background image

S1CG/S1HG

Single-Zone,  

S2CG/S2HG

Dual-Zone

•  Installation, Operation and Maintenance Manual  •

P/N 240007754, Rev. C [3/19/2010]

 

31

 

Made in the USA

Single-zone and Dual-zone Condenser Sequence of Operation

EMI Series condensers are designed to operate 
with EMI Series air handlers. Both the condens-
er (outdoor unit) and air handler (indoor unit) 
have a high volt service connection. Each is to 
be independently connected to the electrical 
service panel. (See the unit name plate for the 
correct breaker type and size). Th

  e outdoor and 

indoor units are also connected to each other 
through a low volt interconnect wiring. A 24v 
transformer located in the indoor unit provides 
the low volt power source. 

Straight cool condensers are designed to oper-
ate as a single stage cooling unit. Heat pump 
condensers are designed to operate as a single 
stage cooling two stage heating unit. For proper 
operation the unit must be matched with an ap-
propriate EMI indoor unit with unit mounted 
controls and/or wall mounted thermostat. For 
two-stage heating operation the indoor unit 
must be equipped with an electric strip heater.

 NOTICE

For remote wall mounted thermostat 
operation be sure to select EMI p/n 
240008209 or a suitable 24v, two stage 
heating, heat pump thermostat.

Condenser operation

The transformer located in the indoor unit 
provides 24v, low-volt control power to the 
condenser (outdoor unit). Th

  is can be measured 

across low-volt terminals “R” and “C”.

Heat pump condensers utilize a reversing valve 
to provide reverse cycle operation. Th

 erefore 

the outdoor unit will act as either a condenser 
or an air handler there-by providing comfort 
cooling or heating to the indoor space. The 
reversing valve is energized in cooling. Should 
the valve fail to actuate, the system will default 
to the heating mode of operation.

Cooling operation, single- and dual-zone

Cooling operation requires that the control 
(either unit mount or remote wall mount ther-
mostat) make a connection between low-volt 
terminals “R” and “Y” along with “R” and “O” 
(heat pumps only). When the indoor control 
is placed in cooling mode, with the set point 
temperature below the room temperature, the 

reversing valve will energize (R & O heat pumps 
only) along with the compressor and outdoor 
fan (R & Y). When the indoor control is satis-
fi ed and the room temperature falls below the 
set temperature, the compressor and fan will 
de-energize. Th

  e anti-short cycle timer (ASCT) 

will prevent the compressor from re-starting for 
three minutes.

Heating operation

Heating operation requires that the control 
(either unit mount or remote wall mount, heat 
pump thermostat) make a connection between 
low-Volt terminals “R” and “Y” only. When the 
indoor control is placed in heating mode, with 
the set point temperature above room tem-
perature, the compressor and outdoor fan (R 
& Y) will energize. When the indoor control is 
satisfi ed and the room temperature rises above 
the set temperature, the compressor and fan will 
de-energize. Th

  e anti-short cycle timer (ASCT) 

will prevent the compressor from re-starting for 
three minutes.

Defrost controls with short cycle 
protection (heat pumps only)

Th

  e unit is equipped with a logic control circuit 

designed to keep system operating at peek ef-
fi ciency. Th

  e 24v circuit provides control to 

the indoor and outdoor systems including a 
three minute, anti-short cycle timer (ASCT) 
compressor protection. 
Th

  e defrost control circuit is designed to keep 

the condenser coil free from frost and ice during 
heating mode. Th

  is is accomplished through the 

precise switching sequence of the outdoor fan, 
reversing valve and indoor auxiliary heater.

Defrost initiation

Th

  e defrost-sensor is located on either the end 

plate or the return bend of the condenser coil. 
A defrost cycle will initiate after the sensor 
closes (approx. 30°F) and remains closed for 
the length of time selected on the control board 
(either 30, 60 or 90 minutes)*.

*Factory sett ings 9–24k Btu = 90 minutes

 

At the start of the defrost cycle, the reversing 
valve will change from heating to cooling mode. 
Th

  e condenser fan will also switch off  there-by 

allowing pressure and temperature

Summary of Contents for S1CG

Page 1: ...only Units 9 000 12 000 18 000 24 000 28 000 33 600 Btuh 2 6 3 5 5 3 7 0 8 3 10 5 kW Capacities Dual Zone Applications S2CG or S2HG Units 9 000 12 000 Btuh 2 6 3 5 kW Installation Operationand Mainte...

Page 2: ...d Dual zone Condenser Sequence of Operation 31 Single zone and Dual zone Condenser Sequence of Operation Testing Defrost Operation Using Test Pins 32 Speci cation and Dimensions 33 Test Unit Performan...

Page 3: ...personal injury or death Read all instructions before using this unit Install or locate this unit only in ac cordance with these instructions Use this unit only for its intended use as described in t...

Page 4: ...andler Multiple units can be lined up in close proximity to an exterior wall Service valves are recessed to reduce tampering All9 000 12 000Btuhunitsareequipped withaDuratecPerformancePackagethat incl...

Page 5: ...installed thermostatically con trolled crankcase heater for straight cool units S1CG or S2CG Recom mended for operation below 60 F Installer supplied items Power wiring Low Volt wiring 18 awg minimum...

Page 6: ...pipingshouldbeadirect line to the indoor unit Site preparation Place the unit on a flat concrete surface 1 or pad if on the ground Roof mounting should use a built up platform to avoid intake of hot a...

Page 7: ...2010 7 Made in the USA Mounting the Unit continued Remove front panel screws Figure 1 1 2 Remove front panel Figure 2 Bottom lag hole locations Figure 3 A A A A B B C C D D E E S1CG S1CG Shown Shown L...

Page 8: ...delay fuses Select the wire size according to the ampacity rating To access electrical connections and wir 3 ing diagram a Figure 6 Page 8 Remove the screws on the side panel that covers the electric...

Page 9: ...ng Run wires to the high volt pigtail in the 6 control box and attach L1 and L2 con nections Also run green wire to ground wire Check wiring diagram for the required 7 number of low voltage wires to b...

Page 10: ...tion and Maintenance Manual Comfort where it counts 10 P N 240007754 Rev C 3 19 2010 Electrical Wiring continued Replacing side panel Figure 12 Fasten loose screws Figure 13 Completed wiring S1CG Figu...

Page 11: ...t Max Trap Height Liquid Line Suction Line H P O D O D 09 50 15 m 20 6 m 15 5 m 1 4 1 2 12 1 4 1 2 18 100 30 m 35 11 m 20 6 m 3 8 5 8 24 3 8 3 4 30 3 8 3 4 36 3 8 3 4 P trap installation A P trap is r...

Page 12: ...he fittings Cap ends of lines until ready for con nections Becertainthatplasticendcapsremain in place when inserting through wall openings Insulate the suction line Isolatetubingfromtransmittingvibra...

Page 13: ...beginning on 5 page 17 to fine tune the refrigerant charge to meet your conditions CAUTION All systems require field charge adjust ments Refer to the Refrigerant Charge Tables for proper weight charge...

Page 14: ...Unit service valves are solid brass for sweat con nections CAUTION Pressure test all field installed piping with nitrogen Using a suitable vacuum pump evacuate the tubing and indoor unit to 500 micro...

Page 15: ...t 59 g m 63 0 S1HG4 WLH24 UNH24 64 oz ft 59 g m 74 0 S1CG3 CAC36 64 oz ft 59 g m 97 5 S1HG9 CAH09 25 oz ft 23 g m 51 3 S1CG6 CAC36 64 oz ft 59 g m 80 0 S1HG2 CAH12 25 oz ft 23 g m 45 75 S1CG9 WLH09 UN...

Page 16: ...LHG12 25 oz ft 23 g m 39 39 S2CG92 WLHG09 WLHG12 25 oz ft 23 g m 44 39 S2HG92 WLHG09 WLHG12 25 oz ft 23 g m 44 39 S2CG99 UNHG09 25 oz ft 23 g m 44 44 S2HG99 UNHG09 25 oz ft 23 g m 44 44 S2CG22 UNHG12...

Page 17: ...ative Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psig...

Page 18: ...ative Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psig...

Page 19: ...e Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psig High...

Page 20: ...ative Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psig...

Page 21: ...e Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psig High...

Page 22: ...e Humidity 50 85 F 80 F 75 F Single zone Operation Charts continued NOTICE Performance data listed in this manual is subject to change without notice For the most current unit system performance data...

Page 23: ...Humidity 50 75 F 70 F 65 F 0 10 20 30 50 70 90 110 130 230 260 290 320 350 380 10 20 30 40 50 60 OutdoorTemp F Liquid Subcooling F Low Pressure psig High Pressure psig Heating Cycle Model S1HG9000 wi...

Page 24: ...50 75 F 70 F 65 F Single zone Operation Charts continued NOTICE Performance data listed in this manual is subject to change without notice For the most current unit system performance data please ref...

Page 25: ...ity 50 75 F 70 F 65 F 0 10 20 30 50 70 90 110 130 230 260 290 320 350 380 10 20 30 40 50 60 OutdoorTemp F Liquid Subcooling F Low Pressure psig High Pressure psig Model S1HG2000 with EMI s WLHG12 UNHG...

Page 26: ...umidity 50 75 F 70 F 65 F Single zone Operation Charts continued NOTICE Performance data listed in this manual is subject to change without notice For the most current unit system performance data ple...

Page 27: ...ity 50 75 F 70 F 65 F 0 10 20 30 50 70 90 110 130 230 260 290 320 350 380 10 20 30 40 50 60 OutdoorTemp F Liquid Subcooling F Low Pressure psig High Pressure psig Model S1HG4000 with EMI s WLHG24 UNHG...

Page 28: ...elative Humidity 50 85 F 80 F 75 F 5 15 25 35 90 110 130 150 170 250 310 370 430 490 550 65 75 85 95 105 115 OutdoorTemp F Note Minimum compressor superheat 5 F Compressor Superheat F Low Pressure psi...

Page 29: ...umidity 50 75 F 70 F 65 F 0 10 20 30 50 70 90 110 130 230 260 290 320 350 380 10 20 30 40 50 60 OutdoorTemp F Liquid Subcooling F Low Pressure psig High Pressure psig Heating Cycle Model S2CG S2HG 12...

Page 30: ...e indoorsectionorroomthermostat Therefore the system operation will be described in the manual pertaining to the indoor section EMI units are designed and constructed for reliability and long life wit...

Page 31: ...her mostat make a connection between low volt terminals R and Y along with R and O heat pumps only When the indoor control is placed in cooling mode with the set point temperature below the room tempe...

Page 32: ...condenser will remain on during the entire defrost test operation The condenser will operate in heating for ap proximately 20 seconds At that point the unit will enter defrost mode for approximately...

Page 33: ...81 44 1118 68 210 S1CG6 36 7 178 23 15 16 608 3 76 12 7 16 316 38 965 15 381 48 1219 68 210 S2CG S2HG99 9 9 7 178 23 15 16 608 3 76 12 7 16 316 38 965 15 381 44 1219 68 159 S2CG S2HG22 12 12 7 178 23...

Page 34: ...EER SHR EER Ref WLC WLH S1CG9 WLHG09 9 000 13 0 0 74 12 2 R410A S1CG2 WLHG12 12 000 13 0 0 68 11 9 R410A S1CG8 WLHG24 18 000 13 0 0 77 12 0 R410A S1CG4 WLHG24 23 800 13 0 0 67 11 4 R410A S1CG3 WLCG30...

Page 35: ...Ref S1HG9 WLHG09 9 000 9 000 13 0 7 7 0 72 12 8 3 3 R410A S1HG2 WLHG12 12 000 11 400 13 0 7 7 0 69 11 8 3 3 R410A S1HG8 WLHG24 18 000 17 600 13 0 7 7 0 76 11 9 3 5 R410A S1HG4 WLHG24 23 800 20 600 13...

Page 36: ...0 208 230 60 1 0 8 0 125 5 2 27 5 2 27 9 8 197 11 15 S2CG performance data Matched with EMI Series Indoor Units S2CG cooling systems with two wall units Table 14 Wall units Condenser Btuh SEER SHR EER...

Page 37: ...1 15 S2HG performance data Matched with EMI Series Indoor Units Heat pump systems with wall units Table 17 Wall units Condenser Cooling Btuh Heating Btuh SEER HSPF SHR EER COP Ref WLHG09 WLHG09 S2HG99...

Page 38: ...OD Fan Motor Amps ID Fan Motor Volts ID Fan Motor Amps Total Volts Total Amps Temperatures Degrees F Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Air han...

Page 39: ...S1CG S1HG Single Zone S2CG S2HG Dual Zone Installation Operation and Maintenance Manual P N 240007754 Rev C 3 19 2010 39 Made in the USA Notes...

Page 40: ...scharge WLC WLH High Wall Air Handler CAC CAH CAC CAH C Cassette assette Air Air H Handler andler S1CG S1HG S2CG S2HG Dual Zone UNC UNH Universal Floor or Ceiling Air Handler T2C T3C T4C and T2C T3C T...

Reviews: