Multi-zone Heat Pump Condensing Units

MULTI-ZONE CONDENSER SEQUENCE OF OPERATION

EMI America Series multi-zone heat pump 

condensers  are  designed  to  operate  with 

EMI  America  Series  indoor  air  handlers. 

Both  the  condenser 

(outdoor  unit)

  and 

evaporator 

(indoor  unit)

  have  a  high  Volt 

service connection. Each is to be indepen-

dently  connected  to  the  electrical  service 

panel.

 (See the unit name plate for the cor-

rect  breaker  type  and  size)

.  The  outdoor 

and indoor units are also connected to each 

other through a low Volt interconnect wiring. 

A 24V transformer located in the indoor unit 

provides the low Volt power source. 

The  S2HA  is  a  limited  range  heat  pump 

that  will  provide  comfort  cooling  or  heat 

pump operation operate at an outdoor tem-

perature  range  between  35°F  and  115°F 

for cooling, 35°F and 75°F for 

(heat pump) 

heating.  The  outdoor  unit  is  equipped 

with  a  thermostat  that  will  switch  off  the 

condenser  when  temperature  falls  below 

35°F. For heat pump mode the condenser 

operation  will  cease  and  then  switch  on 

the indoor electric heat. For cooling mode, 

condenser operation will cease.

The S2HA limited range heat pump con-

densers  are  designed  to  operate  as  a 

single  stage  cooling,  two  stage  heating 

unit. For full operation the unit should be 

matched  with  an  appropriate  EMI  indoor 

unit  with  electric  heat  and  unit  mounted 

controls or a wall mounted thermostat. 

For two stage heating operation the indoor 

unit must be equipped with an electric strip 

heater.

See the instruction manual for the indoor 

unit on the selection of the proper thermo-

stat for the system. 

Condenser Operation:

The transformer located in the indoor unit 

provides  24V,  low-Volt  control  power  to 

the condenser 

(outdoor unit)

. This can be 

measured  across  low-Volt  terminals  “R” 

and “C”.

Heat pump condensers utilize a reversing 

valve  to  provide  reverse  cycle  operation. 

Therefore  the  outdoor  unit  will  act  as  ei-

ther a condenser or an evaporator there-

by providing comfort cooling or heating to 

the  indoor  space.  The  reversing  valve  is 

energized in cooling. Should the valve fail 

to  actuate,  the  system  will  default  to  the 

heating mode of operation.

 

Cooling operation, Multi-zone Heat 

Pump:

Cooling mode operation requires that the 

control  (either  unit  mount  or  remote  wall 

mount thermostat) make a connection be-

tween low-Volt terminals “R” and “Y” along 

with “R” and “O”. When the indoor control 

is placed in cooling mode, with the set point 

temperature below the room temperature, 

the reversing valve will energize 

(R & O)

 

along with the compressor and outdoor fan 

(R & Y)

. When the indoor control is satis-

fied and the room temperature falls below 

the set temperature, the compressor and 

fan will de-energize. The EMI indoor unit 

is equipped with an anti-short cycle timer 

(ASCT)

 will prevent the compressor from 

re-starting for three minutes.

When the outdoor temperature falls below 

35°F, compressor operation will cease.

 Heating operation, Multi-zone Heat 

Pump:

Heating mode operation requires that the 

control  (either  unit  mount  or  remote  wall 

mount  thermostat)  make  a  connection 

between  low-Volt  terminals  “R”  and  “Y” 

only.  When  the  indoor  control  is  placed 

in  heating  mode,  with  the  set  point  tem-

perature  above  room  temperature,  the 

compressor and outdoor fan 

(R & Y)

 will 

energize. When the indoor control is satis-

fied and the room temperature rises above 

the set temperature, the compressor and 

fan will de-energize. The EMI indoor unit 

is equipped with an anti-short cycle timer 

(ASCT) 

will prevent the compressor from 

re-starting for three minutes.

Summary of Contents for Corp

Page 1: ...N 240006458 Rev 1 0 01 07 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company S2HA Multi...

Page 2: ......

Page 3: ...the electric supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn of...

Page 4: ...per Copper coils Wind Baf es Louvers INSTALLER SUPPLIED ITEMS Power wiring Low Volt wiring 18 AWG minimum Secure mounting pad or foundation Refrigerant piping if not supplied Disconnect switch SITE PR...

Page 5: ...side screws and remove Side discharge unit allows for permanent mounting through the feet This is highly recommended due to the vertical design of the unit UNIT MOUNTING SECTION 5 Insert lag bolts thr...

Page 6: ...thin 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief tting 7 Run wires to the hig...

Page 7: ...at least 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel 11 Faste...

Page 8: ...fway mark of the suction riser For example if the suc tion riser is 30 feet tall then a P trap is recom mended at the 15 foot mark of the suction riser see Figure 1 A P trap may be fabri cated using 2...

Page 9: ...e valves by wrapping with a wet rag heat sink before brazing 1 Clean the ends of tubing and insert into ttings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap...

Page 10: ...ass for sweat connections IMPORTANT All systems require eld charge adjustments Refer to the Refrig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper sys...

Page 11: ...be correct for every application To assure the best perfor mancefromtheair conditioner therefrigerant charge should be checked and adjusted if need be on each installation For proper superheat readin...

Page 12: ...p Condensing Units FIELD CHARGING Cooling Cycle S2HA 9 000 Btuh circuit with EMI s WLHA09 or CAHA12 Note Minimum compressor superheat 5 F Cooling Cycle S2HA 12 000 Btuh circuit with EMI s WLHA09 or CA...

Page 13: ...www enviromaster com 13 Multi zone Heat Pump Condensing Units FIELD CHARGING Heat Cycle S2HA 9 000 Btuh circuit with EMI WLHA09 or CAHB12 Heat Cycle S2HA 12 000 Btuh circuit with EMI WLHA12 or CAHB12...

Page 14: ...ure lines occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gaug...

Page 15: ...ci c to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evapo...

Page 16: ...provides 24V low Volt control power to the condenser outdoor unit This can be measured across low Volt terminals R and C Heat pump condensers utilize a reversing valve to provide reverse cycle operat...

Page 17: ...ill be described in the manual pertainingtotheindoorsection TheS2HAwill cease compressor operation at 35 F outdoor temperature If in heating mode the electric heat will take over when the compressor c...

Page 18: ...230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compressor...

Page 19: ...600 13 0 80 12 2 16 000 3 3 2200 WLHA12 WLHA12 22 600 13 0 72 11 9 20 400 3 3 9200 WLHA09 WLHA12 20 600 13 0 76 12 0 18 200 3 3 S2HA CAHB SYSTEM PERFORMANCE MODEL COOLING HEATING S2HA Outdoor Indoor U...

Page 20: ...Phone 1 800 228 9364 Fax 1 800 232 9364 5780 Success Drive Rome NY 13440...

Reviews: