S1CG/S1HG refrigerant charge table
Table 2
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
S1CG9
CAH09
.25 oz/ft
(23 g/m)
39.5
S1HG9
WLH09/UNH09
.25 oz/ft
(23 g/m)
51.3
S1CG2
CAH12
.25 oz/ft
(23 g/m)
33.75
S1HG2
WLH12/UNH12
.25 oz/ft
(23 g/m)
45.75
S1CG8 CAH24
.64 oz/ft
(59 g/m)
65.25
S1HG8
WLH24/UNH24
.64 oz/ft
(59 g/m)
63.0
S1CG4
CAH24
.64 oz/ft
(59 g/m)
63.0
S1HG4
WLH24/UNH24
.64 oz/ft
(59 g/m)
74.0
S1CG3
CAC36
.64 oz/ft
(59 g/m)
97.5
S1HG9
CAH09
.25 oz/ft
(23 g/m)
51.3
S1CG6
CAC36
.64 oz/ft
(59 g/m)
80.0
S1HG2
CAH12
.25 oz/ft
(23 g/m)
45.75
S1CG9
WLH09/UNH09
.25 oz/ft
(23 g/m)
39.5
S1HG8
CAH24
.64 oz/ft
(59 g/m)
63.0
S1CG2
WLH12/UNH12
.25 oz/ft
(23 g/m)
33.75
S1HG4
CAH24
.64 oz/ft
(59 g/m)
74.0
S1CG8
WLH24/UNH24
.64 oz/ft
(59 g/m)
65.25
S1CG4
WLH24/UNH24
.64 oz/ft
(59 g/m)
63.0
S1CG3
WLC30/UNC30
.64 oz/ft
(59 g/m)
97.5
Refrigerant Processing
(continued)
NOTICE –
to fi nd charge adjustment
To fi nd the charge adjustment and system charge for any air handler and tubing
1.
length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Line Adjustment
Round to the nearest ounce and allow for gauges and hoses.