www.enviromaster.com
37
WLCA/WLHA High Wall Evaporator
WLC/WLH HiGH WALL EVAporAtor spECifiCAtions
disCHArGE Air spEEd And fLoW @ 230V
model
High
Cfm
Low
Cfm
Coil
fpm
throw/
ft.
09/12
400
350
Dry
900
15
18/24
750
675
Dry
1,225
25
30/36
1,100
900
Dry
1,250
27
WLC/WLH
intErConnECtinG-LinE sizE
system
Capacity
Btuh
Liquid
o.d.
suction
o.d.
Condensate
i.d.
09
1/4”
1/2”
1/2”
12
1/4”
1/2”
1/2”
18
3/8”
5/8” *
1/2”
24
3/8”
3/4”
1/2”
30
3/8”
3/4” **
1/2”
36
3/8”
3/4” **
1/2”
* WLC/WLH Suction Connection size is 3/4” O.D.
and must bush down at the WLC/WLH Unit.
** WLC Suction Connection size is 5/8” O.D. a factory
supplied kit is provided to transition to 3/4” O.D.
interconnect.
WLC/WLH ELECtriCAL spECifiCAtions
MODEL
#
VOLTS/HZ/PH
FAN
RLA
HP
HEATER
K.W.
AMPS TOTAL
AMPS
MIN
VOLT M.C.A.
HACR
BRKR
smALL CABinEt 09/12
09/12
115/60/1
0.64
0.02
–
–
0.64
104
0.8
15
115/60/1
0.64
0.02
0.75
6.50
7.14
104
8.9
15
208/230/60/1
0.34
0.02
–
–
0.34
197
0.4
15
208/230/60/1
0.34
0.02
3.00
13.04 13.38
197
16.7
20
mEdiUm CABinEt 18/24
24
115/60/1
1.20
0.083
–
–
1.20
104
1.5
15
115/60/1
1.20
0.083
0.75
6.52
7.72
104
9.7
15
115/60/1
1.20
0.083
1.25
10.90 12.10
104
15.1
20
208/230/60/1
0.56
0.070
–
–
0.56
197
0.7
15
208/230/60/1
0.56
0.070
3.00
13.04 13.60
197
17.0
20
208/230/60/1
0.56
0.070
5.00
21.74 22.30
197
27.9
30
LArGE CABinEt 30/36
30/36
208/230/60/1
0.80
1/10
–
–
0.80
197
1.0
15
208/230/60/1
0.80
1/10
5.00
21.74 22.54
197
28.2
30