments For example Shows that parameters P02 P06 and P07 are different Get the phone closer to the controller to send the con guration Even when disconnected from the power Con guration successfully...

Page 7: ...s PPress and then until dFr is shown Press and On and will be shown The defrost could be activated or disactivated by pressing until On be shown and is off With the functions blocked it will only be p...

Page 8: ...mperature Setpoint It is the value set for temperature control where the load supply output is turned off 50 4 200 C Standard value Minimum Maximum Unid Operating mode Heating Cooling P03 Indication s...

Page 9: ...will perform the defrost when the controller is energized Note The defrost time will be in accordance with parameter P11 0 refri 0 refri 1 Degg Standard value Minimum Maximum Operating mode Cooling P...

Page 10: ...ocking time This function activates the permission to block or not the functions through the Easy Key Check item 3 3 on how to activate deactivate the block Option No It does not allow the Loc functio...

Page 11: ...the NFC communication from the controller No NFC Communication between cell phone and Controller enabled Yes NFC communication blocked The cell phone will not communicate with the controller Note This...

Page 12: ...oduct and is exempt from any extra expenses such as supplies services or transportation 8 WARRANTY Still have any questions Contact us e mail marketing emicol com br 9 CUSTOMER SERVICE 12 I S O 9001 2...

Reviews: