background image

23

www.enviromaster.com

The Ductless Split System of Choice

When trouble-shooting the indoor unit, please refer to

the wiring diagram that is supplied with the equipment. It is
located either on the back of the removable return air grill
(CNR and WHP/WCP) or on the back of the access panel
(CHP/CCP and FHP/FCP). If you are unable to locate the
wiring diagram please feel free to call the factory technical
service line at (800) 228-9364 and one can be faxed or
mailed. Please have the full model and serial number avail-
able prior to calling.

EMI 

AmericaSeries

 evaporators are designed to oper-

ate with EMI 

AmericaSeries 

condensers. The evaporator

(indoor unit) and condenser (outdoor unit) are to be inde-
pendently connected to the electrical service panel on sepa-
rate breakers. (See the unit name plate for the correct breaker
type and size). The indoor and outdoor units are also con-
nected to each other via a 24V interconnect wiring. 

A trans-

former typically located in the condensing unit

 provides

the low volt power source for the controls. The number of
low volt interconnect conductors will be three to five de-
pending on heating options. Cooling only and cooling with
electric heat units have three low volt wires. Heat pumps
with electric heat require five low volt interconnect conduc-
tors. Interconnect wire should be at least 18awg. Refer to
the unit wiring diagram for the interconnect diagram that
matches your system.

MAINTENANCE AND TROUBLESHOOTING PROCEDURE

for EMI Air Handlers with Unit Mount Infrared Controls

POWER SUPPLY CHECK

When trouble shooting any EMI product, it is important

to first check the rating plate for proper field voltage and
breaker size. Secondly using a volt meter check the incom-
ing power supply to see that it agrees with the rating plate.
The incoming power should not exceed the nameplate volt-
age. Also the incoming power should not be below the mini-
mum voltage stated on the rating plate (197V for units rated
208/230V and 104V for units rated 115V.

A check for low voltage power should also be made. By

placing a voltmeter across low volt terminals “R” and “C” at
the condenser there should be a reading of 24V.

After checking the condenser, a low voltage check to

the indoor unit can also be made. By placing a meter across
the red and brown low volt wires of the indoor unit there
should also be a reading of 24V.

TEST MODE

Use of the test mode feature can aid in the functional

check of the unit. It can also be a helpful tool when trouble-
shooting to help isolate a problem source.

While in test mode, all timers are eliminated. Avoid
short cycling the compressor. After system checks are
complete, the control must be returned to normal op-
eration. DO NOT LEAVE THE SYSTEM IN TEST
MODE!

To enter test mode the unit must first be in the 

off state.

Next, using the unit mounted keypad depress both the 

up

and 

down

 arrow buttons simultaneously and push the 

On/

Off 

 button in for one second. The unit is now in test mode.

System function checks can now be made without having
to wait for timer delays. To return to normal operation, switch
the unit off again via the 

On/Off

  button for at least 30 sec-

onds. When the system is switched back on, normal op-
eration will resume.

!

!

CAUTION

MAINTENANCE

Service should be performed by a 

qualified

 service

agency and an annual system check is recommended.  EMI
units are designed and constructed for reliability and long
life with minimal maintenance.  You can insure peak oper-
ating efficiency by:

1. Cleaning air filters on a monthly basis: The filter is

accessed by removing the air intake access panel.
Clean with a vacuum cleaner that has a brush at-
tachment or use a garden hose.  Allowing dust to
collect on the filter will cause the unit to lose effi-
ciency and eventually malfunction.

2. Vacuuming dust from the return air grille and coil sur-

face when cleaning the filter.

TROUBLESHOOTING

Summary of Contents for CCP/CHP

Page 1: ...review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it func tions properly To obtain technical service or warranty assis tance duri...

Page 2: ...floor wall or ceiling units and two pipe chilled water fan coil model The air handler offers ease of installation operation and service and can be matched with EMI s SCC SHC single zone condensing uni...

Page 3: ...dard on FHP FCP WHP WCP and CNR optional on CCP CHP backlit LCD display Adjustable operational range from 55 F to 95 F in one degree increments Anti short cycle compressor protection Minimum compresso...

Page 4: ...ter lines to ensure they are not in con tact with each other The unit s must be mounted securely and level EMI indoor units do not contain a low volt trans former Low volt power is supplied by a trans...

Page 5: ...otate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible Figure 5 START UP See the Common section of this manual pages 2 8 f...

Page 6: ...e is satisfied and the two minute minimum run time has elapsed the compressor will cycle off The fan will operate as described in Fan Opera tion Figure 5 NOTE Once the compressor is switched off there...

Page 7: ...denser and energize the indoor heat This is designed to protect the compressor under certain outdoor conditions Next place the setpoint temperature at least two de grees above room temperature The el...

Page 8: ...the indoor unit is not equipped with electric or hydronic heat then a single stage heat pump thermostat is adequate FAN OPERATION Some thermostats are equipped with an auto on fan switch When this swi...

Page 9: ...or fan will switch off after the sixty second purge time has elapsed COMMON TO ALL AIR HANDLERS Continued Units with an optional hydronic heat coil or chilled wa ter coil are also equipped with a free...

Page 10: ...installed NOTE The FHP utilizes a molded plastic top DO NOT sit or stand on it as you may damage the unit 1 Check equipment for damage before mounting 2 Determine the best location for mounting the un...

Page 11: ...nd dampers are field supplied The back side has a 4 knockout for a fresh air duct Block the opening during installation to prevent foreign objects from getting into the unit The duct should be install...

Page 12: ...p units are equipped with a standard air bleeder on the highest point on the unit piping CAUTION Disconnect power when bleeding system Make certain liquid does not contact any electrical com ponents F...

Page 13: ...8 5 8 I D 30 3 8 5 8 I D 36 42 48 3 8 7 8 5 8 I D Model Drain Hose Refrigerant Line Size FHP Shipping Wt Model LBS 9 12 15 110 18 24 30 120 36 42 48 165 FCP FHP Fresh Air Specifications Model Total CF...

Page 14: ...ptional mounting o o o o FHP 36 48 FHP 36 48 Motorized Damper and Power Assisted Fresh Air 4 Fan Type Wall Box Dimensions 14 from finished floor level x 32 wide x 8 deep FHP 09 30 Motorized Damper and...

Page 15: ...e the cardboard template provided with unit packing to test fit the unit before installation 1 The CCP CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Us...

Page 16: ...i s n e S y t i c a p a C d i u l F p m e T d i u l F w o l F i s P D P 2 1 9 0 P C C 0 0 9 7 0 0 9 0 1 0 0 3 3 1 0 0 3 7 0 0 8 8 0 0 8 9 5 4 5 4 5 4 0 1 0 2 0 3 0 3 3 5 8 8 0 0 0 9 0 0 7 2 1 0 0 6 5...

Page 17: ...backing between the unit and the block surface to absorb any potential vibration IMPORTANT If excessive noise or vibration is ex perienced from a unit mounted directly to a block wall the squareness...

Page 18: ...gh one of two 7 8 knockout holes A terminal block marked with L1 and L2 and a ground lug are provided 2 Low voltage wiring EMI requires 18 awg low voltage interconnect wiring must be run to the outdoo...

Page 19: ...TS HZ PH ELECTRIC HEAT INDOOR FAN 1 INDOOR FAN 2 TOTAL AMPS DISCHARGE AIR SPEED AND FLOW LOW HIGH LOW HIGH LOW HIGH DRY 335 370 700 750 10 12 FPM THROW FT CFM COIL 1 4 1 2 INTERCONNECTING REFRIGERANT...

Page 20: ...r circulation Locate outdoor and indoor units as close together as possible Determine how refrigerant and power line may be run to and from unit Determine if the cabinet front can be removed with out...

Page 21: ...Wt 09 12 36 14 10 32 9 24 8 18 16 85 15 18 47 14 10 32 10 34 8 18 27 115 24 30 57 14 10 42 10 44 8 27 28 115 36 57 17 11 42 10 44 10 25 28 115 A B C D E 2 2 1 G I F H Wall Mount Bracket Slot for Brack...

Page 22: ...6 3 8 7 8 Refrigerent Line Size Chilled Line Size I D WHP Suction Connection is 3 4 O D and must be bushed down at the WHP Unit WCP WHP CONNECTIONS WHP s ONLY WCP ELECTRICAL SPECIFICATIONS FLA HP 09A...

Page 23: ...volt age Also the incoming power should not be below the mini mum voltage stated on the rating plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should al...

Page 24: ...in the control box As a safety feature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur E...

Page 25: ...at rating The following current values apply when the unit is con nected to a 230V power supply These values include in door fan motor current 7KW 31 0 AMPS 5KW 22 3 AMPS 3KW 13 5 AMPS Units with elec...

Page 26: ...ll amount of flickering of the display is normal Depending on the room lighting flickering may be more noticeable at some times than others Q How long will the fan run A While the unit is in cooling o...

Page 27: ...tor Volts ID Fan Motor Amps Total Volts Total Amps Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Evaporator DB Temp Split at evap Compressor Superheat Sub...

Page 28: ...other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequenc...

Reviews: